20010309
26
GB
Installation
Example with natural gas G20:
Operation at maximum modulating output
Gas pressure at test point P1)(Fig. 29)
= 35.2 mbar
Pressure in combustion chamber
=
5 mbar
35.2 - 5
= 30.2 mbar
A pressure of 30.2 mbar, column 1, corresponds in Tab. F to an
output of 6000 kW.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To calculate the required gas pressure at test point P1)(Fig. 29),
set the maximum modulating output required from the burner op-
eration:
–
find the nearest output value in Tab. F for the burner in ques-
tion.
–
Read, on the right (column 1), the pressure at the test point
P1) (Fig. 29).
–
Add this value to the estimated pressure in the combustion
chamber.
Example with natural gas G20:
Operation at maximum modulating output
Gas pressure at an output of 6000 kW
= 30.2 mbar
Pressure in combustion chamber
=
5 mbar
30.2 + 5
= 35.2 mbar
pressure required at test point P1)(Fig. 29).
Key (Fig. 29)
P1 Pressure test point at the combustion head
P2 Pressure test point at the gas butterfly valve
2 Manual on/off valve
12 Pilot gas supply
13 Pressure adjuster of pilot line
14 Safety valve
15 Operation valve
5.13.5 Pilot - gas train connection
The burner is fitted with a dedicated gas train that is fixed to the
pipe coupling.
It should be connected to the main train downstream the fil-
ter or the pressure adjuster (depending on configuration).
Oil burners (with LPG pilot) can be directly connected to the LPG
cylinder.
5.13.6 Ignition pilot burner
For proper operation, adjust gas pressure (measured at pressure
test point 1)(Fig. 30) as follows: 16 mbar (7.3 Nm
3
/h).
In the case of ignition problems check:
correct positioning of the ignition electrode;
the gas pressure, according to indications.
5.14
Calibration of the thermal relay
The thermal relay (Fig. 31) is used to avoid damage to the motor
owing to a strong increase in absorption or the lack of a phase.
For the calibration 2), refer to the table given in electrical layout
(Electrical connections set by installer).
To reset, in the case of an intervention of the thermal relay, press
the button “RESET” 1).
The button “STOP” 3) opens the NC (95-96) contact and stops
the motor.
To test the thermal relay, insert a screwdriver in the window
“TEST/TRIP” 4) and move it in the sense of the arrow (towards
right).
Fig. 29
20070790
WARNING
Supply pressure 68 ÷ 500 mbar.
WARNING
Check pilot flame stability before starting up the
main burner.
Fig. 30
D9266
WARNING
Automatic resetting can be dangerous.
This action is not provided for the burner op-
eration.
1
2
3
MAN
AUT
O
STOP
NO
98
97
96
95
RESET
NC
4
TEST/TRIP
Fig. 31
D8685
Содержание RLS 800/E MX
Страница 2: ......
Страница 77: ...39 20010309 Electrical panel layout Schéma tableau électrique ...
Страница 78: ...20010309 40 Electrical panel layout Schéma tableau électrique ...
Страница 80: ...20010309 42 Electrical panel layout Schéma tableau électrique ...
Страница 81: ...43 20010309 Electrical panel layout Schéma tableau électrique 0 1 1 1 ...
Страница 82: ...20010309 44 Electrical panel layout Schéma tableau électrique 0 ...
Страница 83: ...45 20010309 Electrical panel layout Schéma tableau électrique 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Страница 89: ......
Страница 90: ......