15
20190798
GB
Installation
4.4
Operating position
4.5
Opening the burner
4.6
Preparing the boiler
4.6.1
Boring the boiler plate
Pierce the closing plate of the combustion chamber, as in Fig. 10.
The position of the threaded holes can be marked using the
thermal insulation screen supplied with the burner.
Tab. F
4.6.2
Blast tube length
The length of the blast tube must be selected according to the
indications provided by the manufacturer of the boiler, and in any
case it must be greater than the thickness of the boiler door
complete with its fettling.
The available length L (mm) is 376 mm.
For boilers with front flue passes 15)(Fig. 11), or flame inversion
chamber, a protection in refractory material 13)(Fig. 11) must be
inserted between the boiler fettling 14) and the blast tube
12)(Fig. 11).
This protection must not compromise the extraction of the blast
tube.
For boilers with water-cooled front piece, the refractory protection
13-14)(Fig. 11) is not necessary, unless specifically requested by
the boiler manufacturer.
ATTENTION
The burner is designed to operate only in
positions
1
,
2
,
3
and
4
(Fig. 9).
Installation
1
is preferable, as it is the only
one that allows the maintenance operations
as described in this manual.
Installations
2
,
3
and
4
allow operation but
make maintenance and inspection of the
combustion head more difficult.
DANGER
Any other position could compromise the
correct operation of the appliance.
Installation
5
is forbidden for safety reasons.
Fig. 9
2
3
4
5
1
D7739
DANGER
Disconnect the electrical supply from the burner
by means of the system main switch.
DANGER
Close the fuel shut-off valve.
Wait for the components in contact with heat
sources to cool down completely.
Model
D1
DF
RS 250/M MZ
230
325 - 368
M16
Ø
45
45
D F
D 1
Fig. 10
20149117
10
8
7
6
4
3
11 15
14
13
12
L
15
9
5
2
1
100 mm
Fig. 11
D3808
Содержание 20190698
Страница 2: ...Translation of the original instructions...
Страница 40: ...20190798 38 GB Appendix Electrical panel layout 0 0 1 1 2 34 5 6 7 8 5 1 9 7 6 8 7 7 7 7 6 6 0 1 0...
Страница 43: ......