NExSIRIUS
90
NExSIRIUS
90
EN
Par
Variable name
Description
Value range
Default
Min
Max
112
HEAT CLIMATIC NUMBER
Use button
DAY
to select Heat climatic curve:
0
6
0
0. - zone 0, 1
0. No predefined climatic curve (Installer has to set the climatic curve)
1-6. See paragraph “Climatic curve”
p. 89 for details
1. - zona 2
0. No predefined climatic curve (Installer has to set the climatic curve)
1-6. See paragraph “Climatic curve”
p. 89 for details
113
REGION T° O
Minimum outdoor T° depending on the country where the system is installed (Heat
Climatic Curve Zone 0, 1 and 2)
-20 °C
10 °C
-7 °C
114
STOP H T° O
If outdoor T° is equal to or greater than the value of this code, minimum water
tempreature is considered (Heat Climatic Curve Zone 0, 1 and 2)
15 °C
50 °C
20 °C
115
NO HEATING T W1
In Heat mode, minimum water T° going to terminal zone 1 (Heat Climatic Curve Zone 0,
1)
20 °C
60 °C
20 °C
116
MAX W T° W1
In Heat mode, maximum water T° in terminal zone 0, 1 (Heat Climatic Curve Zone 0, 1)
20 °C
80 °C
35 °C
117
NO HEATING T W2
In Heat mode, minimum water T° going to terminal zone 2 (Heat Climatic Curve Zone 2)
20 °C
60 °C
40 °C
118
MAX W T° W2
In Heat mode, maximum water T° in terminal zone 2 (Heat Climatic Curve Zone 2)
20 °C
80 °C
55 °C
119
COOL CLIMATIC NUMBER
Use button
DAY
to select Cool climatic curve:
0
2
0
0. - zone 0, 1
0. No predefined climatic curve (Installer has to draw climatic curve)
1-2. See paragraph “Climatic curve”
p. 89 for details
1.-zone 2
0. No predefined climatic curve (Installer has to draw climatic curve)
1-2. See paragraph “Climatic curve”
p. 89 for details
120
MAX REGION T°
Maximum outdoor T° depending on the Country where the system is installed (Cool
climatic curve zone 0, 1 and 2)
30 °C
50 °C
40 °C
121
COOL STOP T°
If outdoor T° is equal to or less than the value of this code, maximum water
tempreature is considered (Cool climatic curve zone 0, 1 and 2)
0 °C
25 °C
22 °C
122
MIN COOLING W T°
In Cool mode, minimum water T° going to terminal zone 0, 1 (Cool climatic curve zone
0, 1)
4 °C
20 °C
12 °C
123
MAX COOLING W T°
In Cool mode, maximum water T° going to terminal zone 0, 1 (Cool climatic curve zone
0, 1)
4 °C
20 °C
18 °C
124
MIN COOLING W T°
In Cool mode, minimum water T° going to terminal zone 2 (Cool climatic curve zone 2)
4 °C
20 °C
6 °C
125
MAX COOLING W T°
In Cool mode, maximum water T° going to terminal zone 2 (Cool climatic curve zone 2)
4 °C
20 °C
12 °C
The parameters displayed in grey are not available.