background image

 

 

PROTECTION

 

DEVICES

 

AND

 

SAFETY 

E

LECTROMAGNETIC COMPATIBILITY

 

This uninterruptible power supply (UPS) is a product which respects the provisions of class C3 of the standards currently 
in force as regards electromagnetic compatibility.   
 
CAUTION:  
This product is designed for commercial and industrial application in the second environment 

– during installation, it may 

be necessary to add certain restrictions and adopt additional measures in order to prevent disturbances.  
 
 

P

ROTECTION AGAINST OVERVOLTAGE

 

The UPS has been designed to be powered by an AC source with category 2 spike voltage. If the UPS is connected to 
AC  sources  with  different  characteristics  or  if  the  UPS  is  at  risk  of  overvoltage,  even  temporarily,  suitable  external 
protection devices must be installed.  
 
 

P

ROTECTION AGAINST SHORT CIRCUITS

 

 

In the presence of a fault on the load, in order to protect itself, the UPS limits the value and the duration of the current 
supplied (short circuit current). These quantities are also functions of the operating status of the unit at the moment of the 
fault; two different cases can be distinguished:  

 

UPS  in  NORMAL  OPERATION  MODE:  the  load  is  instantly  switched  to  the  bypass  line  (I

2

t=125000A

2

s):  the 

input line is connected to the output without any internal protection (locked after t>0.5s) 

 

UPS in BATTERY OPERATION MODE: the UPS protects itself by supplying output current which is 1.5 times 
the rated current for 0.5s, switching off after this time. 

 

 

 

P

ROTECTION AGAINST BACKFEEDING

 

The UPS is equipped with an internal protection device against backfeeding using metal separation devices.  
 

 

The  UPS  has  an  internal  device  (redundant  bypass  power  supply)  which,  in  the  event  of  a  fault  with  the 
machine,  activates  the bypass  automatically,  ensuring  load  feeding continues  without any  internal  protection 
nor limit of the power supplied to the load. In this emergency condition, any disturbance present on the input 
line also affects the load. See also the 

“Redundant auxiliary power supply for automatic bypass”, paragraph in 

the 

“USE” section. 

 
 

E

XTERNAL PROTECTION DEVICES

 

FUSES / CIRCUIT BREAKERS 

 
On the UPS input line, in a dedicated panel, 

a device to protect against overcurrents must be envisaged

 

This protection device can be created with gG fuses, as shown in the table, or with an equivalent circuit breaker. With a 
separate power input, main line + bypass line, two protection devices are required, one for each line present.  
 

 

External AC protection devices  

UPS model 

Mains input 

Separate bypass input *

 

100 

250A 

250A 

120 

250A 

250A 

*  inside  the  UPS,  on  the  bypass  line,  no  maximum  current  protection  is  envisaged.  This  protection  must  be  envisaged  in  the 
system based on the I2t indications described in the 

“Protection against short circuits” paragraph 

 

 

If the protection device upstream from the UPS interrupts the neutral conductor, it must also interrupt all the 
phase conductors as the same time (four pole switch).  

 

 

Содержание 100 kVA

Страница 1: ...100 120kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEM Riello Multi Plus UPS available from EcoPowerSupplies For more information visit www ecopowersupplies com riello ups...

Страница 2: ...ards to all environmental aspects All our products pursue the objective defined in the environmental management system developed by the company in compliance with standards in force No hazardous mater...

Страница 3: ...CONTENTS PRESENTATION 4 INSTALLATION 8 USE 20 TROUBLESHOOTING 36 TECHNICAL DATA 44...

Страница 4: ...PRESENTATION UPS FRONT VIEWS Control panel with graphic display Front cover panel with ventilation grilles Door handle Switch cover panel Ventilation grille Ext connection area Communication area...

Страница 5: ...AR VIEW Upper board level ventilation fans Battery charger Bypass ventilation fan Compartment ventilation grilles Battery charger Bypass compartment handle Battery charger Bypass compartment Bypass fa...

Страница 6: ...wer share socket fuse Slot for power relay board Cold start IEC connectors connected directly to the output Communication slot 1 Aux switch out contact Communication slot 2 Service bypass R E P O Exte...

Страница 7: ...ss LED Graphic display Stand by alarm LED F1 F2 F3 F4 FUNCTION KEYS The function of each key is shown at the bottom of the display and varies according to the menu ISOLATING SWITCH VIEW SWMB Maintenan...

Страница 8: ...instructions shown on the package Take care when removing the packaging in order to avoid scratching the UPS Remove the stretch film wrapped around the UPS take off the cardboard lid and the HD protec...

Страница 9: ...m 1 front plinth Length 70 6 cm ASSEMBLING THE PLINTHS Take hold of the two 80 6 cm side plinths and 4 burnished knurled screws Secure the two side plinths to the right and left of the UPS To do so us...

Страница 10: ...lation recommended if the external temperature is lower e g 20 C than the temperature at which the UPS or Battery Box is to operate e g 25 C air conditioning system recommended if the external tempera...

Страница 11: ...operate with the earthing system connected The input neutral must always be connected Do not connect the output neutral to the input neutral CAUTION a 4 wire three phase distribution system is requir...

Страница 12: ...as shown in the figure below N B For the input and output connections respect the order from top to bottom as described in the boxes The label marked N present on the terminals identifies the neutral...

Страница 13: ...ECTED THE INPUT AND BYPASS LINES MUST REFER TO THE SAME NEUTRAL POTENTIAL DO NOT CONNECT THE OUTPUT NEUTRAL TO THE INPUT OR BYPASS NEUTRALS N B For the input and output connections respect the order f...

Страница 14: ...te maintenance bypass and remote output switch isolating switches Check the compatibility between the remote maintenance bypass and the system neutral point treatment In the case of several machines i...

Страница 15: ...ELECTRICAL SYSTEM CONNECTION DIAGRAMS UPS without variation of the neutral point treatment UPS with input galvanic isolation UPS with output galvanic isolation...

Страница 16: ...between the SWIN and SWBY isolating switches UPS with input galvanic isolation and separate bypass input Remove the jumpers present between the SWIN and SWBY isolating switches UPS with output galvan...

Страница 17: ...utral point treatment and with separate bypass input connected to an independent power line Remove the jumpers present between the SWIN and SWBY isolating switches UPS with separate bypass input conne...

Страница 18: ...supplying output current which is 1 5 times the rated current for 0 5s switching off after this time PROTECTION AGAINST BACKFEEDING The UPS is equipped with an internal protection device against back...

Страница 19: ...ormer the neutral originating from the mains is connected to the UPS output neutral The system neutral point treatment is not modified THE INPUT NEUTRAL IS CONNECTED TO THE OUTPUT NEUTRAL THE DISTRIBU...

Страница 20: ...ermore some components have their own life cycle and must be checked and replaced if necessary on a periodic basis if their condition makes it necessary in particular the battery the fans and in certa...

Страница 21: ...e installation program instructions For more detailed information regarding installation and use consult the software manual which can be found in the Manuals folder on the CD Rom supplied To check wh...

Страница 22: ...ing switch SWOUT and bypass isolating switch SWBY The maintenance isolating switch SWMB must remain open SWITCHING ON FOR THE FIRST TIME Wait for a few seconds after closing the SWIN Check that the di...

Страница 23: ...inverter To set the Date and Time access menu 8 6 7 see Display menus Use the arrow keys to set the required value and finally confirm by pressing to move on the next field To save the new settings g...

Страница 24: ...is of the memorised capacity value Battery life is linked to the operating temperature and the number of charging and discharging cycles performed The capacity is not constant It increases after a few...

Страница 25: ...the chosen menu UPS STATUS ERRORS FAULTS Area where the UPS operating status is displayed The first line is always active and constantly displays the status of the UPS at that moment The second only b...

Страница 26: ...DISPLAY MENUS...

Страница 27: ...ways powered through the inverter with stabilised voltage and frequency using the energy originating from the input network In this way the bypass line is disabled CAUTION Do not use the SWMB isolatin...

Страница 28: ...r supply the load nevertheless remains powered through the automatic bypass The multiprocessor board and the control panel are not powered therefore the LEDS and the display are off EXTERNAL TEMPERATU...

Страница 29: ...ection of 1 mm Caution respect the polarisation shown in the figure below Pole 1 of the terminal is indicated by a label affixed to the terminal itself After installation it is necessary to enable the...

Страница 30: ...y The duration of the transitory period can be set from 1 to 30 seconds The default value is 10 seconds During the transitory period the power necessary is taken partially from the batteries and parti...

Страница 31: ...um charge Automatic UPS power off in battery operation mode if the charge is lower than 5 Disabled Enabled Disabled CP Autonomy limit Maximum battery operation time Disabled Disabled complete battery...

Страница 32: ...rnal Sync Selects the source of synchronisation for the inverter output From bypass line From bypass line From external input SW Switch on delay Waiting time for automatic power on after the return of...

Страница 33: ...NECTORS RS232 CONNECTOR USB CONNECTOR PIN NAME TYPE SIGNAL PIN SIGNAL 1 IN 1 VBUS 2 TX OUT TX serial line 2 D 3 RX IN RX serial line 3 D 4 4 GND 5 GND POWER 6 OUT 7 8 15V POWER Isolated power supply 1...

Страница 34: ...ge the UPS resumes operation from the inverter If the jumper is removed when no mains power is present the UPS begins to operate from the battery again 4 5 12 BATTERY LOW OUTPUT 1 Signals that the bat...

Страница 35: ...l is emitted when the UPS switches to the bypass in order to compensate for the surge current due to the activation of a distorting load Sound C The signal is emitted when the UPS switches to battery...

Страница 36: ...absence of this connection may damage the UPS and or the load Connect the mains to the terminals as shown in the Installation paragraph THE ISOLATING SWITCH BEHIND THE DOOR SWIN IS OPEN Close the iso...

Страница 37: ...m persists call the nearest assistance centre PHASE 1 HAS MUCH LOWER VOLTAGE THAN THE OTHER TWO PHASES Open SWIN power from the battery wait until the end of the sequence and close SWIN THE DISPLAY SH...

Страница 38: ...T THRESHOLD Wait until the batteries have recharged or force power on in manually from the SYSTEM ON menu THE DISPLAY SHOWS ONE OR MORE OF THE FOLLOWING CODES F06 F07 F08 INPUT STATIC SWITCH SHORT CIR...

Страница 39: ...SHOWS ONE OR MORE OF THE FOLLOWING CODES F37 L37 AMBIENT TEMPERATURE GREATER THAN 40 C HEAT SOURCES IN THE PROXIMITY OF THE UPS AIR SLITS BLOCKED OR TOO CLOSE TO THE WALLS MALFUNCTIONING OF THE TEMPER...

Страница 40: ...batteries to recharge S08 Economy mode active S09 Ready for power on S10 UPS locked load not powered S11 UPS locked load on bypass S12 BOOST stage or battery charger locked load not powered Command i...

Страница 41: ...Bypass frequency outside tolerance range A18 Voltage on bypass line outside tolerance range A19 High peak current on output of Phase 1 A20 High peak current on output of Phase 2 A21 High peak current...

Страница 42: ...orted F16 Sine wave of inverter Phase 3 distorted F17 Inverter stage anomaly F19 Positive battery overvoltage F20 Negative battery overvoltage F21 Positive battery undervoltage F22 Negative battery un...

Страница 43: ...Phase 1 inverter undervoltage L18 Phase 2 inverter undervoltage L19 Phase 3 inverter undervoltage 3 L20 Direct voltage at inverter output or distorted Phase 1 inverter sine wave L21 Direct voltage at...

Страница 44: ...Output current 152 A 182 A Rated apparent output power 100kVA 120kVA Rated active output power 90kW 108kW Output power factor 0 9 Short circuit current 1 5x Ir for t 500ms Output voltage precision re...

Страница 45: ...of installation Max relative humidty during operation 90 without condensation Max installation height 1000 m at rated power 1 power for every 100 m above 1000 m max 4000 m Fan flow rate in place of in...

Отзывы: