Press
to enter the System on menu. When confirmation is
requested, press
“YES”, press
to confirm and wait for a few
seconds. Check that the UPS is set to the state where the load is fed
by the inverter.
Open the input isolating switch (SWIN) and wait for a few seconds.
Check that the UPS is set to
“BATTERY” operation and that the load is
still being powered correctly. A beep must be heard about every 7
seconds.
Close the input isolating switch (SWIN) and wait for a few seconds.
Check that the UPS is no longer operating from the battery and that the
load is being powered correctly from the inverter.
To set the Date and Time, access menu 8.6.7 (see
“Display menus”).
Use the arrow keys (
↑↓
) to set the required value, and finally confirm
by pressing (
) to move on the next field. To save the new settings, go
back to the previous menu by pressing
.
S
WITCHING ON FROM THE MAINS
Close the isolating switch SWIN.
After a few moments the UPS becomes active, capacitor pre-loading takes place
and the “Lock / stand-by” LED
flashes: The UPS is in stand-by mode.
Press
to access the System on menu.
When confirmation is requested, select “YES” and press
again to
confirm. All the LEDs around the display light up for about 1 second and a beep is heard. The display shows the
message “SYSTEM ON” to inform the user of the start of the switching on sequence which ends when the UPS load
is powered by the inverter.