Installation & Servicing Instructions Rinnai E-Series
68
Condensate trap and condensate tray (fi gure 35-37) (2 and 4 year maintenance)
Step 1: Condensate trap
- First remove the screw (7);
- Pull the condensation cup (8) downwards, out of the condensate tray (14)
Check this for impurities. If there is not a lot of impurities it is not necessary to
clean the condensate tray (Go to Step 3). If there is a lot of impurities in the cup
it is necessary to remove and clean the condensate tray according Step 2;
- Check the O-ring (9) of the cup and replace if necessary;
- Clean the parts by fl ushing it with clean water;
- Grease the O-ring again with acid free O-ring grease to make fi tting easier;
- If there is a leak at the condensate trap (8) replace complete condensate trap by
# 809000100;
Step 2: Condensate tray
- Remove the plug from the fl ue gas sensor if present;
- Turn the two short clamping rods (11 and 12) ¼ turn and remove them by pulling
them forward; Note the right turning direction (red indicator);
- Lift the exhaust pipe (13) out of the condensate tray (14);
- Press the condensate tray (14) carefully downwards and remove it by pulling it
forward;
- Replace the gasket between condensate tray and heat exchanger with a new one;
- Clean the condensate tray with water and a hard brush;
- Check the condensate tray for leaks.
Step 3:
Refi tting is done in reverse order.
Note that all gaskets seals completely.
Make sure that during refi tting the clamping rods they are put in the right
position. They should be turned vertical.
If the boiler should activate with clamping rods in the wrong position it will
cause property damage, personal injury or loss of life.
Put the boiler into operation and check the O
2
(see chapter 13.3).
If replacement of new gaskets and burner mentioned in this chapter is not done
within the service interval subscribed by Rinnai the boiler can be damaged and
may cause property damage, personal injury or loss of life.
Use only original spare parts supplied by Rinnai. If non approved parts are used
the boiler can be damaged and may cause property damage, personal injury or
loss of life. Use of non-Rinnai parts will result in the voiding of the limited warranty.
Do not use substitute materials. Use only parts certifi ed with the appliance.
Cleaning the Brazed Plate Heat exchanger (Every 2 year maintenance or as
needed based on water quality)
The brazed plate heat exchanger should be cleaned at the service interval every 2
years. Failure to fl ush the brazed plate heat exchanger will cause damage to it. Follow
the procedure below for cleaning the brazed plate heat exchanger.
1. Turn off the DHW function on the boiler.
2. Close the shutoff valves on both the hot water and cold water lines (V3 and V4).
3. Connect pump outlet hose (H1) to the hot water line at service valve (V1).
!
DANGER
!
DANGER
Clamping rods
fi gure 37
Condensate tray
fi gure 36
Siphon
fi gure 35
8
9
7
!
WARNING
11
12
13
14
!
WARNING