TECHNICAL ASSISTANCE CENTRE
59
INFORMATION DISPLAY MENU
To access the information display menu, a starting with
the standard display, press button
i
; in the small digits
at the top the page number of the current display will
appear, while in the large digits the current value of the
corresponding information will appear.
Pressing button
i
it is possible to pass on to the next
information.
Having reached the last page, you return to the starting
page. To exit the information display menu, press the
"
Mode
" button.
The list of information that can be displayed is shown in
the table below.
INFORMATION DISPLAY
Page number Description
1
Storage cylinder sensor temperature. If the storage cylinder thermostat mode has been set the
symbol “- -” is displayed
2
Return sensor temperature
3
Flue gas probe temperature
4
outdoor temperature sensor. If no device is connected, the symbol “- -” is displayed
5
Output percentage requested from the modules. In the event of strategy B the information regarding
the last module on is displayed.
6
Number of modules connected in cascade.
7
Number of modules connected not malfunctioning.
8
Total output in kW currently delivered by the system.
9
Address of the leader module for strategy B.
10
Output percentage that will be sent to the modules at the next request from the sequencer.
11
Current strategy. 0 indicates strategy A, 1 indicates strategy B.
12
Heating set temperature set using the 0-10Vdc input. If there are no
devices connected at the input, the symbol “- -” is displayed.
13
Number of steady state SIC712 modules
14
Number of SIC712 modules available to the system (active, not malfunctioning)
15
Average outdoor temperature over the last 10 hours
16
Heating delivery setpoint calculated on the basis of the weather curves
17
Effective working output of address 1 module
18
Effective working output of address 2 module
19
Effective working output of address 3 module
20
Effective working output of address 4 module
21
Effective working output of address 5 module
22
Effective working output of address 6 module
23
Effective working output of address 7 module
24
Effective working output of address 8 module