20158125
24
GB
Maintenance
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical As-
sistant and have him carry out the necessary adjustments.
Allow the burner to work for 10 min. and then check the
combustion readings with the parameters indicated within the
appliance instruction manual.
Then carry out a combustion check verifying:
– Smoke temperature at the chimney;
– Content of CO
2
(%);
– Content of CO (ppm);
– Smoke value according to opacity smokes index according to
Bacharach scale.
9.2.3
Safety components
The safety components must be replaced at the end of their life
cycle indicated in Tab. I. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment
conditions.
Tab. I
Safety component
Life cycle
Flame control
10 years or 250,000
operation cycles
Flame sensor
10 years or 250,000
operation cycles
Gas valves (solenoid)
10 years or 250,000
operation cycles
Pressure switches
10 years or 250,000
operation cycles
Pressure adjuster
15 years
Servomotor (electronic
cam) (if present)
10 years or 250,000
operation cycles
Oil valve (solenoid) (if
present)
10 years or 250,000
operation cycles
Oil regulator (if present)
10 years or 250,000
operation cycles
Oil pipes/ couplings
(metallic) (if present)
10 years
Flexible hoses (if present)
5 years or 30,000 pressurised
cycles
Fan impeller
10 years or 500,000 start-ups
Содержание RDB 3.2 BT 58/70
Страница 2: ...Original instructions...