BURNER START-UP CYCLE DIAGNOSTICS
During start-up, indication is according to the followin table:
OPERATING FAULT DIAGNOSTICS
The control box has a self-diagnostic system, which easily allows identifying the operating faults (
RED LED
signal).
ITo use this function, wait at least ten seconds from the safety lock out, and then press the reset button for a minimum of 3 sec-
onds.
After releasing the button, the RED LED starts flashing as shown in the diagram below.
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will provide the information on the possible faults, according to the table below:
COLOUR CODE TABLE
Sequences
Colour code
Pre-purging
Ignition phase
Operation, flame ok
Operating with weak flame signal
Electrical supply lower than ~ 170V
Lock-out
Extraneous light
Key:
Off
Yellow
Green
Red
SIGNAL
PROBABLE CAUSE
2 flashes
The flame does not stabilise at the end of the safety time:
– faulty photocell;
– faulty or soiled oil valves;
– faulty ignition transformer
– poor burner regulation.
3 flashes
– Not used.
4 flashes
– Light in the chamber before firing.
7 flashes
Loss of flame during operations:
– poor burner regulation;
– faulty or soiled oil valves.
8 flashes
– Faulty thermostat for oil permissive signal;
– Heating resistances blown.
10 flashes
– Wiring error or internal fault;
– Presence of electromagnetic disturbance: use the radio disturbance protection kit
RED LED on
wait at least 10 s
Press button
for > 3 s
Signal
Signal
Interval
3 s