OPERATION TROUBLES AND THEIR CAUSES 

The symbol, visible on the reading disc of the pointer, shows the kind of problem.

”

 The control box does not start at the thermostats closing, because of:

- lack of gas;
- the gas pressure switch does not close the contact: bad set;
- the air pressure switch changed over in operation position; 
- the control box fuse is broken;
- the servomotor does not totally change over the closing circuit in being between the terminals 11 and 8 of the

control box.

 Stop at the start-up, because of:

- the servomotor does not change over the max. opening circuit in being between the terminals 9 and 8 of the control

box.

P

 Lock-out

The air pressure switch does not change over, because of:
- defective contact;
- insufficient pressure of the air.

O

 Lock-out

Unperfect operation of the flame detecting circuit, because of:
- probe to earth;
- defective internal amplifier.

P

 Stop during pre-purge phase, because of:

the servomotor does not change over the minimal opening circuit in being between the terminals 10 and 8 of the
control box.

1

 Lock-out due to flame signal lack; if:

- the ionisation probe is not inside of the flame;
- the probe connection to the control box is disconnected;
- the ionization current is insufficient (min. 6 µA).

—

 Lock-out during operation due to:

- flame signal lack;
- no air pressure.

NOTICE

- If lock-out occurs between the start-up and pre-ignition phase without that a symbol comes out, the cause is the

flame simulation.

- If the burner repeats continuously the start-up cycle without lock-out occurring, this is due to the “oscillation” of the

gas pressure switch caused by a setting very near to the gas network pressure, therefore the pressure decreasing
at the burner start-up is sufficient to actuate the gas pressure switch causing a new start-up.

Содержание GAS 6 P/M

Страница 1: ...2915244 3 09 2012 Installation use and maintenance instructions Forced draught gas burner MODEL TYPE GAS 6 P M 536 T80...

Страница 2: ......

Страница 3: ...asured at the cou pling with nil pressure in the combustion chamber and gas with cal orific value of 8600 kcal m3 Maximum gas pressure 150 mbar Electrical supply 3N 380V 60 Hz Fan motor rpm V kW A 335...

Страница 4: ...rol box reset button 5 Servomotor connection 6 Fair leads 7 Wiring terminal block 8 Reset push button of the motor over load relay 9 Air pressure switch 10 Gas pressure test point DIMENSIONS Length av...

Страница 5: ...us the pressurization value Example to obtain 800 kW it is necessary a gas pressure of 11 mbar and the combustion head set as indicated at page 8 If the combustion chamber is pressurized at 2 mbar the...

Страница 6: ...uld be carried out as follows Loosen the screws 2 UNHOOK THE TENSION ROD OF THE AIR DAMPER 1 remove the connecting lead of the servomotor withdraw the group A from the group B After the setting re ass...

Страница 7: ...5244 5 BURNER ELECTRICAL WIRING carried out y the factory D3377...

Страница 8: ...force in the Country Leads minimal section 1 mm2 Adjustment for the motor thermal relay at the beginning of the scale for 380V at the end of the scale for 220V Burners with non stop operation For saf...

Страница 9: ...controller modulating version 8 Pre sheared holeg Further prospective signals or controls can be connected to the burner wiring terminal board by removing the metal weldnuts from the pre sheared holes...

Страница 10: ...west set point When the burner is operating increase the adjustment pressure by turning slowly clockwise the knob till reaching the burner lock out There after turn the knob anticlockwise for 1 mbar a...

Страница 11: ...3 is coincident with the desired set point on the plate 4 Tighten the screws 1 Gas setting Loosen the screw 5 move the ring 6 so that the pointer 7 is coincident with the desired set point 8 Tighten...

Страница 12: ...t button 1st cam it controls the min stroke and remains always positioned on 0 in this way when the burner is off the air damper is totally closed 2nd cam it controls the max stroke generally it is po...

Страница 13: ...justable profile 7 of the cam by gradually acting on the screws 9 3 2 Minimal output setting Gas Disjoint the cam with adjustable profile 6 by means of the button 5 Turn manually anticlockwise the cam...

Страница 14: ...change from 90 to 60 of the tension rod will be sufficient Should this ratio be in higher range 50 100 in this case further to position the tension rod on 60 it shall be shotened Proceed as follows D...

Страница 15: ...N CURRENT The minimum current necessary for the control box operation is 6 A The burner normally supplies a higher current value so that no check is needed However if a measurement of the ionization c...

Страница 16: ...ion of the flame detecting circuit because of probe to earth defective internal amplifier P Stop during pre purge phase because of the servomotor does not change over the minimal opening circuit in be...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com...

Отзывы: