2 Important Notices on Safety
2-3. Precautions
- 6 -
2-3. Precautions
CAUTION
Do not use a transceiver near the detector.
Radio wave from a transceiver near the detector or its cables may disturb commands. If a transceiver is
used, it must be used in a place where it disturbs nothing.
To restart the detector, wait for five seconds or more before doing it.
Restarting the detector within five seconds may cause errors.
Do not use the external output of the detector to control other units.
This is not a control unit. It is not allowed to use the external output of the detector to control other units.
Do not disassemble/modify the detector, or change the settings if not necessary.
Disassembling/Modifying the detector will invalidate the warranty of the performance. Changing the
settings without understanding the specifications may cause alarm malfunctions. Please use the detector
properly in accordance with the operating manual.
Avoid applying organic solvents and others to the window plate for a long time.
The window plate material is a polycarbonate resin. When organic solvents (liquid or highly-concentrated
vapor) and others are applied to the plate for a long time, its color and shape may be changed.
Do not forget to perform a regular maintenance.
Since this is a safety unit, a regular maintenance must be performed to ensure safety. Continuing to use
the detector without performing a maintenance will compromise the sensitivity of the sensor, thus
resulting in inaccurate gas detection.