MASTER HE
SPTMHEE3T16FREN
28
Electrical Data
UPS Size (kVA)
100
120
160
200
250
INVERTER
Rated Power [kVA]
100
120
160
200
250
Rated active Power [kW]
100
120
160
200
250
Nominal Current [A]
144
173
231
289
361
Rated Voltage
400 V 3F + N (configurable from 360 V to 420 V)
Rated Frequency
50 o 60 Hz (configurable on site)
Output Rated voltage regulation
from 360 to 420 V
Static variation
±1 %
Dynamic variation
±5%
Restore time within ±1%
20 ms
Conform To the standard EN 62040-3, class 1
Crest current factor (Ipeak/Irms as
per EN 62040-3)
3:1
Voltage distortion with linear load
≤1% (typica), ≤2% (max)
Voltage distortion with non-linear
load (EN 62040-3)
≤3%
Frequency stability with inverter not
synchronized to the by-pass mains.
±0,05 %
Speed of frequency variation
1 Hz/sec (see note 2)
Phase voltage asymmetry with
balanced and unbalanced load.
≤1%
Voltage phase shift with balanced
and unbalanced load.
120 ±1°el
Overload referred to the rated power
•
Phase / Phase
•
Phase / Neutral
(@ 25°C environment)
110% for 60 minutes, 125% for 10 min., 150% for 1 min.
200% for 6 seconds
Short circuit Current
•
Phase / Phase
•
Phase / Neutral
180% for 1 second
300% for 1 second
Battery mode efficiency (%)
95%