49
SHUTDOWN
49
APPENDIX
Error no. Error
Description
Checks
Solutions
129
DHW_SHORTED
DHW sensor shorted
a- Check the integrity of the
wire connections;
b- Check the DHW
temperature sensor.
a- If the wiring is damaged,
replace it;
b- Verify that the
temperature sensor has the
correct resistance values. If
values are incorrect sensor
must be replaced.
130
FLUE_SHORTED
Flue sensor shorted
132
OUTDOOR_SHORTED
Outdoor sensor shorted
a- Check the integrity of the
wire connections;
b- Check the Outdoor
temperature sensor.
a- If the wiring is damaged,
replace it;
b- Verify that the
temperature sensor has the
correct resistance values. If
values are incorrect sensor
must be replaced.
133
RESET_BUTTON_ERROR
Too many resets in a short
time period
135
T_EXCHANGE_BLOCK_ERROR
Exchange temperature
exceeded 90°C
141
T_SELECTION3_OPEN
Selection 3 sensor open
142
T_OPTIONAL1_OPEN
Optional 1 sensor open
143
T_OPTIONAL2_OPEN
Optional 2 sensor open
144
T_AMBIENT_OPEN
Ambient sensor open
145
T_CHIMNEY_CLOSED
Chimney sensor shorted
155
FLUE_PRESSURE_ERROR
Flue pressure switch is closed
a- Check flue for
obstructions. Clear if found.
b- Check flue pressure
to ensure flue has been
installed and sized properly.
c- Flue pressure switch
default to 2.2”wc.
a- Remove any obstructions
from the exhaust system;
b- Remove any obstruction
from condensate discharge
and confirm the condensate
can flow freely.
156
AIR_DAMPER_ERROR
Air Damper feedback is not
received when the relative
output is closed
162
FLUE_BLOCKED
Flue is blocked, demand
needs to be stopped with
fan at ignition speed, but no
error needed to be stored at
this time
163
LOWEXFLOW_PROTECTION
Flow is too low, demand
needs to be stopped with
fan at ignition speed, but no
error needed to be stored at
this time
a- Flow through the module
is below recommended rate.
b- Check to ensure module
pump is running.
c- Verify valves are open.
d- Possible air entrapment.
WARNINGS
Error no. Error
Description
Checks
Solutions
200
CC_LOSS_COMMUNICATION
Cascade System: Leading
burner lost communication
with one of the depending
burners
a- Check wiring and
connections on individual
Modules.
b- Make sure both controllers
in the boiler are powered on.
c- Make sure Parameter 147
set to 2.
d- Check the position of the
S1 switches on the dependent
module to make sure it is off.
Содержание Array AR 3000
Страница 1: ...cod Doc 0079789 rev 5 09 2018 Array AR 3000 AR 4000 US INSTALLATION AND OPERATION MANUAL...
Страница 39: ...39 SHUTDOWN 39 APPENDIX WIRING DIAGRAM DEPENDENT 5 6 7 8 RIGHT DOOR...
Страница 69: ...69...
Страница 70: ...70...
Страница 71: ...71...