background image

4

GENERAL

GENERAL

The 

R

 

Array  AR 3000

 and 

AR 4000

 MBH Boilers are fully 

modulating,  high-efficiency  condensing  units. They represent 

a true industry advancement that meets the needs of today’s 

energy and environmental concerns. Designed for application in 

any closed loop hydronic system, the modulating capability of the 

Array

 matches energy input directly to fluctuating system loads. 

The turn down ratio for these models is 30:1 for 

AR 3000 

and 40:1 

for 

AR 4000

. These 

Array

 models provide extremely high efficient 

operation and are ideally suited for modern low temperature, as 

well as conventional heating systems.

The 

Array

 Models 

AR 3000

 and 

AR 4000

 operate within the 

following input and output ranges:

Array 

Model

Input Range (BTU/hr.)

Output Range (*) (BTU/hr.)

Minimum

Maximum Minimum

Maximum

AR 3000

100,000

3,000,000

96,100

2,883,000

AR 4000

100,000

4,000,000

96,100

3,844,000

(*)  The output of the boiler is a function of the unit’s firing rate, 

return water temperature and BTU content of the supplied 

gas.

The

  Array 

Series of hot water boilers has been designed in 

compliance with the CSD-1 code.

When installed and operated in accordance with this Instruction 

Manual, these boilers comply with the NOx emission standards 

outlined in:

South Coast Air Quality Management District (SCAQMD), Rule 1146.2

Whether used in singular or modular arrangements, the 

AR 3000 

and 

AR 4000

 offer the maximum venting flexibility with minimum 

installation  space  requirements.  These  Boilers  are  Category  IV, 

positive pressure appliances. Single and/or multiple breeched 

units are capable of operation in the following vent configurations:

−  Conventional, Vertical Conventional, 

−  Sidewall Conventional, Direct Vent,

−  Vertical Sealed, Direct Vent, Horizontal

These boilers are capable of being vented utilizing PP, CPVC, 

Stainless steel AL29-4C vent systems.

The 

Array

’s advanced electronics include several selectable modes 

of operation offering the most efficient operating methods and 

energy management system integration.

IMPORTANT: 

Unless otherwise specified, all descriptions and 

procedures provided in this Installation & Operation Manual 

apply to the 

Array

 series of boiler.

1.1 

Warnings & Cautions

Installers and operating personnel MUST, at all times, observe 

all safety regulations. The following warnings and cautions 

are  general  and  must  be  given  the  same  attention  as  specific 

precautions included in these instructions.

 In addition to all the requirements included in this 

R

 Instruction 

Manual, the installation of units MUST conform with local building 

codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel 

Gas Code Publication No. NFPA-54) for gas-fired boilers and ANSI/

NFPASB for LP gas-fired boilers. 

Where applicable, the equipment shall be installed in accordance 

with the current Installation Code for Gas Burning Appliances and 

Equipment, CSA B149.1, and applicable Provincial regulations for 

the class; which should be carefully followed in all cases. 

Authorities having jurisdiction should be consulted before 

installations are made.

See pages 7 - 13 - 19 for important information regarding 

installation of units within the Commonwealth of Massachusetts.

IMPORTANT: 

This Instruction Manual is an integral part of the 

product and must be maintained in legible condition. It must 

be given to the user by the installer and kept in a safe place 

for future reference.

WARNING: 

Do  not  use  matches,  candles,  flames,  or  other 

sources of ignition to check for gas leaks.

WARNING: 

Fluids under pressure may cause injury to personnel 

or damage to equipment when released. Be sure to shut off 

all incoming and outgoing water shutoff valves. Carefully 

decrease all trapped pressures to zero before performing 

maintenance.

WARNING: 

Before attempting to perform any maintenance on 

the unit, shut off all gas and electrical inputs to the unit.

WARNING: 

The exhaust vent pipe of the unit operates under 

a positive pressure and therefore must be completely sealed 

to prevent leakage of combustion products into living spaces.

WARNING: 

Electrical voltages up to 230  VAC maybe used in 

this equipment. Therefore the cover on the unit’s power box 

(located behind the front panel door) must be installed at all 

times, except during maintenance and servicing.

CAUTION: 

Many soaps used for gas pipe leak testing are 

corrosive to metals. The piping must be rinsed thoroughly 

with clean water after leak checks have been completed.

CAUTION

: DO NOT use this boiler if any part has been submerged 

under water. Call a qualified service technician to inspect and 

replace any part that has been subjected water.

Содержание Array AR 3000

Страница 1: ...cod Doc 0079789 rev 5 09 2018 Array AR 3000 AR 4000 US INSTALLATION AND OPERATION MANUAL...

Страница 2: ...or consequential damages occurring in connection with the furnishing performance or use of this material ENGLISH RANGE MODEL ASSEMBLY NUMBER Array AR 3000 20144522 Array AR 4000 20144042 9WARNING If...

Страница 3: ...the Building 27 4 16 3 Ducted Combustion Air 27 5 COMMISSIONING 27 5 1 Introduction 27 5 2 Filling the Condensate System 27 5 3 Filling the Boiler Heating System 27 5 4 Warnings Concerning the Gas Sup...

Страница 4: ...tallers and operating personnel MUST at all times observe all safety regulations The following warnings and cautions are general and must be given the same attention as specific precautions included i...

Страница 5: ...lied by R are excluded from the R warranty 1 3 General Warning The installation must conform to the requirements of the authority having jurisdiction or in the absence of such requirements to the late...

Страница 6: ...1 PVC female 1 Cardboard box on pallet Component Qty Packaging method 7 Relief Valves Drain Adapter 2 5 NPT female 1 Cardboard box on pallet 8 Flue Adapter 10 8 1 Cardboard box on pallet 9 Mounting A...

Страница 7: ...arbon monoxide detector with an alarm shall be installed 2 APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 7...

Страница 8: ...RIPTION 78 91 2 75 81 67 72 74 6 2 15 5 2 36 2 4 4 10 8 10 1 57 4 5 7 07 7 08 7 75 7 08 35 39 23 47 56 78 2 7 Size and Connections Array AR 3000 AR 4000 Boilers feet may be removed for reducing overal...

Страница 9: ...m3 h 39 52 Water flow at max power T 45 F 25 C GPM 136 182 m3 h 31 41 Vent Air Intake Connections Inch 8 or 10 10 8 or 10 10 mm 200 or 250 250 200 or 250 250 Vent Materials CPVC PP Stainless Steel AL2...

Страница 10: ...10 PRODUCT DESCRIPTION 2 9 Assembly Components 1 5 4 3 6 2 12 18 7 8 14 9 16 10 17 13 11 24 23 15 21 22 20 19 30 29 26 25 31 29 27 33 32...

Страница 11: ...n 22 Vertical supply manifold 23 Condensate drain 24 Relief valve drain Item Description 25 Burner head O ring 26 Burner flange outer 27 Burner gasket 28 Sight glass combustion 29 Igniter 30 Burner tu...

Страница 12: ...DESCRIPTION 2 10 Efficiency Curves Array AR 3000 AR 4000 80 88 90 92 94 96 98 100 70 80 90 100 110 120 130 140 150 160 170 Thermal Efficiency Return water temperature F 36 Degree Rise 100 input 30 inp...

Страница 13: ...U hr energy input for the AR 3000 OR 4 000 000 BTU hr energy input for the AR 4000 The boilers should be mounted on a concrete service housekeeping pad 4 in height The boiler should be located close t...

Страница 14: ...lift from the SIDE ONLY see Fig 3 FOR MASSACHUSSETTS ONLY For Massachusetts installations the unit must be installed by a plumber or gasfitter licensed within the Commonwealth of Massachusetts In addi...

Страница 15: ...28 0 75 0 28 0 75 Fig 8 Array AR 3000 and AR 4000 Anchoring bolt detail 4 5 Boiler Location This boiler is suitable only for indoor installations To operate properly and safely this boiler requires a...

Страница 16: ...ated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle A minimum water pressure is required...

Страница 17: ...ed to a nearby floor drain In multiple unit installations the discharge lines must not be manifolded together Each must be individually run to a suitable discharge location Relief valves should be man...

Страница 18: ...ch NPT gas inlet connection on the top of the unit as shown in Fig 9 9WARNING Never use matches candles flames or other sources of ignition to check for gas leaks 9CAUTION Many of the soaps used for g...

Страница 19: ...codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly or the installation adjustment modification operation or maintenance is ca...

Страница 20: ...POWER the fan will run at the minimum speed Screw B Screw A Fig 16 O2 Adjustment To adjust the O2 value at the minimum input turn the screw B rotate clockwise to decrease O2 shown in Fig 16 Verify tha...

Страница 21: ...n in Fig 21 does not remove power from the left door terminal blocks NOTE All electrical conduit and hardware must be installed so that it does not interfere with the removal of any unit covers inhibi...

Страница 22: ...s air damper alarm must be powered through a relay not included in the boiler to be provided and wired by the installer 101 102 104105 106107 108109 110 111 112 113 114 115 103 ALARM MAIN CH PUMP Air...

Страница 23: ...raps must be filled with water or combustion gases will enter the room with a risk of an excessive level of carbon monoxide Vent connectors serving appliances vented by natural draft shall not be conn...

Страница 24: ...Outdoors through Ventilated Attic EXHAUST BOILER Fig 29 AllCombustionAirFromOutdoors InletAirFromVentilated Crawl Space and Outlet Air to Ventilated Attic EXHAUST BOILER AIR DUCT AIR DUCT Fig 30 All...

Страница 25: ...s through Single Combustion Air Opening BOILER EXHAUST Fig 32 Sealed Combustion Located on Same Side with Exhaust vertical EXHAUST BOILER Fig 33 Sealed Combustion Located on Same Side with Exhaust hor...

Страница 26: ...endix H Venting Size Data 4 16 Combustion Air Air supply is a direct requirement of ANSI 223 1 NFPA 54 CSA B149 1 and local codes These codes should be consulted before a permanent design is determine...

Страница 27: ...ill void any warranty 9CAUTION All of the installation procedures in Installation page 13 must be completed before attempting to start the unit 5 2 Filling the Condensate System The condensate system...

Страница 28: ...Units It mustmatchthenumberofmodulesoftheboiler 6forAR3000 and 8 for AR 4000 By default the number of expected modules is 8 Follow the path below on the Service display Menu Settings Boiler Settings M...

Страница 29: ...ist Fan Speed Maximum Fan Speed Minimum 1 5 1 0 2 0 9 Voltage OFF ON ON OFF Hysterese O F F O N M o d u l a t i n g Fig 42 10VDC Control mode The CH setpoint Min and CH setpoint Max parameters can be...

Страница 30: ...scade installation scheme After the electrical wiring of the Managing controllers of each boiler of the cascade through the Cascade link connections on the Low voltage terminal strips the following st...

Страница 31: ...panel contains the basic controls for monitoring the boiler All other controls indicators and displays necessary to operate adjust and troubleshoot the boiler are available on the 905PB inner display...

Страница 32: ...e temperature water flowrate fan speed flame rod ionization current burner and pump status any error status or service required Use the side buttons to perform the actions listed below Home button mov...

Страница 33: ...ll it will overwrite the oldest log entry Each time the Service Reminder is being reset a new service moment is counted and the Service Overdue counter will be stored in the log history There are two...

Страница 34: ...an Emergency Only in emergencies switch OFF the heating system via the boiler room breaker or the heating system emergency stop switch In dangerous situations immediately close the main fuel shut off...

Страница 35: ...h J6 6 b SLAVE 2 TOUCH SCREEN 485 101 102 104105 106107 108109 110 111 112 113 114 115 103 ALARM MAIN CH PUMP Air Damper DHW 3 WAY CH DHW Pump CH Pump N L3 L2 L1 N L3 L2 L1 OUT IN N L3 L2 L1 A1 A2 A1...

Страница 36: ...1 b 213 GAS VALVE J5 1 bl J5 2 w J2 4 gr FAN 216 J4 2 bl J4 3 w J2 1 gr 5 4 2 1 J4 1 br J4 4 h J4 5 grey J4 6 bl 211 PWM PRESSURE SWITCH SWITCH SWITCH CONDENSATE PRES SWITCH FAN J12 3 J11 1 LWCO J12...

Страница 37: ...12 2 b 202 212 SAFETY LIMIT WATER THERMOSTAT UNIT FLOW TEMP 213 GAS VALVE J5 1 bl J5 2 w J2 4 gr J1 1 w J1 5 bl J1 4 gr FAN 216 J4 2 bl J4 3 w J2 1 gr 5 4 2 1 J4 1 br J4 4 h J4 5 grey J4 6 bl 211 PWM...

Страница 38: ...PUMP 8 PUMP 7 PUMP 6 COM COM O N O N A2 A1 R6 COM COM NO NO A2 A1 R7 A2 A1 R8 NO NO COM COM PUMP 5 COM COM O N O N A2 A1 R5 J3 4 DEP 5 J3 9 DEP 5 M5 LEFT DOOR ON OFF POWER BUTTON M6 M7 M8 PRE WIRED Bl...

Страница 39: ...39 SHUTDOWN 39 APPENDIX WIRING DIAGRAM DEPENDENT 5 6 7 8 RIGHT DOOR...

Страница 40: ...0 5 J10 6 J11 2 J11 4 J11 1 J11 3 J8 1 J8 2 SWL J1 1 J1 5 J1 4 J1 2 PROG OUTPUT 4 CONFIG 1 2 CH Pump 3 DHW Pump PROG OUTPUT 1 2 CH Pump PROG OUTPUT 5 1 General Pump L N L L N N J3 4 J3 9 J3 3 J3 8 J3...

Страница 41: ...24V To 905MN 1 2 3 4 5 6 J25 Wire Colors j25 1 Grey j25 2 Black j25 3 Green j25 4 Yellow j25 5 Red j25 6 Blue CONNECTION DIAGRAM 905PB DISPLAY CONNECTION DIAGRAM 905TS Touchscreen AND 905PB DISPLAY Mo...

Страница 42: ...ck wiring and connections Annually Verify startup Annually Verify the flame stability and signal strength Annually Check relief valve Annually Inspect the burner gasket Annually or every 2000 hours Wh...

Страница 43: ...5ft AR 4000 7ft 16 5ft Array Model Boiler Quantity Combined Max GPM Common Pipe Size Inch Max Equivalent Length of Pipe ft AR 3000 1 150 4 150 2 300 6 300 3 450 6 150 4 600 8 330 AR 4000 1 200 6 180...

Страница 44: ...ray AR 4000 Altitude ft From 0 to 25 From 25 to 50 From 50 to 75 From 75 to 100 0 2 000 4 000 000 4 000 000 4 000 000 4 000 000 3 000 3 671 586 3 607 867 3 544 141 3 480 422 4 000 3 549 798 3 488 189...

Страница 45: ...Safety relay Replace the power control board 4 BLOCKING_TOO_LONG Control had a blocking error for more than 20 hours This error is caused when any of the Blocking errors have occurred and wasn t corre...

Страница 46: ...e flame failures during one demand cycle a Check the integrity of the wire connections of the spark and the earth on heat exchanger b check ionization signal while running a If wires are damaged repla...

Страница 47: ...osed a Check all hydraulic valves and pumps are open and functioning correctly b Check supply sensor c Check the value of the reading of this sensor in the info screen a Change the pump or restart it...

Страница 48: ...t resistance values If values are incorrect sensor must be replaced 122 DHW_OPEN DHW sensor open a Check the integrity of the wire connections b Check the DHW temperature sensor a If the wiring is dam...

Страница 49: ...ressure switch is closed a Check flue for obstructions Clear if found b Check flue pressure to ensure flue has been installed and sized properly c Flue pressure switch default to 2 2 wc a Remove any o...

Страница 50: ...Mode to activate on that particular boiler c Remaining cascade will continue to operate as normal d Check the value of the reading of this sensor on the info screen 204 T_CASCADE_WRONG T_Cascade sens...

Страница 51: ...ED FOR FLOW RATES LESS THAN 4 0 FT SEC COMMON PIPE LENGTH BETWEEN THE CLOSE TEES MUST BE 3 TO 5 TIMES ITS DIAMETER NOTES 1 THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING CONCEPT ONLY 2 INSTALLATIO...

Страница 52: ...l A NOTES 1 THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING CONCEPT ONLY 2 INSTALLATIONS MUST COMPLY WITH ALL LOCAL CODES 3 INSTALL A MINIMUM OF 12 DIAMETERS OF STRAIGHT PIPE UPSTREAM OF ALL CIRCUL...

Страница 53: ...boilers to a single exhaust system No more than eight 8 boilers should be cascade vented together The boiler vent installation must be in compliance with ANSI Z223 1 NFPA 54 and all local state and fe...

Страница 54: ...m above grade or snow line YB Exhaust terminal must be at least 3 feet 915 mm above forced air inlet within 10 feet 3050 mm horizontally USA 6 feet 915 mm above forced air inlet Canada It is not recom...

Страница 55: ...Vent Vent Y Multiple air and vent vertical termination X 12 305 mm Y 12 305 mm Y X Y X X Vertical venting system sealed combustion X 12 305 mm Y 12 305 mm above maximum snow level or at least 24 which...

Страница 56: ...2582 158 70 2221 167 75 1918 176 80 1663 185 85 1446 194 90 1262 203 95 1105 212 100 970 221 105 855 230 110 755 239 115 669 248 120 594 257 125 529 Resistance table for Heat exchanger supply temperat...

Страница 57: ...ly Temp 30 90 40 C 2 Installer 22 Baseline Outdoor Temp 0 30 20 C 2 Installer 23 Design Supply Min Limit 4 82 30 C 2 Installer 24 Design Supply Max Limit 27 90 80 C 2 Installer 25 Warm Weather Shutdow...

Страница 58: ...an Speed Ignition 0 12750 See Appliance settings RPM 2 Installer 116 Prog Input 1 0 Disabled 1 Water pressure sensor 2 CH flow switch 3 Flue pressure switch See Appliance settings 2 Installer 117 Prog...

Страница 59: ...m Pump 5 Cascade Pump 6 Alarm Relay 7 Filling Valve 8 LPG Tank 9 External Igniter 10 Air Damper 14 Alarm Burner CC 15 Status Burner CC 16 Zone pump 17 Mixing valve open 18 Mixing valve closed 19 Anti...

Страница 60: ...2 Installer 139 Dair active Yes No No 2 Installer 140 Minimal Flow 0 0 100 17 l min 2 Installer 107 Anti legionella Day Sun Sat Sun Day 2 Installer 108 Anti legionella Hour 0 23 0 Hour 2 Installer 18...

Страница 61: ...r 159 Delay Per Stop Next Blr 0 1275 1275 Sec 2 Installer 160 Delay Quick Start Next 0 1275 400 Sec 2 Installer 161 Delay Quick Stop Next 0 1275 240 Sec 2 Installer 162 Hyst Down Start Boiler 0 40 5 C...

Страница 62: ...Temp lower than Setpoint Module CH ow is above min_ ow Demand Still active Post Pump timer nished or no longer priority Is the supply Temp Above the module setpoint Hyst Up Is the supply Temp Above th...

Страница 63: ...Purge 0 Pre Purge 1 Fan on ignition speed Blocking error Pre ignition on Ignite ignition on Gas Valve open Flame Proving Checking ame Locking error Burn Fan on ignition speed within time Flame Current...

Страница 64: ...Air damper open First module active Post pump ready Locking error Boiler in stand by Locking error Blocking error Clear demand Remove all active modules Turn First module on immediately Remove module...

Страница 65: ...BOILER ADD REMOVE MODULE Add module function Delay period for starting new module is 0 Air damper open Are we allowed to add another dependent YES YES YES Add dependent to the cascade demand Open Air...

Страница 66: ...oint add fast System Temp lower than Setpoint add First boiler active Post pump ready Locking error System in stand by Locking error Blocking error Clear demand Remove all active boilers Turn on rst b...

Страница 67: ...or starting new boiler is 0 Are we allowed to add another dependent Are we allowed to remove another dependent YES YES YES YES Remove dependent from the cascade demand Remove dependent from the cascad...

Страница 68: ...r is closed Supply return Flue sensor are OK Module LWCO detects water Flue condensate pressure sitch closed State burn Flue gas Temp above the max_ ue_gas_temp YES YES YES YES YES YES YES Stand by Lo...

Страница 69: ...69...

Страница 70: ...70...

Страница 71: ...71...

Страница 72: ...A 02043 2165 Meadowpine Blvd Mississauga Ontario Canada L5N 6H6 Tel 905 542 0303 www riello com North America www rielloboilers com The manufacturer strives to continuously improve all products Appea...

Отзывы: