MASTER HE
SPTMHEE3T16FREN
30
Electrical Data
UPS Size (kVA)
100
120
160
200
250
SYSTEM
AC/AC efficiency
(On line) – [%]
•
Full load
•
Load 75%
•
Load 50%
•
Load 25%
95.1
95.2
94.8
92.5
94.5
95.2
95.2
93.5
95.2
95.5
95.3
94.0
94.5
95.3
95.5
94.5
Efficiency system in STAND-BY
mode [%]
•
Charge 100%
•
Charge 50%
99
98.5
Neutral size (I/rated current)
1.73
1.44
1,73
1,38
1,1
Dissipated power without load
•
[Kw]
•
[Kcal/h]
•
[BTU/h] see note 3
1.5
1290
5118
1.5
1290
5118
2.1
1806
7165
2.1
1806
7165
2.5
2150
8530
Dissipated power with 50% of load
•
[Kw]
•
[Kcal/h]
•
[BTU/h] see note 3
2.7
2358
9358
3
2601
10322
3.9
3392
13462
4.7
4052
16078
5.9
5065
20098
Dissipated power with 100% of load
•
KW
•
Kcal/h
•
BTU/h ((see note 3)
5.2
4430
8790
7
6005
23831
8.1
6937
27527
11.6
10009
39718
14.6
12511
49648
Maximum current dispersion
300 mA maximum
Noise level at 1m from the front
(from 0 to full load ) - [dbA]
65
68
Notes:
(1)
The number of Pb elements can vary from 222 to 258
(2)
The parallel version can be calibrated from 0,1 to 1Hz/s.
(3)
3.97 BTU = 1kcal.