BURNERS - BRUCIATORI - BRULERS - BRENNER - QUEMADORES - 

ГОРЕЛКИ

MANUAL OF INSTALLATION - USE - MAINTENANCE

G258A
G335A
G380A
G400A

Gas - Light oil burners

LMV 2x/3x

 

Microprocessor controlled

Содержание G335A

Страница 1: ...M039530CA 0 1 07 2023 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES MANUAL OF INSTALLATION USE MAINTENANCE G258A G335A G380A G400A Gas Light oil burners LMV 2x 3x Microprocessor controlled...

Страница 2: ...e employed exclusively for the use for which it was designed Before connecting the burner make sure that the unit rating is the same as delivery mains electricity gas oil or other fuel Observe caution...

Страница 3: ...ixtures DIRECTIVES AND STANDARDS Gas burners European directives Regulation 2016 426 UE appliances burning gaseous fuels 2014 35 UE Low Tension Directive 2014 30 UE Electromagnetic compatibility Direc...

Страница 4: ...quipment of machi nes EN 60335 2 Electrical equipment of non electric appliances for house hold and similar purposes Safety requirements Burner data plate For the following information please refer to...

Страница 5: ...tion is to transfer oil from the tank to the nozzle in the desired quantity and pressure To adjust this pressure pumps are provided with a pressure regulator except for some models for which a separat...

Страница 6: ...TRY see data plate 6 BURNER VERSION A Standard Y Special 7 EQUIPMENT 0 2 gas valves 1 2 gas valves gas proving system 7 2 gas valves maximum gas pressure switch 8 2 gas valves gas proving system maxim...

Страница 7: ...40 Power supply triphase 220 V 230 V 3 380 V 400 V 3N 50 Hz Auxiliary Power supply 220 V 230 V 2 220 V 230 V 1N 50 Hz Total power consumption kW 5 6 7 1 9 1 Pump motor kW 1 1 1 1 1 1 Electric motor kW...

Страница 8: ...210 190 G335A 100 1547 181 850 372 35 271 592 145 460 395 1087 509 1499 1085 414 254 290 447 380 518 M12 453 300 340 320 791 148 642 942 353 708 210 190 G380A 50 1486 181 850 372 35 271 550 100 490 39...

Страница 9: ...or 6 Solenoid valve 6 1 Solenoid valve 10 Oil distributor 12 Pressure gauge 13 Pressure governor 15 Pressure switch 16 One way valve 16 1 One way valve 18 Flexible hose 19 Manual valve 20 Pressure gau...

Страница 10: ...lue upstream the burner s gas valve Then subtract the backpressure The result is called pgas Draw a vertical line matching the furnace input value 600kW in the example quoted on the x axis as far as i...

Страница 11: ...gas flow rate curvesPerformance Curves GAS PRESSURE mbar G258A MG Stm3 h G335A MG Stm3 h GAS PRESSURE mbar G380A MG Stm3 h G400A MG Stm3 h ATTENTION the gas rate value is quoted on the x axis the rela...

Страница 12: ...sure in the combustion head insert the pressure gauge probes one into the combustion chamber s pres sure outlet to get the pressure in the combustion chamber and the other one into the butterfly valve...

Страница 13: ...ssure burner head vs natural gas flow rate Curves are referred to pressure 0 mbar in the combustion chamber Gas pressure in combustion head G258A M Stm3 h G335A M Stm3 h Gas pressure in combustion hea...

Страница 14: ...se dimensions are 1600mm x 1000mm x 860 mm L x P x H Such packages fear moisture and are not suitable for stacking Packing cases of this type are affected by humidity and are not suitable for stacking...

Страница 15: ...supplier to verify that a correct matching is possible with respect of the application involved To correctly match the burner to the boiler verify the type of the blast tube Verify the necessary inpu...

Страница 16: ...diagrams are in compliance with the current laws Gas train with valves group VGD and MBE with built in gas pressure governor gas leakage pressure switch PGCP Legend WARNING before executing the conne...

Страница 17: ...B DLE 10 Manual valve optional MULTIBLOC DUNGS MB DLE 405 412 MB DLE 415 420 Mounting 1 Mount flange onto tube lines use appropriate sealing agent 2 Insert MB DLE note position of O rings 3 Remove Mul...

Страница 18: ...oried by min and max pressure switches set to 20 of the setpoint 2 Mounting on pipe Sensor position 5x DN according to MBE Pipe fitting with female thread size mount sensor with seal observe torque 3...

Страница 19: ...ilizer Caution the SKP2 diaphragm D must be vertical WARNING removing the four screws BS causes the device to be unserviceable SA SA TP D BS SKP1 SKP2 SIEMENS VGD Mounting positions TP Siemens VGD con...

Страница 20: ...ct the gas valves group and pressure switches plugs Overall dimensions mm BURNERS WITH INVERTER VARIANT if provided ATTENTION it is reccomended to install the filter with gas flow parallel to the floo...

Страница 21: ...s and with a signal in 0 10V controls it through the inverter Generally the curve of the inverter goes from 50 to 100 of the engine revolutions This in addition to improving the setting of the burner...

Страница 22: ...controls it through the inverter Generally the curve of the inverter goes from 50 to 100 of the engine revolutions This in addition to improving the setting of the burner also allows a saving on the c...

Страница 23: ...and keep this position for a preset time td3 in order to fill the test space Test gas pressure EV1 closes and keep this position for a preset time td2 The pressure switch PGCP has not to detect a pre...

Страница 24: ...be suited for single pipe system recommended in the case of gravity feed as decribed before To change from a 1 pipe system to a 2 pipe system insert the by pass plug G as for ccw rota tion referring t...

Страница 25: ...e nozzle reducing efficiency Always use O Rings or mechanical seal copper or aluminium gaskets jun ctions if possible An external filter should always be installed in the suction line upstream the fue...

Страница 26: ...e pump being careful to avoid exchanging the lines see the arrows marked on the pump For further information refer to the technical documentation of the pump Diesel filters Suntec TA Oil viscosity 3 7...

Страница 27: ...it breaker WARNING It is forbidden to use the fuel pipes for the execution and or completion of the grounding The system must comply with the current regulations Earth the system always check in advan...

Страница 28: ...time of the offer contract Provide sufficient protections for cables and connectors taking into consideration positioning spaces and the panel burner tracing sur faces Always consult beforehand the el...

Страница 29: ...ING WITH THESE E G DISCONNECTION EVEN PARTIAL OF THE ELECTRICAL LEADS OPENING THE GENERATOR DOOR DISMANTLING OF PART OF THE BURNER NEVER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE EXCEPT FOR ITS M...

Страница 30: ...he control box drives the actuator opening and when the maximum opening position is reached the pre purge time counting starts At the end of the pre purge time the actuator is in the light oil ignitio...

Страница 31: ...ratio curvepoints see the LMV related manual Set now the low flame output according to the procedure described on the Siemens LMV manual in order to avoid the low flame output increasing too much or...

Страница 32: ...gised 6 Fan motor energised 7 Ignition transformers energised 8 Open valves 9 Flame 10 Lock unlock codes 11 Closing actuator 12 Opening actuator 13 Unit measure 14 Key F A While pressing the two keys...

Страница 33: ...curezza trasformatore accensione ON TSA1 1st safety time ignition transformer ON Ph42 TSA1 primo tempo sicurezza trasformatore accensione OFF TSA1 1st safety time ignition transformer OFF t42 preignit...

Страница 34: ...omplete visualisation press enter again the data will be completely shown for 1 to 3 seconds By pressing enter or and at the same time the system will exit the parameter visualisation and go back to t...

Страница 35: ...s orto return to the normal display If a message like the one below is shown during operation it means that the burner is locked out and the Errore code is shown in the example error code 4 this messa...

Страница 36: ...is accessed 143 by pressing the End message will blink 3 PressPress InFo for more than three seconds or for more than three seconds orto return to the normal display For further nformation see tha LM...

Страница 37: ...1 NOZZLE SUPPLY PRESSURE 25 bar Atomisation angle according to the return pressure _________ Flow rate ATTENTION To achieve the maximum flow rate close completely the return line FLOW RATE kg h DIMENS...

Страница 38: ...PART III OPERATION 38 FLUIDICS KW3 60 NOZZLE SUPPLY PRESSURE 20 bar VISCOSITY AT NOZZLE 5 cSt Pressure on return bar Flow rate kg h The nominal size of the nozzle is indicated at the ends of the curve...

Страница 39: ...RESSURE 20 bar VISCOSITY AT NOZZLE 5 cS Pressure on return bar Flow rate kg h Pressure on return bar Flow rate kg h The nominal size of the nozzle is indicated at the ends of the curve The nominal siz...

Страница 40: ...eturn bar Flow rate kg h The nominal size of the nozzle is indicated at the ends of the curve Pressure on return bar Flow rate kg h The nominal size of the nozzle is indicated at the ends of the curve...

Страница 41: ...wise rotation reduces start flow rate anticlockwise rotation incre ases it Do not use a screwdriver on the screw VR The pressure stabilizer is adjusted by operating the screw VS located under the cove...

Страница 42: ...requires PS 10 40 or PS 50 200 Outlet pressure MIN 10 25 50 75 MAX PS 10 40 4 mbar 0 4 kPa 2 w c 10 mbar 1 0 kPa 4 w c 25 mbar 2 5 kPa 10 w c 50 mbar 5 0 kPa 20 w c 75 mbar 7 5 kPa 30 w c 100 mbar 10...

Страница 43: ...Refit the transparent plastic cover on the pressure switch Calibration the maximum gas pressure switch when provided To calibrate the maximum pressure switch proceed as follows according to its mounti...

Страница 44: ...position must be regulated in the plant during the commissioning The factory setting depends on the type of fuel for which the burner is designed For natural gas burners plate holes are fully opened...

Страница 45: ...accepted Examination of ignition electrodes cleaning possible adjustment and if necessary replacement Check the detection electrode photocell depending on burner model clean adjust if necessary and re...

Страница 46: ...D E F F E 1 3 4 6 T 2 A r re 5 T 1 3 pe 0 pa 5 pBr 0 3 pe pa 6 5 pBr 1 1 0 5 3 6 2 2 Prese di pressione MB DLE 415 420 B01 MB DLE 405 412 0 1 2 3 4 5 2 pe pBr 2 pe 3 pa pBr 5 0 3 pa 2 3 5 0 Check the...

Страница 47: ...he top H 2 Remove the UV detector out of its housing disconnect electrode cables and the light oil flexible hoses 3 Loosen the screws V holding the gas manifold G loosen the connectors E 4 Some models...

Страница 48: ...ombustion head ATTENTION avoid the electrodes to get in touch with metallic parts blast tube head etc otherwise the boiler operation would be compromised Check the electrodes position after any interv...

Страница 49: ...it if necessary 3 after removing the oil gun unscrew the nozzle and replace it if necessary 4 in order to replace the electrodes unscrew the VE fixing screws and remove them place the new electrodes...

Страница 50: ...decrease in performance The owner makes the decision whether to finish using the burner or replacing and disposing of it based on the actual state of the appliance and any repair costs The use of the...

Страница 51: ...witch functions and links Burner control damaged Replace burner control BURNER LOCKS OUT WITHOUT ANY GAS FLOW Gas valves don t open Check voltage on valves if necessary replace valve or the burner con...

Страница 52: ...of cables in the ignition transformer or into the electrodes Improve the installation Ignition transformer damaged Replace the transformer PUMP TOO NOISY Suction too high over 0 35 bar dirty filters...

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ...a L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors an...

Страница 57: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...

Страница 58: ...900 Process data 32 Actuators references 33 Gas proving system 33 Air fuel curve points 33 COMMISSIONING THE BURNER 34 Warm setting 38 Cold setting 39 BURNER STARTUP WITH LMV2x ALREADY PROGRAMMED 40...

Страница 59: ...CTIONS FOR BURNERS z The burner should be installed in a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only b...

Страница 60: ...ditions such as the development of toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 2009 142 EC Gas Appliances Directive 2006 95 EC on low voltage Directi...

Страница 61: ...apparatus EN 50165 Electrical equipment of non electric appliances for household and similar purposes Safety requirements UNI EN 746 2 Industrial thermoprocessing equipment Burner data plate For the...

Страница 62: ...forms all the burner control functions and of the Siemens AZL local programming unit that interfaces the system with the user Keys 1 Burner 2 AZL2 3 Air actuator 4 Fuel actuator 5 LMV2 User interface...

Страница 63: ...ice mode Info and Enter keys Used for Info and Service menues Used as Enter key in the setting modes Used as Reset key in the burner operation mode Used to enter a lower level menu Key Used to decreas...

Страница 64: ...8 Parameters level heating engineer...

Страница 65: ...ription Password 000 Internal parameters OEM Service 100 Informazioni generali General OEM Service Info 200 Controllo bruciatore Burner control OEM Service 300 Controllo bruciatore solo LMV26 Burner c...

Страница 66: ...kup data set Service Info Param Descrizione Description Password LMV20 LMV27 LMV26 LMV37 102 Data produzione in gg mm aa Identification date yy mm dd Service Info x x x 103 Numero identificativ Identi...

Страница 67: ...ed OEM Service x x 145 Indirizzo dispositivo per Modbus Device address for Modbus OEM Service x x 146 Velocit di trasmissione per Modbus Baud rate for Modbus OEM Service x x 147 Parit per Modbus Parit...

Страница 68: ...erci zio azzerabile da Service Fuel 1 Operation hours resettable Service Info x 174 Fuel 1 secondo combustibile Numero di partenze azzerabile da Service Fuel 1 Number of startups resettable Service In...

Страница 69: ...e fuel train modula ting multistage actuators etc __ undefined delete curves 1 gas direct ignition G mod 2 ignition by gas pilot connected between the two gas solenoid valves EV1 EV2 Gp1 mod 3 ignitio...

Страница 70: ...x x x 210 Allarme impedimento avviamento 0 non attivo 1 attivo Alarm in the event of start prevention 0 deactivated 1 activated OEM Service x x x 211 Tempo aumento giri ventilatore valore fab brica 2...

Страница 71: ...nge impostazione 20s 60min Gas Prepurge time default value 20s range 20s 60min OEM Service x x x 226 Gas tempo di preaccensione valore fab brica 2s range impostazione 0 2s 60min Gas Preignition time d...

Страница 72: ...ivo 1 esso modificabile solo su LMV37 Dal punto di vista della sicurezza il funzionamento continuo valido esclusiva mente per bruciatori di gas con elettrodo di rilevazione Gas Forced intermittent ope...

Страница 73: ...Postpurge time 3 abortion with load controller LR ON OEM Service x x x 261 Olio sonda rilevazione fiamma attivo valore fabbrica 0 0 QRB QRC 1 ION QRA Oil active detector flame evaluation default value...

Страница 74: ...0 inactive 1 active from phase 38 2 active from safety time TSA OEM Service x x 277 Olio Pressostato olio di massima ingresso POC 0 inattivo 1 pressostato olio di massima 2 POC Oil Pressure switch max...

Страница 75: ...lvole EV1 EV2 del gas regolazione pneumatica Gp1 mod pneu 9 accensione tramite pilota gas con attacco a monte dell elettrovalvola EV1 del gas regolazione pneumatica Gp2 mod pneu 10 olio modulante con...

Страница 76: ...ore fabbrica 1 0 QRB QRC 1 ION QRA Fuel 1 Gas active detector flame evalua tion default value 1 0 QRB QRC 1 ION QRA OEM Service x 322 Combustibile 1 Gas Preventilazione valore fabbrica 1 1 attivo 0 no...

Страница 77: ...Intervallo 2 valore fabbrica 2s range impostazione 0 2s 60min Fuel 1 Gas Interval 2 default value 2s range 0 2s 60min OEM Service x 333 Combustibile 1 Gas Tempo postcombu stione valore fabbrica 8s ra...

Страница 78: ...t filling time default value 3s range 0 2s 10s OEM x 345 Combustibile 1 Gas tempo test pressione gas valore fabbrica 10s range imposta zione 0 2s 60s Fuel 1 Gas proving test time gas pres sure default...

Страница 79: ...mbustibile 1 Olio tempo di risposta a cadute di pressione entro TSA1 e TSA2 valore fabbrica 1 8s range imposta zione 0 2s 14 8s Fuel 1 Oil time to respond to pressure faults in TSA1 and TSA2 default v...

Страница 80: ...censione corta Ph38 fase pro gramma 38 1 preaccensione lunga con ventilatore Ph22 fase programma 22 Fuel 1 Oil time oil ignition default value 1 0 short preignition Ph38 progr phase 38 1 long preignit...

Страница 81: ...ting the cur ves OEM Service x x x 403 Curve controllo inverter F A si accede alla lista dei punti da impostare da P0 a P9 con sultare paragrafo Impostazione curve Ratio control curves VSD curve setti...

Страница 82: ...repurge speed 100 Index 2 postpurge speed 50 OEM Service x x 504 Combustibile 1 Posizione servocomando combustibile in assenza di fiamma no flame Indice 0 posizione di sosta 0 Indice 1 posizione preve...

Страница 83: ...di carico per modulazione valore fabbrica n d range imposta zione 20 100 Lower load limit default value n d range 20 100 OEM Service x x x 546 Percentuale massima di carico per modula zione valore fa...

Страница 84: ...0 combustibile Indice 1 aria Tolerance limit of position monitoring 0 1 Index 0 fuel Index 1 air OEM Service x x x 608 Combustibile 1 Impostazione punto di riferi mento Indice 0 combustibile Indice 1...

Страница 85: ...top SQN1 3 both OEM x 613 Tipo di servocomando Indice 0 combustibile Indice 1 aria 0 5s 90 1Nm 1 2Nm 3Nm 1 10s 90 6Nm 2 17s 90 10Nm Type of actuator Index 0 fuel Index 1 air 0 5 s 90 1Nm 1 2Nm 3Nm 1 1...

Страница 86: ...tion of analog output default value 0 0 DC 0 10 V 1 DC 2 10 V 2 DC 0 2 10 V OEM Service LMV27 x x ATTENTION as for SQM3x actuators set the direction according to the acutator function As far as SQN1x...

Страница 87: ...ror history 701 725 02 diagnostic code Service Info Storico errori 701 725 03 classe errore Error history 701 725 03 error class Service Info Storico errori 701 725 04 fase Error history 701 725 04 ph...

Страница 88: ...Active load source OEM Service 945 Solo con LMV26 Combustibile attuale 0 combustibile 0 1 combustibile 1 Actual fuel 0 fuel 0 1 fuel 1 Service Info 947 Risultato interrogazione contatti codifica bit...

Страница 89: ...a leakage test designed to detect leaking gas valves and if necessary to pre vent the valves from opening or ignition from being switched on Lockout is initiated When performing valve proving the gas...

Страница 90: ...2x already programmed At the first LMV startup the AZL display will show It means that the unit was never set or that no mode was chisen or that some parameters have to be set furthert Push F fuel and...

Страница 91: ...l elettrov EV1 del gas Gp2 mod 4 accensione a gasolio modul Lo mod 5 accens a gasolio bistadio Lo 2 stage 6 accens a gasolio tristadio Lo 3 stage Burner operating mode fuel train mod multi stage actua...

Страница 92: ...e fuel actuator 0F until the requested value is reached for example 12 15 see below for the ignition point or press F and to decrease the angle To set the air damper opening angle 0A in the ignition p...

Страница 93: ...er is operating warm setting by pressing the ENTER InFo or while the burner is in stand by mode cold setting by pressing ENTER CAUTION at the first burner adjustment it is recommended to set the maxim...

Страница 94: ...ugh the flue analyser Keep the air excess inside normal figures from 3 to 7 residual O2 operating by means for the air damper servomotor Keep increasing the air damper opening and then the gas throttl...

Страница 95: ...t before end by pressing ESC or for a faulty shutdown the message OFF UPr Start preven tion will be diplayed until all the curvepoints will be set Note2 if the gas flow rate at high flame point maximu...

Страница 96: ...e than 5 seconds to process the curve downwards The curve is then a straight line go on checking the combustion values point by point change them if necessary and in case linearise the curve again Bef...

Страница 97: ...e burntime Ph72 travelling to postpurging Ph74 postpurge countdown is displayed Press ESC the parameter 546 Setting the maximum load is displayed Then press to exit the programming mode The display wi...

Страница 98: ...n Longer or shorter pushes on the button do not produce a reset so that the system maintains the lockout position Timeout for menu operation The time for automatically leaving the parameter setting le...

Страница 99: ...levels By means of a proper use of the keys it is possible to enter the various level parameters as shown in the following flow chart The burner and consequently the LMV2x are factory set the air and...

Страница 100: ...nd go back to the flashing number The Info level shows some basic parameters as 5 Example choose parameter 102 to show the date the display shows parameter 102 flashing on the left and characters _ _...

Страница 101: ...h another message Diagnostic code in the example diagnostic code 3 Record the codes and find out the fault in the Error table To perform the reset press InFo for one second The unit displays an event...

Страница 102: ...ht By pressinf or it is possible to scroll up down the parameter list 2 Once the last parameter is accessed 143 by pressing the End message will blink 3 Press InFo for more than three seconds or for m...

Страница 103: ...ignition time OFF Ph44 t44 intervallo 1 t44 interval 1 Ph50 TSA2 secondo tempo sicurezza TSA2 2nd safety time Ph52 t52 intervallo 2 t52 interval 2 Ph60 Funzionamento 1 stazionario Operation 1 stationa...

Страница 104: ...ess ENTER until the display will show with the button go to the group 000 of the parameters and press with the buttons and go to 050 parameter press the disply show press again with the button select...

Страница 105: ...uttons by pressing enter to confirm iWith the buttons go to the group 000 of the parameters press end select the 050 parameter press the disply show with the button the display shows press again with...

Страница 106: ...50 ERROR CODE TABLE...

Страница 107: ...51...

Страница 108: ...52...

Страница 109: ...53...

Страница 110: ...54...

Страница 111: ...55...

Страница 112: ...56...

Страница 113: ...57...

Страница 114: ...58...

Страница 115: ...59...

Страница 116: ...60...

Страница 117: ...61...

Страница 118: ...62...

Страница 119: ...63...

Страница 120: ...64...

Страница 121: ...L PE QRB C N ION QRB C X75 1 X10 05 1 X10 06 1 X3 02 1 PLUFT FLAMME P L PE N L 2 3 L X5 03 1 X8 04 1 X8 02 1 X5 03 X10 05 X7 01 X8 04 X8 02 X75 X10 06 X3 02 X3 04 N PE L 1 1 1 1 1 1 1 1 1 QRA QRA QRA...

Страница 122: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...

Страница 123: ...tion speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply 4 Feedback signal 3 PWM Pulse Width Modulation speed output 2 GND signal reference 1 External supply 24V DC ConnectorX75 Con...

Страница 124: ...dulation speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply ConnectorX75 ConnectorX64 ConnectorX74 2 Fuel meter input 1 Supply fuel meter ConnectorX5 02 Connections Pmax 4 Feedback...

Страница 125: ......

Страница 126: ......

Страница 127: ......

Страница 128: ...and data subject to change Errors and omissions excepted C I B UNIGAS S p A Via L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail...