3.7   Routine maintenance

3.7.1  Warnings

Before carrying out any maintenance work, make sure that 

the unit is not and cannot be, either casually or acciden-

tally, electrically powered.

Therefore, the electrical power must be disconnected any 

time maintenance work is carried out.

 

 

It is the duty of the buyer to perform all maintenance 

operations.

 

 

 

Only designated personnel qualified and trained can 

perform maintenance operations.

 

 

 If the unit must be disassembled, protect your hands 

with gloves.

3.7.2 Monthly checks

 

 

Control of the general conditions of the unit.

 

 

 Overall control of power consumption during heat pump 

operation.

 

 

 Overall control of the operation of the electrical heater.

3.7.3  Quarterly checks

 

 

Checking the tightness of all electrical connections.

 

 

 Control of the settings and programming parameters.

 

 

 Checking the status of the contacts of the fan and com-

pressor.

 

 

 Monitoring of air filters in the hydraulic circuit.

 

 

 Control the sacrificial anode.

 

 

 Check the operation of safety valve.

 

 

 Control the preload of expansion tank.

 

 

 Control of the general conditions of the unit and the in-

stallation and testing of leaks.

3.7.4  Yearly checks

 

 

Checking the refrigerant charge.

 

 

 Control the filter dryer.

 

 

 Checking the condition of the refrigerant circuit.

 

 

 Control of the electrical heater.

 

 

Check tightness of bolts, nuts, flanges and water con-

nections that may have been loosened by the vibrations.

3.8 Troubleshooting

In case of abnormal behaviour of the heat pump, without 

activation of alarms described in section "Alarms descrip-

tion", before calling the after sales service you can check 

by the following table if the problem is easily solved.

FAULTS 

POSSIBLE CAUSES 

The heat pump doesn't 

start

 

 

there is no electricity

 

 

 the main switch is open

 

 

 

the plug is not inserted 

into the electrical socket, 

or not enough to make 

contact

 

 

 

the safety fuse on the 

socket has blown

3.7   Planmäßige Wartung

3.7.1 Hinweise

Vor jedem Wartungseingriff muss sichergestellt sein, dass 

das Gerät nicht unter Spannung steht und auch nicht verse-

hentlich unter Spannung gestellt werden kann.

Bei jeder Wartung ist daher der Netzstecker zu ziehen.

 

 

Die Ausführung aller Wartungsarbeiten an der Wärme-

pumpe obliegt dem Auftraggeber.

 

 

 Nur entsprechend ausgebildetes und qualifiziertes Fach-

personal darf die Wartungsarbeiten ausführen.

 

 

 Sollte es notwendig sein, die Einheit auszubauen, dann 

müssen hierzu Arbeitshandschuhe verwendet werden.

3.7.2 Monatliche Kontrollen

 

 

Kontrolle des allgemeinen Gerätezustandes.

 

 

 

Allgemeine Kontrolle der Stromaufnahme während des 

Betriebs der Wärmepumpe.

 

 

 Allgemeine Kontrolle des Betriebs des elektrischen Wider-

stands.

3.7.3 Vierteljährliche Kontrollen

 

 

Prüfung aller elektrischen Anschlüsse.

 

 

 Prüfung der Einstellungen und der Programmierparameter.

 

 

 Prüfung der Kontakte des Lüfters und des Verdichters.

 

 

 Kontrolle der Filter am Wasserkreis.

 

 

 Kontrolle der Opferanode.

 

 

 Funktionsprüfung des Sicherheitsventils der Anlage.

 

 

 Kontrolle des Vorladedrucks des Ausdehnungsgefäßes des 

Anlage.

 

 

 Kontrolle des allgemeinen Zustands des Gerätes und der 

Anlage und Überprüfung auf Leckstellen.

3.7.4 Jährliche Kontrollen

 

 

Kontrolle der Kältemittelfüllung.

 

 

 Kontrolle des Entwässerungsfilters.

 

 

 Kontrolle des Erhaltungszustands des Kühlkreislaufs.

 

 

 Kontrolle des elektrischen Widerstands.

 

 

Prüfung aller Bolzen, Muttern, Flansche und Wasseran-

schlüsse, die sich durch Erschütterungen gelockert haben 

könnten.

3.8 Ortung der Störungen

Treten an der Wärmepumpe Unregelmäßigkeiten auf, ohne 

dass jedoch einer der in Abschnitt "Alarmbeschreibung" 

beschriebenen Alarme ausgelöst wird, dann prüfen Sie zu-

nächst anhand der nachfolgenden Tabelle, ob das Problem 

ganz einfach beseitigt werden kann, bevor Sie sich an den 

Kundendienst wenden.

STÖRUNGEN 

MÖGLICHE URSACHEN 

Die Wärmepumpe schaltet 

sich nicht ein

 

 

Es ist kein Strom vorhanden

 

 

 Der Hauptschalter des 

Stromkreises ist getrennt

 

 

 

Der Stecker ist nicht oder 

nicht richtig in der Steck-

dose eingesteckt

 

 

 Die Sicherung an der Steck-

dose ist unterbrochen

Содержание NexPro 300

Страница 1: ...rb 1 05 2016 NexPro EN HEAT PUMP FOR DOMESTIC HOT WATER INSTRUCTIONS FOR THE INSTALLER AND FOR THE TECHNICAL ASSISTANCE CENTRE DE W RMEPUMPE F R BRAUCHWARMWASSERAUFBEREITUNG BEDIENUNGSANLEITUNG F R DE...

Страница 2: ...chmals vielen Dank Riello S p A HEAT PUMP FOR DOMESTIC HOT WATER W RMEPUMPE F R BRAUCHWARMWASSERAUFBEREITUNG MODEL CODE Nex Pro 20035655 Nex Pro C 20035656 Nex Pro CS 20035657 MODELL CODE Nex Pro 2003...

Страница 3: ...10 2 1 1 Verpackung 10 2 1 2 Handling und Transport 10 2 1 3 Kontrolle bei bernahme der Lieferung 10 2 1 4 Lagerung 11 2 2 Installation und Inbetriebnahme 11 2 2 1 Begriffsbestimmungen 11 2 3 Sicherhe...

Страница 4: ...n We remind you that the use of products that employ elec trical energy and water requires that a number of essen tial safety rules be followed including This appliance must not be used by children an...

Страница 5: ...gas f rmigen Gemischen und oder festen Partikeln verun reinigt ist Der Einsatz des Ger ts f r andere als die vorgesehenen Zwecke die nicht mit den Beschreibungen in diesem Handbuch bereinstimmen f hr...

Страница 6: ...eit der Au en luft neue umweltfreundliche W rme zu entziehen Es k nnen auch zus tzliche Energiequellen verwendet wer den indem W rmetauscher an Heizkessel oder Solarzellen angeschlossen werden Das Sta...

Страница 7: ...ree energy sources model NEX PRO CS Modulierende Einstellung des L fters entsprechend der Luft und Wassertemperatur Funktion Dynamischer Sollwert Regelung der Mindestintervalle zwischen aufeinander fo...

Страница 8: ...ahresverbrauch AEC 5 kWh 826 Daily consumption QELEC 5 Tagesverbrauch QELEC 5 Wh 4000 Maximum power input Maximale Stromaufnahme A 6 5 Refrigerant K ltemittel type Typ R134A Refrigerant charge K ltemi...

Страница 9: ...60 160 160 mm 660 660 660 Transport weight Transportgewicht kg 122 137 155 POSITION POSITION DESCRIPTION BESCHREIBUNG 1 Hot water Warmwasser M 1 2 Boiler delivery Kesselvorlauf M 1 3 Probe well F hler...

Страница 10: ...igneten Material umwickelt das erst bei der Mon tage abgenommen werden darf 2 1 2 Handling und Transport F r das Handling sind je nach Gewicht geeignete Mittel zu verwenden wie in der letztg ltigen Fa...

Страница 11: ...von Vibrations und W rmequellen gehalten werden Die Herstellerfirma haftet nicht f r Sch den durch un sachgem e Entladung oder mangelnden Schutz f r Witterungseinfl ssen 2 2 Installation und Inbetrieb...

Страница 12: ...baren Parameter Bearbeitung der Alarmsituationen Kontrolle der Betriebsmittel 2 6 Benutzerschnittstelle Zeichenerkl rung Abb 5 1 Display 2 Key UP 3 Key DOWN 4 Key SET 5 Key ON OFF 6 Key activation ant...

Страница 13: ...e total operation hours KEY SET Allows to View the parameters list View the selected parameter Confirm the modification of the parameter KEY ANTIBACTERIAL TREATMENT Push the key to activate the antiba...

Страница 14: ...GND INT POWER SUPPLY BASIC BOARD BASISPLATINE THERMOSTAT LOW PRESSURE ELEKTRONISCHE ANODE OPTIONAL EIN AUS BER TIMER BOILER ENABLING EING NGE AUSG NGE ON OFF WITH CONTACTOR 3mF COMPRESSOR P FAN S C R...

Страница 15: ...tion enabling r3 NC FC compressor ignition enabling r1 DIGITAL OUTPUTS INT GND volt free contact for boiler enabling r7 DER DIGITALEING NGE ZUSTAND Hp GND hoher Druck ID1 Bp GND niedriger Druck nur Vo...

Страница 16: ...t to the right of the display being on and fixed To exit from displaying mode press and hold the SET key or wait 60 seconds since the last release of UP DOWN or SET keys 2 8 Betriebslogik 2 8 1 Einste...

Страница 17: ...i Ger te Luft Wasser W rmepumpe und elektrischer Wider stand erfolgt steuert der mit zwei F hlern einem Was sertemperaturf hler S1 und einem Lufttemperaturf hler S2 ausgestattete Regler das Anlaufen d...

Страница 18: ...die vom F hler S1 gemessene Temperatur unter dem Sollwert es sind jedoch die ber die Parameter H20 und H21 eingestellten Verz gerungen aktiv blinkt die zweifar bige LED L1 gr n Ist die W rmepumpe akti...

Страница 19: ...to force the antibacterial treatment at any time 2 11 Betriebsweise zyklische antibak terielle Behandlung Die zyklische antibakterielle Behandlung wird ber die Taste Zyklus ausgew hlt Das Ger t kann h...

Страница 20: ...rt ein bzw ausgeschaltet werden Der dynamische Sollwert ist nur f r die W rmepumpe aktiv F r den dynamischen Sollwert m ssen folgende Parameter eingestellt werden H34 Neigung der Kompensierungsgeraden...

Страница 21: ...er NEX PRO an eine Anlage mit mehreren zus tz lichen Energiequellen angeschlossen muss die Einschalt priorit t der verschiedenen Quellen festgelegt werden und normalerweise erfolgt dies unter Ber cksi...

Страница 22: ...lers besteht die Wahlm glichkeit ob der Widerstand nur in den Stunden gespeist werden soll in denen der Tarif am g nstigsten ist Zu diesem Zweck steht an der Basisplatine des Ger ts ein normalerweise...

Страница 23: ...m des Verdichters gekop pelt d h l uft der L fter l uft auch der Verdichter Der Parameter F02 bestimmt die Art der Regelung F02 0 EIN AUS Regelung F02 1 modulierende Regelung Im Falle der modulierende...

Страница 24: ...HoursElect Heater Visualize HoursGasHeater ResetCount HoursPdC Reset Count HoursElect Heater Reset Count days Reset Count HoursGasHeater VisualizeOn Off Elect Heater contactGND RES VisualizeOn Off Un...

Страница 25: ...ckw chter ZustandsanzeigeNiederdruckw chter ZustandsanzeigeWiderstand berEin AusKontakt ZustandsanzeigeMaschine berEin AusKontakt ZustandsanzeigeVerdichter ZustandsanzeigeWiderstand ZustandsanzeigeL f...

Страница 26: ...ime between switching off and switching on Time OFF ON expressed in ten second intervals H21 100 0 255 10 SEC Minimum time between two successive starts Time ON ON expressed in ten second intervals H2...

Страница 27: ...halten und Einschalten EIN AUS Zeit ausge dr ckt in Zehntelsekunden H21 100 0 255 Sek 10 Mindestzeitraum zwischen zwei aufeinander folgenden Einschaltungen EIN EIN Zeit ausgedr ckt in Zehntelsekunden...

Страница 28: ...fttempera tur bei deren berschreiten der L fter im niedrigsten Drehzahlbe reich aktiviert werden muss F06 6 0 10 C Temperatur differenz f r Aktivierung des L fters im h chsten Dreh zahlbereich F07 15...

Страница 29: ...ellt die kontinu ierliche Dauer des Zustands S1 AL5 ein bei deren berschreiten der Alarm hohe Tem peratur ausgel st wird AL7 10 0 255 Anz 3 Anzahl Ausl sun gen Stunde Hoher Druck Wech sel von automati...

Страница 30: ...vor der Inbetrieb nahme Pr fen Sie vor dem Starten des Ger tes den korrekten Anschluss des Erdungskabels das Vorhandensein einer Schutzsicherung an der Steck dose das korrekt eingesteckte Versorgungs...

Страница 31: ...umen auf in denen ent flammbare Gase saure angreifende und korrosive Sub stanzen vorhanden sind die die verschiedenen Bauteile irreparabel besch digen k nnen Planen Sie f r Installations Reparatur und...

Страница 32: ...Solar heating circuit pump D Temperature sensor E Solar panels F Safety valve G Expansion tank 3 1 1 Hinweise f r die Installation des Modells NEX PRO CS Zeichenerkl rung Abb 14 A NEX PRO CS B BWW Umw...

Страница 33: ...reducer 3 Inspection valve 4 Non return valve 5 Drain valve 6 Safety diaphragm valve 7 Circulation pump 8 Drain Only for NEX PRO C and NEX PRO CS models Only for NEX PRO CS models 3 2 Wasseranschl ss...

Страница 34: ...pe bildet flie t durch das auf der R ckseite des Ger ts austre tende durch den Isoliermantel gef hrte Abflussrohr ab mit gewinde von 1 2 Dieser Austritt muss an eine Leitung angeschlossen werden damit...

Страница 35: ...adjustment of 90 from fully open Fig 17 A to fully closed fig 17 B 3 5 Luftverteilung mit motorgesteuerter runder Regelklappe Zubeh rcode 20039876 Die Verbindung der D mpfer ist in Abb 16 dargestellt...

Страница 36: ...tversorgung getrennt ist Die elektrischen Anschl sse an die Steuertafeln d rfen nur von Fachpersonal unter Beachtung des beigepackten Schaltplans durchgef hrt werden F hren Sie eine Kontrolle der Elek...

Страница 37: ...ige Wartung 3 7 1 Hinweise Vor jedem Wartungseingriff muss sichergestellt sein dass das Ger t nicht unter Spannung steht und auch nicht verse hentlich unter Spannung gestellt werden kann Bei jeder War...

Страница 38: ...UNGEN M GLICHE URSACHEN Der Verdichter und oder L f ter schalten sich nicht ein Die eingestellten Sicher heitszeiten sind noch nicht abgelaufen Das System ist ges ttigt keine anstehende Star terforder...

Страница 39: ...39 NexPro...

Страница 40: ...range of products the appear ance and dimensions the technical data the equipment and accessories can be subject to variation Da das Unternehmen dauerhaft bestrebt ist seine Produkte zu verbessern k...

Отзывы: