NExSIRIUS
82
NExSIRIUS
82
EN
Par
Variable name
Description
Value range
Default
Min
Max
1
USER CONTROL
Use
DAYS
button to select below mentioned functions
0
1
0. Home Antifreeze option
1
0: Disable
1: Enable
1. Silent Mode
0
0: Not Active
1: Active
2. Power off all the electric heater
0
0: Operating as normal
1: Electric heater disable
3. Specifies if domestic hot water is produced despite sensor diagnostics or disinfection
cycle failure
0
The code is automatically reset to 0 when the above problem is solved
0: No
1: Yes
4. Specifies whether activation of the backup (for heating) or booster (for DHW) heating
elements is permitted when the external unit has an alarm.
0
0: No
1: Yes
5. Domestic hot water BOOSTER: Allows to heat up domestic hot water electric heater
regardless the heater schedule
0
The code is automatically reset to 0 once the domestic hot water setpoint is reached
0. Domestic hot water heater is turned on, if needed, according to the schedule
1. Domestic hot water heater is turned on, if needed, regardless the schedule
6. Water Pump Management zone 0, 1
0
0. Water pump of zone 0, 1 does not stop when room 0, 1 set point is reached
1. Water pump of zone 0, 1 stops when room 0, 1 setpoint is reached
7. Water Pump Management zone 2
0
0. Water pump of zone 2 does not stop when room 2 setpoint is reached
1. Water pump of zone 2 stops when room 2 setpoint is reached
2
HOME ANTIFREEZE T°
Home antifreeze threshold T° value
6 °C
12 °C
6 °C
3
FREQ REDUCT
Value of the outdoor unit frequency reduction in %
50%
100%
100%
4
ROOM HYSTERESIS
Hysteresis on room temperature (see thermostat function)
0,1
2
0,5
5
ADJUST T° ZONES
Modifies maximum temperature of heating climatic curve and minimum temperature
of cooling climatic curve.
-5 °C
+5 °C
0 °C
Use
DAYS
button to select below mentioned functions
0. Water set point adjustment in Heat mode for zone 0, 1
1. Water set point adjustment in Heat mode for zone 2
2. Water set point adjustment in Cool mode for zone 0, 1
3. Water set point adjustment in Cool mode for zone 2
6
DAY PERIOD
User can select how many periods per day is available for the scheduling.
1
3
Use
DAYS
button to select below mentioned functions
3
Day 0 - Zone 0, 1 and 2 schedule
0. no schedule; Schedule Icon will not be displayed
1. 2 periods
2. 4 periods
3. 6 periods
Day 1 - Domestic hot water schedule
2
1. 2 periods
2. 4 periods
7
TROOM SENSOR ADJ ZONES
Use
DAYS
button to select below mentioned functions:
-5 °C
+5 °C
0 °C
0. Room temperature sensor adjustment for zone 0, 1
1. Room temperature sensor adjustment for zone 2