INSTALLER
38
CONDENSATE NEUTRALISER
b
The connection pipes used must be as short and
straight as possible. Any curves or sharp bends can
lead to the hoses becoming clogged and can therefore
prevent proper condensate discharge.
TYPE N2 NEUTRALISATION UNIT
The TYPE N2 neutralisation unit was designed for systems
equipped with the central heating plant condensate outlet
trap located lower than the boiler condensate outlet. This
neutralisation kits does not require electric connections.
The inlet fitting (A) of the N2 neutralisation unit (the lower
fitting) must be connected to the boiler condensate drain
using the flexible hose (C) supplied with the unit. This con-
densate drain hose is specially made to prevent combustion
fumes escaping into the atmosphere.
The outlet fitting (B) of the neutralisation unit (the top fitting)
must be connected to the boiler room’s waste water drain pit
using another section of flexible hose (not supplied).
b
The central heating system's condensate drain pit
must be located at a lower level than the fitting (B) on
the neutralisation unit.
N2
Type
Qt y.
granulate
Dimensions
(mm)
Ø
fittings
N2
25 kg
400x300x220
1"
A
B
C
If it necessary to neutralise the condensate produced in
the flue pipe, it is recommended that the boiler's and flue
pipe's condensate outlet be connected with a "T" fitting
and then bring it to the input of the N2 neutraliser.
b
Make sure that you tighten the hose clamps sufficient-
ly.
NEUTRALISATION UNIT TYPE HN2 (with pump)
The TYPE HN2 neutralisation unit was designed for systems
equipped with the central heating plant condensate outlet
trap located higher than the boiler condensate outlet.
The pump is controlled by an electric level contact with
which the HN2 neutralisation unit is fitted.
Refer to the instructions provided to connect these neutral-
isation units up electrically. The electrical protection rating
is IP44.
(*) with panel = 3m
Type
Consumption
(W)
Electrical
(V-Hz)
Condensate
output
(l/m) (*)
Dimensions
(mm)
Qt y.
granulate
(kg)
Ø
fittings
HN2
50
230-50
12
400x300x220
25
1"