Technical description of the burner
4.13
Actuator (SQM48.4....)
Warning notes
All activities (mounting, installation and service work, etc.)
must be performed by qualified staff.
Before making any wiring changes in the connection area of
the SQM4..., completely isolate the burner control from the
mains supply (all-polar disconnection).
Ensure protection against electric shock hazard by providing
adequate protection for the connection terminals and by
securing the housing cover.
Check to ensure that wiring is in an orderly state.
Fall or shock can adversely affect the safety functions. Such
units must not be put into operation, even if they do not
exhibit any damage.
Mounting notes
•
Ensure that the relevant national safety regulations are com-
plied with.
•
The connection between actuator drive shaft and controlling
element must be rigid with no mechanical play.
•
To avoid inadmissible loads on bearings caused by rigid
hubs, it is recommended to use compensating clutches with
no mechanical play (e.g. metal bellows clutches).
Installation notes
• Always run the high-voltage ignition cables separate from the
unit and other cables while observing the greatest possible
distance.
• To ensure protection against electric shock hazard, make cer-
tain that the AC 230 V section of the SQM4... is strictly segre-
gated from the functional low-voltage section.
• The holding torque is reduced when the actuator’s power sup-
ply is switched off.
•
The housing cover may only be removed for short periods of
time for wiring or when making the addressing. It must be
made certain that dust or dirt will not get inside the actuator
while such work is carried out.
•
The actuator contains a printed circuit board with ESD-sensi-
tive components.
•
The top side of the board carries a cover which affords pro-
tection against direct contact. This protective cover must not
be removed! The underside side of the board must not be
touched.
Technical data
Tab. C
WARNING
To avoid injury to persons, damage to prop-
erty or the environment, the following warn-
ing notes should be observed!
Do not open, interfere with or modify the ac-
tuators!
WARNING
When servicing or replacing the actuators,
take care not to invert the connectors.
Operating voltage
AC 2 x 12 V via bus cable from the
basic unit or via a separate trans-
former
Safety class
extra low-voltage with safe isolation
from mains voltage
Power consumption
26...34 VA
Degree of protection
to EN 60 529, IP 54, provided ade-
quate cable entries are used
Cable connection
RAST3.5 connectors
Direction of rotation
- Standard is counterclockwise
- Reverse is clockwise
Nominal torque (max)
20 Nm
Holding torque (max)
20 Nm
Running time (min.) for
90°
30 s.
Weight
approx. 1.6 kg
Environmental conditions:
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
DIN EN 60 721-3-3
class 3K3
class 3M3
-20...+60 °C
< 95 % r.h.
Fig. 7
D8271
Содержание RLS 800/E MX
Страница 2: ......
Страница 77: ...39 20010309 Electrical panel layout Schéma tableau électrique ...
Страница 78: ...20010309 40 Electrical panel layout Schéma tableau électrique ...
Страница 80: ...20010309 42 Electrical panel layout Schéma tableau électrique ...
Страница 81: ...43 20010309 Electrical panel layout Schéma tableau électrique 0 1 1 1 ...
Страница 82: ...20010309 44 Electrical panel layout Schéma tableau électrique 0 ...
Страница 83: ...45 20010309 Electrical panel layout Schéma tableau électrique 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Страница 89: ......
Страница 90: ......