16
I
NSTRUCTIONS FOR
8
–
10
K
VA
MODELS
Follow the instruction below to access the terminals of the UPS and made the electrical connections:
1. Remove the terminals cover in the back of the
UPS, placed below the disconnector switches
(see
"UPS
VIEWS
")
2. Pierce the rubber grommets to allow the wires
passing.
3. We recommend using double-insulated multi-
core cables to be connected, respectively, to
the “INPUT”, “OUTPUT” and “BYPASS”
terminals (if present).
4. For the cross section and the cable stripping,
refer to the paragraph "
C
ONNECTION CABLES
CROSS SECTION DETAILS
”.
5. The wires should be stripped and inserted into
the terminals (for the length of the stripping,
refer to the paragraph “
C
ONNECTION CABLES
CROSS SECTION DETAILS
”).
NOTE:
To remove the wire, insert a flat blade
screwdriver into the clamp slot above the wire
inlet.
6. Fix the cables to the ties block in the back of the
UPS.
7. When the installation is complete, close the
terminals cover and secure with the screws
Option with cable glands (not supplied):
Cable glands (not supplied) can be used to secure the cables. The cable glands will be mounted in place of the rubber
grommets in the terminal cover panel (see picture
Option 1
). Alternatively, remove the pre-cut flanges and mount the cable
glands in the slots (see picture
Option 2
).
Option 1
Option 2