ELECTRICAL CONNECTIONS
- Before working on the controller, disconnect the power supply and ensure it cannot be reconnected! Check that there
is no power!
- Electrical connections must be made only by an expert service technician, and in accordance with pertinent regula-
tions and standards. Do not use the controller if there are visible signs of damage on the housing.
- Low voltage cables must be routed separately from mains voltage cables. Feed temperature sensor cables only into
the left hand side of the controller, and mains voltage cables only into the right hand side.
- The user must install a device capable of disconnecting all poles, such as a thermal magnetic breaker.
- Cables connected to the controller must be stripped by no more than 55 mm, and the cable jacket must extend into the
housing to a point just beyond the strain relief gland.
- The controller and the Vortex Flow Sensor must have the same ground potential. The VFS has a functional earth connec-
tion (PELV). The PE output of the controller must be connected to the pipe system at a point near the sensor.
Connection terminals
V2
V1
S8
S7
VFS2
1
S
F
V
C
R
SD Card
Ethernet
S6
S5
S4
S3
S2
S1
GND
R6
NC
C
NO
R5 R4 R3 R2 R1
N
L
Low voltage
Voltage-free
relay
Relay
Mains
Low voltage
b
max. 12VAC/DC
Term.
Connection for
S1
Sensor 1
S2
Sensor 2
...
S8
Sensor 8
V1 optional variable speed control output for high effi-
ciency pumps
V2 optional variable speed control output for high effi-
ciency pumps
VFS1
Grundfos Direct Sensor
VFS2
Grundfos Direct Sensor
SD Card slot
for data logging and firmware updates.
b
Make certain the SD card is fitted the right way
round! The card must be inserted without forcing!
Ethernet
for connection to Local Area Network (LAN)
Voltage-free relay
NO normally open
C common
NC normally closed
Relay
b
Current 230Vac 50-60Hz
Term.
Connection for
R1 Relay1
R2
Relay 2
...
R6
Relay 6
N neutral conductor N
L live conductor L