Electrical Data
UPS Size (kVA)
100
120
160
200
250
INPUT
Rated Voltage
400 Vac 3F-phase without neutral
Rated Voltage tolerance (%) without
battery sharing, according with load
rate
+20%, -10% (100% load)
+20%, -20% (85% load)
+20%, -30% (75% load)
+20%, -40% (65% load)
Rated Frequency (Hz)
50/60
Input frequency tolerance
from 45 to 65 Hz
Rated current absorbed at rated
voltage [A]
153
185
245
309
386
Rated power absorbed at rated
voltage [kVA]
106
128
170
214
267
Max current absorbed at full load
and battery in recharge [A]
170
204
273
341
426
Input Power Factor at rated voltage
with battery in recharge (from 25% to
100% load)
>0,99
Current Harmonic distortion (THDi)
with main THDV < 1%
•
Load 100%
•
Load 75%
•
Load 50%
•
Load 25%
<3%
<3%
<5%
<8%
Progressive start of rectifier (Power
Walk-in Duration)
from 0 to 120 second (Configurable)
Delay of Progressive start of rectifier
(Power Walk-in Start Delay )
from 0 to 120 second (Configurable)
D.C. INTERMEDIATE CIRCUIT
Number of lead cells / Battery blocks
(see note 1)
240 (40 batteries)
Rated battery voltage (Vdc)
480
Ripple current with recharged
battery (%)
Approx 0
Float voltage (2,26 V/el., can be
calibrated) – Vdc
542
Recharge Voltage (2,4 V/el., can be
calibrated) – Vdc
576
Maximum output voltage (Vdc)
600
End of discharge voltage Vdc (1,6
V/el, can be calibrated) - Vdc
384
Voltage Compensation with
reference to the battery cabinet
temperature (V per °C)
-0,11%
Maximum current to charge battery
with 240 elements (A). (mains
voltage 400V)
•
Load 100%
18
20
30
37
•
Load 90%
36
45
60
75
•
Load 80%
56
65
90
110
•
Load
≤ 70%
66
80
105
130