4 How to Use
4-5. How to wire
- 15 -
SD-2600
4-5. How to wire
<Recommended Cable>
3-wire (when the contact is not used)
CVVS1.25 mm
2
- 3-core
5-wire (when the contact is used)
CVVS1.25 mm
2
- 5-core
<Parts. length table of outside conductor lead-in>
The parts for the external cable inlet are different from specifications. Use the appropriate parts, referring
to the following lists.
ATEX/IECEx Specifications
Cable overall outer
diameter(mm)
Rubber seal inner
diameter(mm)
Washer inner
diameter(mm)
Clamp inner
diameter(mm)
From Φ9.6 to less than Φ10.5
Φ11
Φ12
Φ10.8
From Φ10.5 to less than Φ11.5
Φ12
Φ12
Φ11.8
From Φ11.5 to less than Φ12.5
Φ13
Φ14
Φ12.8
From Φ12.5 to less than Φ13.0
Φ13.5
Φ14
Φ13.8
TIIS Specifications
Cable overall outer
diameter(mm)
Rubber seal inner
diameter(mm)
Washer inner
diameter(mm)
From Φ9.6 to less than Φ11.0
Φ11
Φ12
From Φ11.0 to less than Φ11.5
Φ12
Φ12
From Φ11.5 to less than Φ12.0
Φ12
Φ14
From Φ12.0 to less than Φ13.0
Φ13
Φ14
Φ13.0
Φ13.5
Φ14
CAUTION
Be careful not to damage the internal electronic circuit when wiring. In addition, be careful not to apply
stresses on the gas monitor when (overweight) cables are installed.
The power cables and signal cables must not be installed together with the motor power cables, etc.
When these cables must be installed together for unavoidable reasons, put the power cables and
signal cables in a metal conduit. The conduit must be connected to a grounding circuit.
When stranded wires are used, prevent wires from contacting each other.
Use the dedicated handling lever to wire.