COMBUSTION CHAMBER PRESSURE - MAXIMUM OUTPUT
Minimum output: 300 kW - 258.000 kcal/h
MINIMUM GAS PRESSURE - OUTPUT
Pressure: detected at the pressure test-point 10) (fig. 1) with oil mbar into the combustion chamber.
Should the combustion chamber be pressurized, the pressure necessary will be that of the graph plus
the pressurization value.
Example: to obtain 800 kW it is necessary a gas pressure of 11 mbar and the combustion head set as indicated at
page 8.
If the combustion chamber is pressurized at 2 mbar, the pressure detected at the test-point 10) is:
11+2=13 mbar.
If this value is too high, for very low gas pipework pressures, the gas gear 6) (page 8) could be more
open. Do not decrease the pressure at the coupling under the values shown in the diagram.
Output:
the maximum value is obtainable with gas Pci 8600 kcal/m
3
.