TECHNICAL SPECIFICATIONS
DESCRIPTION
SC SUN 300
Thermal power exchanged
129
kW
Maximum flow rate, primary circuit
6000
l/h
Maximum flow rate, secondary circuit
116,7
l/min
Primary circuit ΔT
20
°C
Surface area of panels
200
m
2
Minimum permissible temperature
2
°C
Maximum operating temperature
110
°C
Maximum operating pressure, primary side
10
bar
Non-return valve opening pressure, primary circuit
40
mbar
Non-return valve opening pressure, secondary circuit
40
mbar
Absorbed electric power, primary circulator (max/stand-by)
155 / 1,72
W
Absorbed electric power, second circulator (max/stand-by)
70 / 1
W
Absorbed electric power, solar controller (stand-by)
0,5
W
Energy efficiency, solar controller
1
%
Power supply voltage
230
V
Power supply frequency
50-60
Hz
Ingress protection
40
IP
Net weight
155
kg
Water volume
45
l
Heating curves - pressure drop
9
10
11
12
8
7
6
5
4
2
3
1
0
88,2
98,0
107,8
117,6
78,4
68,6
58,8
49,0
39,2
19,6
29,4
9,8
0
0
1000
2000
3000
4000
5000
6000
∆P (m H
2
O)
∆P (kPa)
Produzione ACS (l/h)
Wilo Stratos Para 30/1-12
Wilo Stratos Para 30/1-8
DP Primario
DP Secondario
DHW production (l/h)
Primary ΔP
Secondary ΔP