ALARM
DESCRIPTION
OUTPUT SWITCH AND MANUAL BY-PASS SWITCH
OPEN
This alarm indicates when there is no output voltage due
to the simultaneous opening of the SWOUT output switch
and the SWMB manual bypass switch.
ACTIVE/DISABLED SHUTDOWN COMMAND.
This alarm indicates when the shutdown command
(Rec In by-pass) has been activated on the
front panel or through the connection of the RS232
interface (Powershield³).
REMOTE SHUTDOWN COMMAND:
ACTIVATED/DISABLED.
This alarm indicates when the shutdown command
(Rec In by-pass) has been activated via
remote contact.
CHANGED MEMORY: CODE = NUMBER
Indicates that the system settings have been changed.
BATTERY OVERTEMPERATURE
The temperature in the battery cabinet has exceeded the
set limits.
BATTERY TEST FAILED
The battery test has encountered a battery fault
FAULTY FAN ALARM
This alarm indicates a faulty fan inside the system
(optional function - on request).
FAULT FUSE
This alarm indicates one or more faulty fuses inside the
system (optional function - on request).
FAULT ON PARALLEL CONNECTION
The parallel connection has been interrupted or is
disconnected
AUTO-OFF Timer: Toff= 0: 0', Ton= 0: 0'
This alarm indicates when the daily timer comes in
function set for the automatic UPS start-up and
shutdown. If required this function is enabled at start-up.
12.2.
LED Remote mimic panel
It can be connected up to a distance of 200m from the UPS for remote supervising.
The panel provides information about UPS functions:
•
Green LED: normal operation;
•
Yellow LED: not critical alarm;
•
Red LED: alarm.
UPS start-up and shutdown commands can also be sent from the mimic panel.
12.3.
Remote graphic panel
Graphic remote panel gets available remotely on the Graphic Display the information on the UPS status, the measurements
and the alarms. In addition it is fitted a RS485 port which gets available the same information in JBUS/MODBUS protocol
for the BMS.
The max distance between the UPS and remote panel is approx 300 mt.
RS232