![Riello 20190698 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/riello/20190698/20190698_installation-use-and-maintenance-instructions_1460039021.webp)
19
20190798
GB
Installation
4.12
Closing the burner
Once the combustion head adjustment is completed:
reassemble the burner on slide bars 3)(Fig. 19), about 100
mm from the pipe coupling 4)(Fig. 19);
insert the probe cable and the electrode cable, then slide the
burner as far as the pipe coupling.
Refit screws 2) on slide bars 3).
Fix the burner to the pipe coupling with screws 1)(Fig. 19).
Reconnect the articulated coupling 7) to the graduated
sector 6)(Fig. 19).
ATTENTION
When fitting the burner on the two slide bars, it is
advisable to gently draw out the high voltage
cable and the flame detection probe cable until
they are slightly stretched.
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.
2
3
1
4
7
6
Fig. 19
D3813
Содержание 20190698
Страница 2: ...Translation of the original instructions...
Страница 40: ...20190798 38 GB Appendix Electrical panel layout 0 0 1 1 2 34 5 6 7 8 5 1 9 7 6 8 7 7 7 7 6 6 0 1 0...
Страница 43: ......