46
SHUTDOWN
46
APPENDIX
Error no. Error
Description
Checks
Solutions
13
APS_NOT_OPEN
Air pressure switch not
working
14
APS_NOT_CLOSED
Air pressure switch not
working
15
MAX_TEMP_ERROR
The external overheat
protection is enabled or the
T_Supply sensor measures a
temperature of over
100°C (212°F)
a- Check module water
temp.
b- Check the pump to verify
the flow circulation;
c- Check if the valves on
hydraulic circuit are open;
d- Check the high limit
switch.
a- Change the pump or
restart it;
b- Open the valves on
hydraulic circuit;
c- Change the high limit
switch.
16
FLUE_GAS_ERROR
Flue temperature exceeded
the maximum flue
temperature
17
STACK_ERROR
Internal software error
Replace the power control
board
18
INSTRUCTION_ERROR
Internal software error
Replace the power control
board
19
ION_CHECK_FAILED
Internal software error
Replace the power control
board
20
FLAME_OUT_TOO_LATE
Flame still present 10
seconds after closing the gas
valve
Replace the gas valve
21
FLAME_BEFORE_IGNIT
Flame is detected before
ignition
Replace the gas valve
22
TOO_MANY_FLAME_LOSS
Three flame failures during
one demand cycle
a- Check the integrity of
the wire connections of the
spark and the earth on heat
exchanger
b- check ionization signal
while running
a- If wires are damaged,
replace them
b- check for proper
combustion settings - if
correct replace spark/
flamerod.
23
CORRUPTED_ERROR_NR
Error code RAM byte was
corrupted to an unknown
error code
24
FLUE_SWITCH_NOT_CLOSING
The blocked flue sensor is
not closed within 10 minutes
29
PSM_ERROR
Internal software error
30
REGISTER_ERROR
Internal software error
Replace the power control
board
33
LWCO_1_ERROR
Low Water Cut-Off 1 error
a- Check to ensure all valves
are open, pump is running.
b- Check the wiring
between the controller and
the LWCO probe.
a- Verify water is in the
boiler.
b- Verify good connection
between control module
and low water probe.
34
LWCO_2_ERROR
Low Water Cut-Off 2 error
NA
NA
35
GAS_PRESSURE_ERROR
Gas pressure switch is open.
This can either be the High
or Low Gas Pressure Switch.
a- Check gas pressure to
ensure it is correct and in
the recommended range for
the unit.
b- Check with as many
modules on as possible to
ensure supply connections
are sized properly.
36
AIR_DAMPER_LOCKING
Air Damper feedback is not
received when the relative
output is closed for the
fourth time.