Start-up, calibration and operation of the burner
8.10 Programming menu
The programming menu can only be accessed via the reset push-
button or the remote reset during OPERATION.
If in page menu the reset push-button is not pressed, after 10
seconds occur automatic exit and there is a green led blinking for
the value set.
If the number of pressures on the push-button exceeds the max-
imum allowable, the value in memory will remain the maximum
one.
If the push-button or remote reset is pressed for more than 60
seconds, a failure of the push-button will be visualised and the
control-box will restart.
BLOCK DIAGRAM FOR ENTERING THE MENU
Tab. F
8.10.1 Shutdown test
Sequence for shutdown test
Programming allowed in OPERATION.
Press the button for 5 sec.
t < 10 sec.
The RED LED blinks twice (0.2 sec. ON; 0.2 sec. OFF)
Release the button
The burner will initialise a shutdown followed by a restart
After shutdown, the burner restarts automatically and the number
of recycling attempts is restored.
At the exit of shutdown test page menu there are no leds flashing.
8.10.2 Light diagnosis
Sequence for enable/disable
Programming allowed in OPERATION.
Press the button for 15 sec.
t < 20 sec.
GREEN led flashing 2 times
Release the button
GREEN led OFF
Press push-button 1 time for enable or 2 times for disable
function
(*)
GREEN led ON and OFF at every press and release
After 10 sec., the GREEN LED will blink for the number of
times programmed (0.5 sec. ON; 0.5 sec. OFF).
8.10.3 Intermittent operation
Sequence for enable/disable
Programming allowed in OPERATION.
Press the button for 20 sec.
t < 25 sec.
GREEN led flashing 3 times
Release the button
GREEN led OFF
Press push-button 1 time for disable function
(*)
Press the button twice to enable a shutdown every 1 hour
(*)
Press the button 3 times to enable a shutdown every 24
hours
(*)
GREEN led ON and OFF at every press and release
After 10 sec., the GREEN LED will blink for the number of
times programmed (0.5 sec. ON; 0.5 sec. OFF)
The modification of the intermittent operation setting parameter
takes effect:
Function
Button release
time
No. of Led
blinks per
menu page
No. of pressings
of the reset push-button
No. of Led
blinks (green)
Quitting the menu
Shutdown test
5s
t < 10s
2 blinks
RED
/
none
/
none
Automatic, at the
end of the blinking
Light diagnosis
15s
t < 20s
2 blinks
GREEN
1 = enabled
2 = disabled (default)
1 blink
2 blink
10 sec. after the release of
the button
Intermittent
operation
20s
t < 25s
3 blinks
GREEN
1 = 0 disabled
2 = 1 hour
3 = 24 hours (default)
1 blink
2 blink
3 blink
10 sec. after the release of
the button
Last lockout
memorised
25s
t < 30s
4 blinks
GREEN
/
none
Displaying the type
of lockout accord-
ing to the table sec-
tion 8.8.2
10 sec. after the release of
the button
OPERATION (WITH FLAME)
SWITCHING OFF
INTERMITTENT
OPERATION
2 RED
2 GREEN
3 GREEN
AUTOMATIC
OUTLET
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
TEST
BRIGHTNESS
DIAGNOSIS
20 SECS.
LAST LOCKOUT
MEMORISED
25 SECS.
4 GREEN
10 SEC. AFTER
RELEASE
S9155
5 SECS.
15 SEC.
BURNER STATE
TYPE OF
FUNCTION
NUMBER
OUTLET
OF BLINKS
Fig. 24