background image

 Installation & Servicing Instructions Rinnai E-Series 

20

NOTICE

i

NOTICE

i

6.1.1  

Safety valve

An ASME 30 psi pressure relief valve is included with the boiler and must be 
fi tted before any shut off  valve in the system.

6.1.2  

Low water cut off 

The Rinnai E boiler has a factory installed pressure sensor type Low Water Cut 
Off  (LWCO). Check your local codes to see if a Low Water Cut Off  is required 
(LWCO) and if this device conforms to local code.  

The boiler's internal low water cut off  is not serviceable or adjustable .

6.2   

Boiler expansion tank

Choose  an  expansion  tank  volume,  of  which  is  geared  to  the  installation’s  water 
capacity.  The  pre-charge  pressure  depends  on  the  installation  height  above  the 
expansion tank. Fit the expansion tank into the return pipe as close as possible to 
the boiler return connection. The expansion tank should be sourced locally.  Please 
refer to the expansion tank manufacturer for further information.

Fill the expansion tank to a minimum of 14.5 psi.

The boiler cannot be used with an open type expansion tank.

6.3   

Underfl oor heating system (plastic pipes)

When  using  oxygen-permeable  tubing,  e.  g.  for  underfl oor  heating  systems,  the 
system must be separated using plate heat exchangers.

No recourse can be made to the terms of the limited warranty in the event of 
failure to observe the regulations pertaining to plastic underfl oor heating pipes.

6.4    

Gas supply connection

Only work on gas lines if you are licensed for such work.
If  these  instructions  are  not  followed  exactly,  a  fi re  or  explosion  may  result 
causing property damage, personal injury or death.

Rinnai wall mounted E boilers are built to run on their specifi ed gas type either 
Natural  Gas  or  Liquid  Propane  (not  for  E50CRN).  The  gas  type  the  boiler  is 
suitable for is indicated on the packaging and on the boiler by a blue label with 
Natural Gas and on the identifi cation plate on the boiler.
First check the identifi cation plate on the boiler for the suitable gas type. 

Do not use the boiler for another type of gas than indicated on the identifi cation 
plate of the boiler. This will cause improper functioning and can damage the 
boiler.

NOTICE

i

!

DANGER

!

DANGER

!

WARNING

NOTICE

i

NOTICE

i

Содержание E110CRN

Страница 1: ...manual provided with this boiler Installation and service must be performed by a licensed professional service agency or the gas supplier who must read and follow the supplied instructions before installing servicing or removing this boiler CAUTION The user manual is part of the documentation that is delivered to the installation s operator Go through the information in this manual with the owner ...

Страница 2: ...rking on heating and gas systems Subject to technical changes Changes may be made without notice to the illustrations process steps and technical data as a result of our policy of continuous improvement Updating of documentation Please contact us if you have any suggestions for improvements or corrections California Proposition 65 lists chemical substances known to the state to cause cancer birth ...

Страница 3: ...rsion from parallel to concentric vent system 30 6 7 3 2 Installing air filter 30 6 7 4 Vent air intake terminal position 31 6 7 5 Direct vent closet and alcove installation 33 6 7 6 Dimensioning of the exhaust and air intake duct 34 6 7 7 Combustion air and vent piping lengths 35 6 7 8 Calculation of compensation factor 36 6 7 9 Room Air System indoor combustion air 37 7 Electrical connections 40 ...

Страница 4: ...vere personal injury death or substantial property damage WARNING Indicates the presence of hazards that can cause severe personal injury death or substantial property damage CAUTION Indicates presence of hazards that will or can cause minor personal injury or property damage CAUTION Risk of electric shock Indicates presence of hazards due to electric shock NOTICE Indicates special instructions on...

Страница 5: ...iler must be located in an area where leakage of the boiler or connections will not result in damage to the area adjacent to the boiler or to lower floors of the structure When such locations cannot be avoided it is recommended that a suitable drain pan be installed under the boiler The boiler must be installed in such way that the all components are protected from water dripping spraying rain etc ...

Страница 6: ...ax concentration 50 Noble Noburst AL Fernox Alphi 11 Approved system cleaner Noble Noburst Hydronic System Cleaner Fernox F3 Cleaner Rhomar Hydro Solv 9100 Sentinel X400 The system cleaners from NoBurst Rhomar and Fernox are not to be used in the boiler The boiler must be closed off valved off from the rest of the system or not connected while the cleaners are in the system The system should then be...

Страница 7: ...r distribution system to ensure safe operation FOR INSTALLATIONS IN THE COMMONWEALTH OF MASSACHUSETTS NOTICE BEFORE INSTALLATION This direct vent appliance must be installed by a licensed professional If you are not properly trained you must not install this unit IMPORTANT In the State of Massachusetts 248 CMR 4 00 5 00 For all side wall horizontally vented gas fueled equipment installed in every ...

Страница 8: ...the heat exchanger to the water in the central heating system By cooling down the exhaust gases condensate is formed This results in high efficiency The condensate which has no effect on the heat exchanger and the function of the boiler is drained through a condensate collector trap The boiler is provided with an intelligent control system CMS Control Management System The boiler anticipates the heat...

Страница 9: ...ng 15mm x 3 4 NPT ext 2 2 2 Nut 15mm compression fitting 2 2 2 Concentric flue adapter Ø80 125mm 1 Plug flue gas 2 Gasket air supply Ø120 1 Cover air supply Ø80 1 Gasket vent system air supply 1 Feed through plug flue gas 1 1 Flue adapter 3 pps UL appr 1 1 Air supply adapter 3 pps UL appr 1 1 Lip ring flue pipe ø80 1 1 Wall mounting bracket HEX1 2S 1 1 1 Template 1 1 1 Installation Service Instructions...

Страница 10: ...FWV DZD IURP WKH ERLOHU DQG RU DURXQG FRPEXVWLRQ DLU LQWDNH 6SUD FDQV FRQWDLQLQJ FKORUR IOXRUFDUERQV PPRQLXP DQG RU DPPRQLXP VROXWLRQV 3HUPDQHQW ZDYH VROXWLRQV KDLU SURGXFW DXQGU HTXLSPHQW KORULQDWHG ZD HV DQG RU FOHDQHUV 6ZLPPLQJ SRRO FKHPLFDOV EDVHG RQ FKORULQH DOFLXP FKORULGH XVHG IRU WKDZLQJ 6RGLXP FKORULGH XVHG IRU ZDWHU VRIWHQLQJ 5HIULJHUDQW OHDNV 3DLQW RU YDUQLVK UHPRYHUV GURFKORULF DFLG PX...

Страница 11: ...weight with its water content Take note of the necessary space around the boiler for installation of venting system pipework and servicing See drawing on pages 12 and 13 Drill the necessary holes using the template Install the mounting bracket to the wall The boiler must be installed using the included mounting hardware Lifting and carrying precautions To avoid personal injury please follow these ...

Страница 12: ...QW HQWHU WR FHQWHU YHQW DQG DLU VXSSO DFN YHQW HIW VLGH JDV SLSH J 0 137 HIW VLGH VXSSO SLSH I 0 137 PP HIW VLGH UHWXUQ SLSH U 0 137 PP HIW VLGH FRQGHQVDWH SLSH F PP 1 HIW VLGH FROG ZDWHU SLSH N 0 137 PP 2 HIW VLGH KRW ZDWHU SLSH Z 0 137 PP 3 3LSH OHQJWK RI J 4 3LSH OHQJWK RI F 5 3LSH OHQJWK RI N DQG Z 6 3LSH OHQJWK RI I DQG U 7 DFN HQWHU RI SLSH F N DQG Z 8 DFN HQWHU RI SLSH I J DQG U 5 PP RPEL 9...

Страница 13: ...24 600 5 3 1 Clearances from boiler Minimum required clearances to combustibles Minimum required clearances to non combustibles Required service clearances All types All types All types inch mm inch mm inch mm Top of boiler 0 0 10 250 Back of boiler 0 0 0 Front of boiler 1 25 1 25 24 600 Left side of boiler 0 0 2 50 Right side of boiler 0 0 2 50 Floor Ground to bottom of boiler 0 0 10 250 30 762 i...

Страница 14: ...KW HPSW OEV NJ DWHU FRQWHQW JDOORQ OLWHU DWHU FRQWHQW JDOORQ OLWHU IWHU UXQ WLPH SXPS PLQ IWHU UXQ WLPH SXPS PLQ 306 DWHU SUHVVXUH PLQ PD 36 EDU 30 DWHU SUHVVXUH PD 36 EDU 6XSSO WHPSHUDWXUH PD 3XPS W SH 83 5 83 5 83 5 YDLODEOH SXPS KHLJKW 36 N3D RRW RI KHDG SSURYDOV IORZ DW 7 JDOORQ PLQ IORZ DW 7 OLWHU PLQ IORZ DW 7 JDOORQ PLQ IORZ DW 7 OLWHU PLQ 0D IORZ UDWH JDOORQ PLQ OLWHU PLQ WHPSHUDWXUH 7LQ 3...

Страница 15: ...a 1 1 4 32 mm PVC sleeve See further chapter 6 6 The vent system and air supply system It consists of a twin pipe connection that will accept 80mm flue and intake air or with the use of the included adapters 3 PVC CPVC flue and intake See further chapter 6 7 The pipes to be connected to the boiler must be cleaned before connecting in order to prevent dirt from entering and damaging the boiler NOTI...

Страница 16: ...llelwiththeboilerwithappropriate valves to prevent the chilled medium from entering the boiler The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle S...

Страница 17: ...n connections on the plumbing kit V1 and V2 2 Open the bypass valve V4 3 Connect pump outlet hose H1 to the purge station BD1 and connect H2 to the inlet of the pump and place the other end in the pail 4 Connect drain hose H3 to the return side purge station BD2 5 Pour the system cleaner into a pail and follow the system cleaner instructions on circulation time and volume to be added to the system...

Страница 18: ...re NOT to be used in the boiler The boiler must be closed off valved off from the rest of the system or not connected while the cleaners are in the system The system should then be drained and then thoroughly flushed with clean water to remove all the system cleaner Approved inhibitors Rhomar Pro tek 922 Sentinel X100 Noble Noburst AL inhibitor Connect the expansion tank to the system See chapter 6 2...

Страница 19: ...d to be used on pressurized heating systems only closed loop If the boiler is to be installed in a system that utilizes zone pumps and not zone valves a low loss header plumbing kit should also be installed part number 804000061 If the pressure drop in the loop system is greater than the available head pressure from the boiler pump a low loss header plumbing kit should be used part number 80400006...

Страница 20: ... boiler cannot be used with an open type expansion tank 6 3 Underfloor heating system plastic pipes When using oxygen permeable tubing e g for underfloor heating systems the system must be separated using plate heat exchangers No recourse can be made to the terms of the limited warranty in the event of failure to observe the regulations pertaining to plastic underfloor heating pipes 6 4 Gas supply co...

Страница 21: ...uipped with external 3 4 M NPT thread Use appropriate sealing The connection to the boiler must include a suitable method of disconnection and a gas control valve must be installed adjacent to the boiler for isolation purposes The nominal inlet gas pressure measured at the boiler should be 7 W C 18 mbar for Natural gas Gas A Maximum pressure with no flow lockup or with the boiler running is 10 5 in...

Страница 22: ...ing A sediment trap must be provided upstream of the gas shut off valve The boiler pipe is equipped with external 3 4 M NPT thread Use appropriate sealing The connection to the boiler must include a suitable method of disconnection A gas shut off valve must be installed adjacent to the boiler for isolation purposes The nominal inlet working gas pressure measured at the boiler should be 11 inch W C f...

Страница 23: ...o remove the inside mechanism of the flow restrictor 6 5 1 Domestic Water quality Appropriate steps must be taken to ensure the brazed plate heat exchanger does not become plugged by scale caused by hard water or sediment If the plate heat exchanger becomes plugged by either scaling from hard water or sediment it is not the responsibility of Rinnai Maximum Level Total Hardness Up to 200 mg L Alumin...

Страница 24: ...ilers on the domestic hot water side to prevent scalding This valve will regulate the water temperature leaving the brazed plate heat exchanger See the figure 11 for the suggested piping DHW piping with thermostatic mixing valve fig 11 Hot water can be dangerous especially for infants or children the elderly or infirm There is hot water scald potential if the thermostat is set too high Water temper...

Страница 25: ...ust be manually operated once a year to check for correct operation The relief valve should be added to the hot water outlet line according to the manufacturer instructions DO NOT place any other type valve or shut off device between the relief valve and the combi boiler Do not plug the relief valve and do not install any reducing fittings or other restrictions in the relief line The relief line sho...

Страница 26: ... connection should have a minimum diameter of 1 25 32mm Install the condensation drain pipe according to applicable local code If the condensate outlet of the boiler is lower than the public sewage system a condensate pump must be used The condensate produced by the boiler has a pH value between 3 and 4 Install a neutralization unit if required by local code It is recommended but not required to i...

Страница 27: ...2 see table 9 The boiler is unsuitable to install on a common vent installation see also chapter 18 Do not connect the venting system with an existing vent or chimney Do not common vent with the vent pipe of any other boiler or appliance Vent connections must be firmly pressed together so that the gaskets form an air tight seal Refer to the instructions of the vent system manufacturer for component...

Страница 28: ...ntric termination figure 12A Horizontal with parallel termination figure 12B Examples sealed combustions Vertical with parallel termination figure 12E Wall thickness for vent termination installation Minimum 100mm 4 Maximum 508mm 20 10 MINIMUM INSIDE EDGE T O INSIDE EDGE 12 OVER MAXIMUM SNOW LEVEL OR 24 WHICHEVER IS GREATER 6 7 2a Examples vent and air supply systems parallel ...

Страница 29: ...oof terminal and bends figure 13D Short termination with wall terminal figure 13A Termination with wall terminal on higher level figure 13B Examples roof terminals Examples wall terminals Wall thickness for vent termination installation Minimum 100mm 4 Maximum 508mm 20 6 7 2b Examples vent and air supply systems concentric ...

Страница 30: ...Examples vent and air supply systems PP Twin Pipe and Flex Vertical twin pipe termination figure 13F Horizontal twin pipe elbow termination figure 13G Horizontal twin pipe concentric termination figure 13H Horizontal twin pipe elbow termination below grade figure 13J ...

Страница 31: ...Installation Servicing Instructions Rinnai E Series 31 Flex through chimney termination figure 13K Flex through B vent as a chase termination figure 13L ...

Страница 32: ...ngers supports and restraints which are able to withstand all static and dynamic loading conditions which act upon the vent piping system and the associated Rinnai boiler Hangers supports and restraints shall be 100 corrosion proof UV resistant and impact resistant Exhaust vent pipe MUST be securely fastened to the structure to avoid movement The first hanger support MUST be located directly after ...

Страница 33: ... to which the concentric ventingandairsupplysystemcanbefitted withorwithoutelbowpieces Themaximum permissible pipe length is set out in table 9 chapter 6 7 6 The E50CRN boiler is provided standard initially with a parallel connection but can be converted to a concentric system with with an optional adapter Part nr 808000023 Room Air System indoor combustion air The boiler can use room air for combu...

Страница 34: ...sket 3 A Push the 2 clips of both 3 connections slightly inwards B Pull both 3 connections out of the boiler C Connect the concentric vent adapter Check if all rubber seals 2 3 5 and 6 are positioned on the concentric vent adapter Push the concentric vent adapter in the boiler in the boiler exhaust pipe until CLICK Press the 3 cover 1 in the connection at the back until CLICK OK C A B 1 2 3 4 6 5 ...

Страница 35: ...ack of the boiler 5 Pull the rubber seal around the bottom of the exhaust connector 6 Push the exhaust connector in the boiler in the boiler exhaust pipe until CLICK 7 Push the rubber plug in open position in the O2 measuring opening and close the stop D Connect the parallel vent system 6 7 3 3 Installing air filter 1 Pull the 3 connections out of air intake of the boiler 2 Push the air filter into ...

Страница 36: ... 10 000 Btuh 3 kW 9 inches 30 cm for appliances 10 000 Btuh 3 kW and 50 000 Btuh 30 kW 12 inches 91 cm for appliances 50 000 Btuh 30 kW 4 feet 1 2 m below or to side of opening 1 foot 300 mm above opening C Clearance to permanently closed window D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet 61 cm from the center line of the terminal E Cle...

Страница 37: ...densation may also accumulate on the outside of the air inlet pipe Such conditions must be considered and where necessary insulation of the inlet pipe may be required In cold and or humid weather water vapor may condense on leaving the vent terminal The effect of such water condensation must be considered The terminal must be located in a place not likely to cause a nuisance Cellular or Foam core P...

Страница 38: ...ir applications see sections 6 7 5 and 6 7 8 12 300 mm minimum 12 300 mm minimum 12 300 mm minimum INTAKE EXHAUST 12 300 mm minimum 12 300 mm minimum Terminal positions PVC figure 16 WARNING 15 386mm 6 148mm 11 268mm Closed door 1 25 4mm 10 254mm 1 25mm minimum clearance around vent pipes 2 50mm 2 50mm 1 25mm minimum clearance around hot water pipes 8 200mm 8 200mm Closet installation figure 17 10 ...

Страница 39: ...jury death or substantial property damage Installation must comply with local requirements and with the National Fuel Gas Code ANSI Z223 1 For closet and alcove installation CPVC material instead of PVC must be used in a closet alcove structure Failure to follow this warning could result in fire personal injury or death All vent pipes must be connected and properly supported and the exhaust must be...

Страница 40: ...dd 5 ft Total Multiply with factor Equivalent length Combustion air ft ft ft ft ft 0 5 ft Vent ft ft ft ft ft 0 5 ft ft Total equivalent length Concentric system Length concentric tube boiler to roof horizontal Number of elbows 90 x 6 Number of elbows 45 x 3 Concentric terminal Add 2 ft Total Multiply with factor Total equivalent length ft ft ft ft ft 1 0 ft 0D LPXP TXLYDOHQW HQJWK LPHQVLRQ LQ HHW...

Страница 41: ...that the units are commisioned properly Not involving of Rinnai s Engineering group would result in no support of the product and no warranty 3 Calculate the Compensation Factor Total CF T CF T CF V CF A The result is the setting for Parameter 73 Change parameter 73 according to this result See Chapter 10 1 how to change parameters Example of calculation E50CRN Eq lenth vent system taken from prev...

Страница 42: ...ay and can become toxic when used as combustion air in gas appliances Such chemicals can be found in but not limited to bleach ammonia cat litter aerosol sprays cleaning solvents varnish paint and air fresheners Do not store these products or similar products in the vicinity of this boiler Unconfined Space An unconfined space is defined in NFPA 54 as a space whose volume is not less than 50 cubic fee...

Страница 43: ...illustrated in figure 17 consideration must be taken for the design of the louvers or grills to maintain the required free area required for all gas utilizing equipment in the space If the free area of the louver or grill design is not available assume wood louvers will have 25 free area and metal louvers or grills will have 75 free area Under no circumstance should the louver grill or screen have ...

Страница 44: ...n communicating directly with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 in2 2000 Btu hr 1100 mm2 kW of total input rating of all appliances in the confined space Note If ducts are used the cross sectional area of the duct must be greater than or equal to the required free area of the openings to which they are connected When communicating indirectly with...

Страница 45: ...trol Tower Use a step drill bit to create a knockout in the grey plastic cover of the boiler for a strain relief Connect a power supply cable to the cable harness terminal strip that connects to both the power switch on the front of the Control Tower and the terminal strip with positions 1 2 and 3 on the inside of the Control Tower The boiler must be electrically grounded in accordance with local ...

Страница 46: ...RS100 it is suggested that a jumper be placed on terminals 22 and 23 so that in the event the control is damaged the boiler will still fire based on outdoor reset A jumper should also be used when commissioning or trouble shooting the boiler Power stealing thermostats cannot be connected to terminals 22 and 23 NOTICE i NOTICE i Connection terminal E Series CAUTION Terminals 4 to 11 are for Rinnai u...

Страница 47: ... supply Cylinder connection 8U 35 60 00 Outside sensor Bus Controller 24 V 100 mA 1 2 3 4 5 6 7 8 9 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L N L N L N L CH DHW N A B DHW sensor three way valve Room therm On Off External safety contact Label all wires prior to diconnection when servicing or replacing controls Wiring errors can cause improper and dangerous operation CAUTION ...

Страница 48: ...Installation Servicing Instructions Rinnai E Series 48 electrical ladder diagram fi gure 23a ...

Страница 49: ...en the system has been filled the automatic de aeration program starts when a program has been selected by pressing the button for Central Heating DHW or pump program of The program takes 17 minutes and stops automatically After this the unit will function normally See also Filling and de aerate the boiler and installation chapter 9 On a call for heating or hot water the control system will select ...

Страница 50: ...t is required to be installed 6 Mode button After briefly pressing a selection of the data chapters can be retrieved After pressing for 5 seconds it is possible to enter the code as described in chapter 11 3 7 Step button After briefly pressing the water pressure can be retrieved and pages per chapter can be retrieved After pressing for 5 seconds it switches from the Good state to technical read o...

Страница 51: ...ments of the water system Before filling the heating system the complete system including all zones must be thoroughly cleaned and flushed to remove sediment Flush until clean water runs free of sediment Rinnai suggests using an approved system cleaner to flush the system but not the boiler Always use Rinnai approved antifreezes See the list at the end of this chapter Never use reverse osmosis deioni...

Страница 52: ... Noburst AL Fernox Alphi 11 Approved system cleaner Noble Noburst Hydronic System Cleaner Fernox F3 Cleaner Rhomar Hydro Solv 9100 Sentinel X400 The system cleaners from NoBurst Rhomar and Fernox are not to be used in the boiler The boiler must be closed off valved off from the rest of the system or not connected while the cleaners are in the system The system should then be drained and then thoroug...

Страница 53: ... reduce during this period and therefore topping off with water will have to be done During normal use the following messages can occur with the necessary follow up NOTICE i Water pressure is too low 12 PSI flashing FILL will alternate with indication of water pressure boiler power of 50 is possible The installation needs to be topped off Water pressure is too high 42 PSI if HIGH indication remains c...

Страница 54: ...Do not use this appliance if any parts have been under water Immediately call a licensed professional to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above this label 2 Turn off al electrical power of the appliance 3 Set the thermostat or other operating control to the lo...

Страница 55: ...tton until the code C123 is shown Press the STORE button to confirm the code code blinks1 x Now you have acces to the installer level There are 4 chapters Parameters Information chapter no adjustments possible Service chapter Error chapter no adjustments possible The content of the chapters is described on the following pages Press briefly the MODE button to select one of the 4 chapters i e PARA Pre...

Страница 56: ...urve graph 4 32 F 10 0 F fine adjustment heating curve day temperature 8 to 10 F 11 0 F fine adjustment heating curve night temperature 8 to 10 F 14 10 F min gradient speed F min 0 28 F min 15 00 Booster after night decrease no 00 yes 01 23 4 F Frost Temperature 4 to 50 F 27 100 F Minimum T set CH 0 158 F 36 E50CR 00 Type of three way valve and DHW capability E75CR 20 VC 2010 VC 8010 x0 E110CR 20 ...

Страница 57: ...ta in this table can be requested by the RS100 Most of the adjustments which are stated in this table are unnecessary when in combination with the Rinnai RS100 thermostat and will be taken care of by the RS100 itself and do not have to be adjusted For further information regarding to the RS100 thermostat refer to the Rinnai RS100 installation manual Parameter Info Service and Error chapters Table ...

Страница 58: ... button chapter PARA Press the STORE button The word Copy will appear and the factory settings are active again 11 Isolating the boiler Some situations require turning the entire boiler off By switching off the three buttons with the LED s for central heating hot water and pump program or the boiler is switched off Do not shut off the power of the boiler which means the circulation pump and the three ...

Страница 59: ... boiler settings such as burner pressure and adjustment of the air quantity are unnecessary in most cases due to the fact that the boiler operates with a zero pressure control This means the correct gas quantity is controlled by the suction operation of the fan The fine adjustment of the zero pressure which is carried out at the factory is once only which means that adjusting of this value is unnec...

Страница 60: ...llowed on the input of the gas burner fitting is 14 inch W C 35mbar 12 2 Testing the Ignition Safety shut off device Switch off system using the Central Heating button and the DHW button Disconnect the plug and socket connection of the ionization cable Switch on the sytem using the Central Heating button and the DHW button Press the MODE button for 5 seconds The display will show COdE followed by an ...

Страница 61: ...llowed by an arbitrary number Select by means of the or the button the code C123 Press the Store button to confirm the code code blinks 1 x Press the MODE button until SERV is shown Press the STEP button once until 1 is shown alternately 1 and OFF will be shown Calibrate the O2 meter Place the probe of the O2 meter into the check point see fig 27 Press the button until the maximum value in kW is ach...

Страница 62: ...e measuring range shown below The O2 value at low load must lie higher than the O2 value at full load The measuring procedure must be carried out until a constant measuring result is achieved Please take up contact with Rinnai if the values should lie outside of the applicable tolerances Switching off Press the button until is shown keep button pressed With this the procedure has ended Choose the r...

Страница 63: ...e means less O2 After this setting has been made once more test the O2 value at full load and low load See Step 1 and 2 Replace the black cover on the gas valve and secure it with the screw For high altitude installations elevations between 2000 ft and 4500 ft 600 m and 1350 m in Canadian area it is required to fill out the High Altitude Label Place the filled out High Altitude Label on the controll...

Страница 64: ...until SERV is shown Press the STEP button once until 1 is shown alternately 1 and OFF will be shown Press the button until the maximum value in kW is achieved The boiler will burn on full load value on display in kW value in BTU hr x3415 Measure the ionization When the boiler is in full load the ionization current must be 4 μA and write down this value in the log book Press the button until OFF is...

Страница 65: ...hours and full maintenance every 4 years or 8000 hours of operation whichever occurs first When doing this the circumstances of the boiler s location must be taken into account From this one can determine whether to deviate from this advice Please contact Rinnai for further guidance on the frequency and service requirements Contact details can be found on the back page of this manual 13 2 Inspectio...

Страница 66: ...test of the heating system See chapter 9 2 Filling the heating system 13 2 6 Checking venting systems Check the following points Is the prescribed combustion air flue system used Have the instructions for configuring the flue system as specified in the relevant Installation instruction for the flue gas system been observed Check air intake and or air filter and flue gas for obstruction pollution or damag...

Страница 67: ...moved from the hood and the venturi Clean the fan with a soft brush and a vacuum cleaner Replace the gasket and ensure that all gaskets of the fan parts are mounted correctly Heat exchanger every 4 year maintenance Check the heat exchanger for contamination Clean this if necessary with a soft brush and a vacuum cleaner Prevent debris from falling down into the heat exchanger Flushing the heat exch...

Страница 68: ...hat all gaskets seals completely Make sure that during refitting the clamping rods they are put in the right position They should be turned vertical If the boiler should activate with clamping rods in the wrong position it will cause property damage personal injury or loss of life Put the boiler into operation and check the O2 see chapter 13 3 If replacement of new gaskets and burner mentioned in t...

Страница 69: ...culate through the brazed plate heat exchanger for at least 45 minutes 9 Turn off the pump CP 10 Rinse the cleaning solution from the brazed plate heat exchanger as follows a Remove the free end of the drain hose H3 from the pail b Close service valve V2 and open shutoff valve V4 Do not open shutoff valve V3 c Disconnect both H1 and H3 from the service valves d Connect H3 to V1 and place the end of t...

Страница 70: ...g combustion analyzer Verify proper operation after servicing Always reset the service interval counter after full maintenance interval every 4 years or 8000 hours of operation 13 3 1 Reset service interval counter At 8000 hours of use SERVICE will scroll across the display Good will display as well alternatively To reset the 8000 hour service notification Enter the 1st Tier Settings 123 Code Briefl...

Страница 71: ...ater filter return CH 12 three way valve 13 circulation pump 14 exhaust 15 combustion air supply 16 CSA Data Plate serial number T1 supply sensor T2 return sensor T3 sensor DHW Rinnai E Series figure 41 17 ASME NB CRN data plate P1 water pressure sensor 14 Parts of the boiler G gas pipe A supply central heating R return central heating C condensate pipe K cold water pipe W hot water pipe 4 2 1 3 15 ...

Страница 72: ... Block 67 A T has been detected between flow and return sensor whereas the burner is not in operation After the T has disappeared the block will clear Block 85 The control has not detected a water flow The venting cycle is started If during this cycle water flow is detected the venting cycle is ended and the burner is released Error with a number in the last two positions Error 00 Poor flame forming E...

Страница 73: ...fter the average T has disappeared the block will disappear Check the supply and return sensor for the resistance value and replace the defective sensor Check the installation for any external heat source and rectify this flue sensor temperature too high Check vent system flue sensor or thermostat contact open Call Rinnai flue sensor or thermostat contact closed Call Rinnai flue gas thermostat contact...

Страница 74: ...en there is power to the gas valve that the gas valve opens The minimum gas pre pressure during the start must be a minimum of 7 W C 17 mbar check the 24 Volts in the gas during ignition block s open position 2 There is a temperature difference between supply 3 and return 4 Boiler has gone out after ignition Due to insufficient ionization the burner has gone out after ignition Ionization flow ionizati...

Страница 75: ...flow sensor failure controller failure Check the data in Error mode Boiler data during error 1 Error 14 2 Operational status 00 3 Flow temp 22 4 Return temp xx 5 kW burner 00 6 pomp xx variable values x3415 BTU hr A temperature of 36 is displayed at position 3 Check the wiring and or measure the resistance of the flow sensor The resistance should be approx 12 kOhm at 77 F See table in Appendix B If ...

Страница 76: ...the sensor The wiring is OK but the error is repeated Remove the plug from the flow sensor as a result of which Error 36 occurs Replace the sensor Shut down of return sensor T2 Check the data in Error mode Boiler data during error 1 Error 32 2 Operational status 00 3 Flow temp xx 4 Return temp 230 5 kW burner 00 6 pomp xx variable values x3415 BTU hr Check the wiring check the wiring for the sensor...

Страница 77: ...program into the new control unit Control unit error Software error control unit Replace the control unit Remove the E Prom from the defective control unit and place it onto the new control unit The controller will automatically load the program into the new control unit Electrical leakage to ground Moisture on controller PCB Check if there is water leaking on or in the boiler Stop water leak and ...

Страница 78: ...l heating installation gets hot without being requested 1 Key pump program is on Switch off 2 Dirt in three port valve or three port valve cartridge is binding Clean or replace Insufficient quantity of hot water 1 Hot and cold water connection to the boiler mixed up Check left hot right cold 2 Incorrect flow reducing valve Check for the type and for contamination if necessary replace Combi and or clea...

Страница 79: ...Installation Servicing Instructions Rinnai E Series 79 ...

Страница 80: ...or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do NOT try to light any appliance Do NOT touch any electrical switch Do NOT use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the g...

Страница 81: ...X X 77 S4323310 COVER AIR SUPPLY Ø80mm 807000075 X X X X X 78 AA1CA05U CONCENTRIC FLUE ADAPTOR 80 125 MM 808000023 X X X X X 80 S4323510 GASKET AIR INTAKE ø80 SHR 809000047 X X X X X 81 S4857200 FLUE GAS CONNECTOR 3 808000030 X X X X X 82 S4857100 AIR INTAKE CONNECTOR 3 808000031 X X X X X 83 S4662600 FLUE GAS PIPE OSS1 808000032 X X X S4662700 FLUE GAS PIPE OSS2 3 4 808000033 X X 84 S4521600 PLUG...

Страница 82: ...Installation Servicing Instructions Rinnai E Series 82 Parts heat exchanger E Series 30 31 64 32 33 34 35 36 40 41 52 54 83 60 61 62 55 53 37 46 51 43 44 39 45 47 59 63 49 38 56 ...

Страница 83: ...X S4778700 HEAT EXCHANGER OSS2 ASME 807000020 X X S4278100 BOILER TOOL KIT 809000024 X X X X X 44 S4709500 GASKET CONDENSATE TRAY OSS1 809000025 X X X S4714900 GASKET CONDENSATE TRAY OSS2 809000026 X X 45 S4380600 CAP DE AERATOR SHR 3 PER PACKAGE 807000023 X X X X X 46 S4419110 DE AERATOR CHROME 807000024 X X X X X 47 S4342300 O RING ø13 94X2 62 DE AER 2 PER PACKAGE 809000028 X X X X X 51 S4709100...

Страница 84: ...tions Rinnai E Series 84 95 94 105 106 107 131 108 106a 109 111 117 137 118 119 119a 119b 121 138 123 124 125 126 127 128 93 92 129 130 122 104 103 101 100 102 97 91 308 304 99 96 98 112 113 94a 108 146 139 96a Parts pipes E Series ...

Страница 85: ...SATE COLLECTOR 809000081 X X X X X 111 S4421200 TRAP E SERIES 809000100 X X X X X 112 S4309900 O RING ø40X3 53 TRAP TRAY 809000084 X X X X X 113 S4443200 O RING ø18 72X2 62 EPDM 3 PER PACKAGE 809000052 X X X X X 117 S4401600 PIPE ø15 HOT WATER 807000053 X X X X X 118 S4440000 BOLT M 5X12 IMBUS VERZ 3 PER PACKAGE 809000045 X X X X X 119 S4462400 PLATE EXCHANGER 24KW PF ESHR 807000054 X X X S4722600...

Страница 86: ...ions Rinnai E Series 86 Parts electrical components E Series 162 T1 supply sensor 160 T2 return sensor 167 T3 DHW sensor 166 T5 flue gas sensor 168 HLS high limit switch 161 P1 water pressure sensor 166 167 168 146 162 160 161 168 170 ...

Страница 87: ...47 S4883800 PUMP UPER 20 58 120V 807000126 X X X S4883900 PUMP UPER 20 78 120V 807000127 X X 160 S4309700 NTC T2 T3 805000032 X X X X X 161 S4466300 WATERPRESSURE SENSOR 805000034 X X X X X S4435400 WATER PRESSURE SENSOR CABLE 805000050 X X X X X 162 S4307420 NTC T1 T3 805000035 X X X X X 163 S4710100 IGNITION ELECTRODE GASKET OSS 805000036 X X X X X S4323800 IGNITION CABLE SHR 805000037 X X X X X...

Страница 88: ... HQJWK 6 6HDOHG RPEXVWLRQ 9HQW HQJWK 6 6HDOHG RPEXVWLRQ GMXVWDEOH 9HQW HQJWK 6 9 6HDOHG RPEXVWLRQ OERZ 6 DOO LW Z DS 66 0 5RRI LW Z FDS 66 75 0DQXIDFWXUHU 7 SH HVFULSWLRQV 3DUWV DuraVent PolyPro PP 7ZLQ 3LSH 7HUPLQDWLRQ 336 73 PP 7ZLQ 3LSH 7HUPLQDWLRQ 336 73 PP 6LQJOH 3LSH 7HUP 336 67 PP VLQJOH 3LSH 7HUPLQDWLRQ 336 67 PP RUL RQWDO 7HUPLQDWLRQ LW RQFHQWULF 336 PP RUL RQWDO 7HUPLQDWLRQ LW RQFHQWULF ...

Страница 89: ...6XSSRUW ODPS 6 6SDFHU 63 6FUHHQV 33V 89 ODFN 633 LUG 6FUHHQ 66 666 DOO 3ODWH ODFN 3 DOO 3ODWH KLWH 3 7ZLQ 3LSH WR RQFHQWULF GDSWRU 7 DVH 6XSSRUW 6 6 KLPQH RYHU 66 Z 33V 89 QG 3LSH 6 0 KLPQH RYHU 33V 89 ODFN 6 3 KLPQH RYHU 66 Z 66 QG 3LSH 6 6 OERZ 6 OERZ 6 OERZ RQJ 6 OERZ RQJ 33V 89 ODFN 6 89 OERZ RQJ 6 OERZ RQJ 33V 89 ODFN 6 89 6ZHHS OERZ 6 5 QG 3LSH 33V 89 ODFN 6 3 QG 3LSH 33V 89 ODFN 6 3 6LQJOH ...

Страница 90: ...Telephone 800 463 9572 905 403 0264 Fax 905 403 9195 www ipexamerica com Simpson Dura Vent Telephone 518 463 7284 Fax 518 463 5271 sales duravent com www protechinfo com Rinnai Ubbink Telephone 800 621 9419 Fax 678 829 1666 www rinnai us York International Telephone 405 364 4040 877 874 7378 www york com products unitary CENTROTHERM Eco System Telephone 877 434 3432 Fax 518 618 3166 info centrothe...

Страница 91: ...et Sensor Data and Resistance table NTC sensors Resistance table NTC Sensors Temp NTC 12K F 12k 77 F supply sensor T1 return sensor T2 DHW sensor T3 outside sensor T4 flue gas sensor T5 4 98 000 0 4 90 000 3 2 82 000 6 8 74 000 10 4 66 000 14 58 000 17 6 53 500 21 2 49 000 24 8 45 000 28 4 40 500 32 36 000 35 6 33 500 39 2 30 900 42 8 28 200 46 4 25 600 50 23 000 53 6 21 400 57 2 19 900 60 8 18 10...

Страница 92: ...t no 804000061 Suitable for E50CRN E75CRN E75CRP E110CRN E110CRP plumbing kit 1 figure 3 Appendix B Optional accessories Low Loss Header Clearances to combustible and non combustible is 0 inch for sides top front and floor ground The recommended service clearance to the bottom from the low loss header is 12 inches The plumbing kit is not intended to support the weight of the piping Appropriate pipin...

Страница 93: ...Clean pipe ends tho roughly The outside surface has to be smooth before fitting 1 Push the complete fitting over the pipe as far as possible Ferrule should be over the pipe completely 2 Turn the nut handtight clockwise 3 Use 2 wrenches one to hold the fitting on its place the other for tighten the nut clockwise in 3 4 turn 2 1 3 WARNING NOTICE i NOTICE i Do not overtighten these fittings when conne...

Страница 94: ...from directly below the boiler to the left side of the boiler only The kit includes all the parts required to relocate the low loss header including all mounting brackets and material This kit provides an alternative to for installations with height limitations and allows for an alternative piping installation Kit 1 for boiler models E50CR E75CR and E110CR Rinnai part number 804000071 Side mountin...

Страница 95: ...leaner Rhomar Hydro Solv 9100 Sentinel X400 The system cleaners from NoBurst Rhomar and Fernox are NOT to be used in the boiler The boiler must be closed off valved off from the rest of the system or not connected while the cleaners are in the system The system should then be drained and then thoroughly flushed with clean water to remove all the system cleaner Approved inhibitors Rhomar Pro tek 922 S...

Страница 96: ...ifi cations and dimensions without prior notice Distributor for the USA R i n n a i A m e r i c a C o r p o r a t e 1 0 3 I n t e r n a t i o n a l D r i v e P e a c h t r e e C i t y G A 3 0 2 6 9 Toll Free 800 621 9419 Tel 678 829 1700 Fax 678 829 1666 E mail info rinnai us Internet www rinnai us E O E 800000013 07 2016 ...

Отзывы: