5 How to Operate
5-6. How to exit
- 27 -
<Setting Display "1-2">
Display various setting values.
5-6. How to exit
To turn off the detector, turn off the power supply (24 VDC) to the detector.
AL.:
The contact is activated
due to the gas alarm.
FAU.: The contact is activated
due to the fault alarm.
A.orF.: The contact is activated
due to the gas alarm or
the fault alarm.
WARNING
When the detector is turned off, an alarm may be activated on the upper (central) system.
Before turning off the detector, INHIBIT (point skip) on the upper (central) system must be activated.
Decide whether power can be turned off by checking the operation of the devices connected to the
external output or external contact output terminal of the detector.
If the alarm contact is energized (option), it is activated when the detector is turned "OFF".
Press SET key.
LED