7 Maintenance
7-1. Maintenance intervals and items
- 43 -
7
Maintenance
The alarm system is an important instrument for the purpose of safety.
To maintain the performance of the alarm system and improve the reliability of safety, perform a regular
maintenance.
7-1. Maintenance intervals and items
Daily maintenance: Perform maintenance before beginning to work.
Monthly maintenance: Perform maintenance on the alarm circuit (alarm test) once a month.
Regular maintenance: Perform maintenance once or more every six months to maintain the
performance as a safety unit.
Maintenance
item
Maintenance content
Daily
maintenance
Monthly
maintenance
Regular
maintenance
Power supply
check
Check that the power lamp lights up.
○
○
○
Concentration
display check
Check that the concentration display value
is zero.
When the reading is incorrect, perform zero
adjustment after ensuring that no other
gases exist around the detector head.
○
○
○
Alarm test
Inspect the alarm circuit by using the alarm
test function.
-
○
○
Span
adjustment
Perform the span adjustment by using the
calibration gas.
- -
○
<About Maintenance Services>
We provide services on regular maintenance including span adjustment, other adjustments and
maintenance.
To make the calibration gas, dedicated tools, such as a gas cylinder of the specified concentration and
gas sampling bag must be used.
Our qualified service engineers have sufficient knowledge about the dedicated tools used for services,
along with other products. To maintain the safety operation of the alarm system, please use our
maintenance service.
The followings are typical maintenance services. Please contact RIKEN KEIKI for more information.
Main services
Power supply check
: Checks the power supply voltage. Verifies that the power lamp lights
up.
(Verifies that relevant points can be identified on the system.)
(When a UPS (uninterruptible power system) is used, checks the
operation with the UPS.)
Concentration display check
: Verifies that the concentration display value is zero by using the fresh
air.
Performs zero adjustment if the reading is incorrect.