31
20190798
GB
Maintenance
Combustion head
Open the burner and make sure that all components of the
combustion head are in good condition, not deformed by the
high temperatures, free of impurities from the surroundings
and correctly positioned.
If in doubt, disassemble the elbow 5)(Fig. 38).
Gas filter
Change the gas filter when it is dirty.
Flame inspection window
Clean the glass of the flame inspection window (Fig. 39).
Combustion
Carry out an analysis of the combustion flue gases.
Significant differences with respect to the previous
measurements indicate the points where most care should be
exercised during maintenance.
If the combustion values measured before starting maintenance
do not comply with applicable Standards or do not indicate
efficient combustion, consult the Tab. H or contact our Technical
Support Service to implement the necessary adjustments.
It is advisable to set the burner according to the type of gas used
and following the indications in Tab. H.
Tab. H
6.2.4
Safety components
The safety components should be replaced at the end of their life
cycle indicated in the following table.
Tab. I
EN 676
Air excess
Max. output
1.2
Min. output
1.3
GAS
CO
2
theoretic
al max. 0% O
2
CO
2
% Calibration
CO
NO
X
= 1.2
= 1.3
mg/kWh mg/kWh
G 20
11.7
9.7
9.0
100
170
G 25
11.5
9.5
8.8
100
170
G 31
13.7
11.4
10.5
100
230
10
8
7
6
1 3
4
1
2
5
Fig. 38
D3824
D709
Fig. 39
ATTENTION
The specified life cycles do not refer to the
warranty terms indicated in the delivery or
payment conditions.
Safety component
Life cycle
Flame control
10 years or 250.000
operation cycles
Flame sensor
10 years or 250.000
operation cycles
Gas valves (solenoid)
10 years or 250.000
operation cycles
Pressure switches
10 years or 250.000
operation cycles
Pressure adjuster
15 years
Servomotor (electronic
cam)(if any)
10 years or 250.000
operation cycles
Oil valve (solenoid)(if any)
10 years or 250.000
operation cycles
Oil regulator (if present)
10 years or 250.000
operation cycles
Oil pipes/ couplings
(metallic) (if present)
10 years
Flexible hoses (if present)
5 years or 30.000 pressurised
cycles
Fan impeller
10 years or 500.000 start-ups