Installation & Servicing Instructions Rinnai E-Series
46
Connection terminal
fi
gure 22
NOTICE
i
The Rinnai room thermostat and controls must be connected to their allocated
connections. All other types or makes of room thermostats or controls which
are used must have a Volt free contact.
When using an on/off thermostat or control, it may be necessary to calibrate the
anticipating resistance to prevent too high temperature fl uctuations. As a standard
rule this means mercury thermostats. This resistance wire is present in the Control
Tower and must be connected to terminals 23 and 27. The anticipating resistance in
the room thermostat has to be set at 0.11 A.
For more detailed questions regarding the components which are not supplied, the
distributor should be contacted.
When wiring an RS100 it is suggested that a jumper be placed on terminals 22
and 23 so that in the event the control is damaged the boiler will still fi re based
on outdoor reset.
A jumper should also be used when commissioning or trouble shooting the
boiler.
Power stealing thermostats cannot be connected to terminals 22 and 23.
NOTICE
i
NOTICE
i
Connection terminal E-Series
CAUTION
Terminals 4 to 11 are for Rinnai use only and not for use in any installation.
!
CAUTION
120 V~
10
11
120 V~
120 V~
120 V~
Power supply
Cylinder connection
8U.35.60.00
Outside
sensor
Bus
Controller
24 V~
100 mA
1
2
3
4
5
6
7
8
9
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
N
L
N
L
N
L
N
L
CH
DHW
N
A
B
DHW
sensor
three-way valve
Room
therm.
On / Off
External
safety
contact
120 V
olts
Rinnai only
main power supply
120 V
olts
Rinnai only
120 V
olts
Rinnai only
internal or external
three-way valve motor
and
tank sensor
Bus room thermostat
RS100
On/off
thermostat or
control (V
olt free)
AR
V12 outdoor sensor
External safety contact