NExSIRIUS
43
EN
Internal unit terminal block
Terminals
Description
Details
1 – 2 – 3
Indoor unit power and signal
4 – 5
Not usable
6 – N
Boiler heater control (DHW
Booster)
Output, 230 V, max. 2 A
(inductive)
7-8 – N
Domestic hot water 3-way
valve
Output, 230 V, max. 2 A
(inductive)
10 – 11
Domestic hot water boiler
sensor
Input, analogue
12 – 15
Energy cost limiter (ECO)
Input, dry contact
13 – N
Multi-purpose output
Output, 230 V, max. 2 A
(inductive)
14 – 15
Remote On - off
Input, dry contact
15
Common for digital inputs
Input, dry contact
W – C – G – Y
On-board or remote user
interface
20 – 15
Room thermostat
Input, dry contact
21 – 15
Heat/Cool switch
Input, dry contact
22 – 15
Domestic hot water
Input, dry contact
Rc – Rh – G2
– Y2
Not available
N
Neutral
31 – N
Boiler (only indoor unit
without heating element)
Output, 230 V, max. 2 A
(inductive)
IT
Morsettiera unità interna
Morsetti
Descrizione
Dettagli
1 – 2 – 3
Alimentazione unità interna
e segnale
4 – 5
Non utilizzabile
6 – N
Controllo resistenza bollitore
(Booster ACS)
Uscita, 230 V, max 2A
(induttiva)
7- 8 – N
Valvola 3 vie acqua calda
sanitaria
Uscita, 230 V, max 2A
(induttiva)
10 – 11
Sonda bollitore acqua calda
sanitaria
Ingresso, analogico
12 – 15
Limitatore costo energia (ECO)
Ingresso, contatto pulito
13 – N
Uscita multiuso
Uscita, 230 V, max 2A
(induttiva)
14 – 15
On – off remoto
Ingresso, contatto pulito
15
Comune ingressi digitali
Ingresso, contatto pulito
W – C – G – Y
Pannello comandi bordo unità
o remotizzato
20 – 15
Termostato ambiente
Ingresso, contatto pulito
21 – 15
Selettore riscaldamento /
raffreddamento
Ingresso, contatto pulito
22 – 15
Acqua calda sanitaria
Ingresso, contatto pulito
Rc – Rh – G2
– Y2
Non disponibile
N
Neutro
31 – N
Caldaia (solo unità interna
senza resistenza)
Uscita, 230 V, max 2A
(induttiva)
Rh
Rc
21
15
Y
G
C
W
22
22
21
20
20
15
14
14
Y
12
12
G
11
11
C
10
10
W
Y2
Y2
Rh
G2
G2
Rc
3
2
1
4
13
31
3
N
N
2
8
8
1
7
7
4
6
6
13
5
5
31
Содержание NexSirius
Страница 99: ......