 •  The installation of both anti-derailment buffers is 

absolutely obligatory

 before starting programming.

•   Make sure the safety devices are at rest and the ECU is receiving power otherwise you will not be able to enter programming.

PROGRAMMING PROCEDURE (Setting the programmer)

Dip-switch settings DS1

CAUTION:

 If you change the dip settings you must memorise them; press the 

"PROG" 

button, "dIP" will appear on the display indicating that the settings have 

been memorised.

Motor selection (DIP1)

"ON"   =  Single motor operation

"OFF"  =  Double motor operation

Opening direction gate delay (DIP 2)

"ON"   =  Gate delay enabled
"OFF"  =  Gate delay disabled

If you enable gate delay the following will occur: during the opening movement gate 

leaf 1 moves first and then gate leaf 2. In the closing direction gate leaf 

2

 

moves 

first then gate leaf 1. If gate delay is disabled both gate leaves move simultaneously.

Sequential command TD/CH1 (DIP3)

"ON"   =  Sequential command "open-close"

Travel direction inversion only during closing.

"OFF"  =  Sequential command "open-block-close-block"

Automatic reclosing (DIP4)

"ON"   =  Automatic reclosing enabled
"OFF"  =  Automatic reclosing disabled

Pre-flashing (DIP 5)

"ON"   =  Pre-flashing activated
"OFF"  =  Pre-flashing excluded

Warning light output (DIP 6)

"ON"   =  Warning light output intermittent 
"OFF"  =  Warning light output fixed

Indicator light (DIP 7)

"ON"   =  Indicator light intermittent

*

 

"OFF"  =  Indicator light fixed

The indicator light flashes slowly during opening, rapidly during closing; remains 

lit when the gate is blocked but not completely closed

 

and is off when the gate 

is completely closed.

FTCI mode (DIP 8)

"ON"   = 

FTCI

 also active when the gate is blocked

If the photocells are in alarm and the gate is blocked, no movement commands 

will be accepted (even opening commands).

"OFF"  = 

FTCI

 active only during closing

In both cases activating the 

FTCI

 safety device during the closing stage will force 

travel direction inversion.

FTCI test (DIP 9)

"ON"   = 

FTCI

 test enabled

"OFF"  = 

FTCI

 test disabled

If you enable the security test you will have to connect both the transmitter and 

the receiver to the controlled load output (

CTRL

 

24 Vdc

). When the test is enabled 

one second will pass between receiving a command and carrying it out. 

FTCS test (DIP 10)

"ON"   = 

FTCS

 test enabled

"OFF"  = 

FTCS

 test disabled

If you enable the security test you will have to connect both the transmitter and 

the receiver to the controlled load output (

CTRL

 

24 Vdc

). When the test is enabled 

one second will pass between receiving a command and carrying it out. 

Electric lock (DIP 11)

"ON"   =  Electric lock enabled

"OFF"  =  Electric lock disabled

If the electric lock is enabled the ELS output (binding post 6) will be activated 

before gate leaf 1 moves and will remain active until gate leaf one has moved 

for a few seconds.

Travel limit motor 1 (DIP 12)

“ON”    =  Travel limit motor 1 enabled
“OFF”   =  Travel limit motor 1 disabled

Travel limit motor 2 (DIP 13)

“ON”    =  Travel limit motor 2 enabled
“OFF”   =  Travel limit motor 2 disabled

Dip 14

  =  Not used

• 

GATE LEAF 1

 STARTS TO OPEN. WHEN IT ARRIVES AT THE TRAVEL LIMIT PRESS PROG. 

• 

GATE LEAF 2

 STARTS TO OPEN. WHEN IT ARRIVES AT THE TRAVEL LIMIT PRESS PROG. 

• 

GATE LEAF 2

 STARTS TO CLOSE. WHEN IT ARRIVES AT THE TRAVEL LIMIT PRESS PROG. 

• 

GATE LEAF 1

 STARTS TO CLOSE. WHEN IT ARRIVES AT THE TRAVEL LIMIT PRESS PROG. 

NOTE: 

IF THE PROGRAMMER IS SET TO WORK A SINGLE MOTOR THE PROGRAMMING WILL 

EXCLUDE THE STEPS FOR GATE LEAF 2.  

AFTER HAVING CARRIED OUT THIS MANOEUVRE THE LOGIC CONTROL WILL OPEN THEN 

CLOSE THE GATE LEAVES COMPLETELY IN ORDER TO CALIBRATE THE CURRENT SENSOR. 

WHEN THE GATE REACHES THE 

COMPLETELY CLOSED POSITION THE 

PROGRAMMER SAVES THE PARAMETERS 

AND QUITS THE PROGRAMMING MODE

THE OPERATION HAS NOT 

SUCCEEDED. YOU WILL HAVE 

TO REPEAT THE 

PROGRAMMING PROCEDURE.

PRESS THE 

PROG

 BUTTON FOR MORE 

THAN 4 SECONDS: THE "

PAUSE

" SYMBOL 

WILL APPEAR INDICATING THAT YOU ARE 

IN THE PAUSE PROGRAMMING MODE

1...4... sec.

PRESS PROG

THE PAUSE TIME COUNT 

ENDS AND THE DOOR OPENS 

SLOWLY IN ORDER TO FIND 

THE COMPLETELY OPEN 

POSITION. 

THE PAUSE TIME COUNT 

WILL START (

MIN. 2 

SECONDS: MAX 120 

SECONDS

) INDICATED BY 

THE "

PAUSE

" SYMBOL 

FLASHING ON THE DISPLAY 

PRESS PROG

ATTENTION!

 IF THE GATE MOVES 

IN THE CLOSING DIRECTION THE 

MOTOR CONNECTION IS 

INCORRECT.  PRESS “

PROG

” 

AGAIN TO CANCEL THE 

PROGRAMMING PROCEDURE, 

INVERT THE MOTOR 

CONNECTION (RED AND BLACK 

CABLE) AND REPEAT THE 

PROGRAMMING PROCEDURE.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Содержание Cardin PRG230M2 Series

Страница 1: ... importanti Pagina 3 Collegamento elettrico Pagine 3 4 Procedura di programmazione Pagine 5 6 Comando via radio Pagina 7 Modalità di funzionamento Pagina 7 Indicazioni del display Pagina 7 Caratteristiche tecniche Pagina 28 230 Vac Motors PROGRAMMATORE ELETTRONICO PER IL COMANDO DI PORTE E PORTONI MOTORIZZATI ELECTRONIC PROGRAMMER CONTROLLING MOTORISED GATES AND DOORS PROGRAMMATEURÉLECTRONIQUE POU...

Страница 2: ... x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x...

Страница 3: ...le limitazi one di coppia e gestione dei rallentamenti con spazio di rallentamento impostabile Predisposta per l inserimento di una scheda radio ricevente standard Cardin La programmazione eseguibile mediante un solo pulsante permette la regolazione della corsa totale delle ante Attenzione Nel programmatore è presente la tensione a 230 Vac Per la conformità alla normativa sulla sicurezza elettrica...

Страница 4: ...ollegamento terra Nota 1 La somma delle due uscite per carichi esterni non deve superare 10W Nota 2 La selezione del tipo di contatto N C 8 2 kΩ viene effettuata da menu visua lizzabile sul display a 6 cifre parametro SC TUTTI I CONTATTI N C NON UTILIZZATI VANNO PONTICELLATI e di conse guenza i test sulle sicurezze corrispondenti FTCI FTCS DIP9 e DIP10 devono essere disabilitati Se si vuole attiva...

Страница 5: ...TCS DIP 10 ON Test su FTCS abilitato OFF Test su FTCS disabilitato Se si abilita il test sulle sicurezze bisogna alimentare sia la parte trasmittente che la parte ricevente ai carichi controllati CTRL 24 Vdc Con il test abilitato passa circa un secondo dalla ricezione di un comando alla sua effettiva esecuzione Elettroserratura DIP 11 ON Elettroserratura abilitata OFF Elettroserratura disabilitata...

Страница 6: ... N C CSP N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ Per i valore da A ad F vedere il paragrafo selezione del contatto a pagina 7 10 sec 10 sec PREMERE PROG Ad ogni pressione del tasto si modifica l impostazione tra 0 9 A F Dopo 10 secondi dalla ultima modifica si uscirà automaticamente salvando il valore selezionato es 5 10 sec Dopo 10 secondi dall ultima modifica il sistema esce autom...

Страница 7: ...a di emergenza Nelcasoincuiilprogrammatoreelettroniconondovessepiùrispondereaicomandi per un malfunzionamento agire sugli ingressi EMRG1 o EMRG2 per muovere anta 1 in modalità uomo presente Gli ingressi EMRG1 ed EMRG2 agiscono direttamente sul controllo del motore escludendo la logica Attenzione Durante la manovra di emergenza tutte le sicurezze risultano disabilitate e non c è controllo sulla pos...

Страница 8: ...rdin motors The manufacturer accepts no liability for situations arising from the use of an electrical installation which does not conform to the local standards and regulations in force Attention Only for EU customers WEEE marking This symbol indicates that once the products life span has expired it must be disposed of separately from other rubbish The user is therefore obliged to either take the...

Страница 9: ...programmer power supply 230Vac 50 60Hz 44 Electronic programmer earth wire 230Vac 50 60Hz 45 Earth connection 46 Earth connection Note 1 The total of the 2 external device outputs must not exceed 10 W Note 2 Theselectionofthetypeofcontact N C 8 2kΩ iscarriedoutusingparameter SC on the six figure display ALL UNUSED NC CONTACTS MUST BE JUMPED and consequently the security device test must also be de...

Страница 10: ...one second will pass between receiving a command and carrying it out FTCS test DIP 10 ON FTCS test enabled OFF FTCS test disabled If you enable the security test you will have to connect both the transmitter and thereceivertothecontrolledloadoutput CTRL24Vdc Whenthetestisenabled one second will pass between receiving a command and carrying it out Electric lock DIP 11 ON Electric lock enabled OFF E...

Страница 11: ...e delay 2 medium gate delay PRESS PROG Each time the button is pressed the number increases from 1 to 3 PRESS PROG PRESS PROG Selecting the type of security contact 0 1 2 3 4 5 6 7 8 9 TB N C N C N C N C N C N C N C N C 8 2 KΩ 8 2 KΩ FTCS N C N C N C N C 8 2 KΩ 8 2 KΩ 8 2 KΩ 8 2 KΩ N C N C FTCI N C N C 8 2 KΩ 8 2 KΩ N C N C 8 2 KΩ 8 2 KΩ N C N C CSP N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ N C ...

Страница 12: ...an be moved by hand 4 Emergency manoeuvre If the electronic programmer no longer responds to commands due to a malfunction you may use the EMRG1 or EMRG2 inputs to move the gate leaf manually The EMRG1 or EMRG2 inputs directly command the motor without passing through the logic control Attention During the emergency manoeuvre all safety devices are disabled and there is no gate positioning control...

Страница 13: ...nt pour chaque vantail avec indications sur afficheur à 6 chiffres Possibilité de fonctionnement même à défaut de fins de course mécaniques Sélection du couple moteur Contrôle du lancement initial limitation du couple et gestion des décélérations avec distance de ralentissement réglable L appareil est prédisposé pour l insertion d une carte radio réceptrice standard Cardin La programmation réalisa...

Страница 14: ...sitifs externes ne doit pas être supé rieure à 10 W Nota 2 LasélectiondutypedecontactN F 8 2kΩs effectuesurlemenuvisionnable sur l afficheur à 6 chiffres paramètre SC FAIREUNPONTSURTOUSLESCONTACTSN F INUTILISÉSet enconséquence invalider les tests sur les dispositifs de sécurité correspondants FTCI FTCS DIP9 et DIP10 en position OFF Si l on désire activer le test sur les dispositifs FTCI et FTCS la...

Страница 15: ...squ enfermeture c estd abordlevantail 2etensuitelevantail1 Avecdécalageinvalidé lesvantauxdémarrentsimultanément Commande séquentielle TD CH1 DIP 3 ON Commande séquentielle ouverture fermeture L inversion du sens de marche ne se produit qu en phase de fermeture OFF Commande séquentielle ouverture blocage fermeture blocage Refermeture automatique DIP 4 ON Refermeture automatique validée OFF Referme...

Страница 16: ...e du temps de ralentissement 0 ralentissement exclu 1 min 2 3 4 5 max APPUYER SUR PROG Chaque pression sur la touche augmente d une unité de 1 à 3 10 sec 10 sec Réglage du décalage entre les vantaux 1 décalage minimum 3 décalage maximum 2 décalage moyen APPUYER SUR PROG Chaque pression sur la touche augmente d une unité de 1 à 3 APPUYER SUR PROG APPUYER SUR PROG Sélection du contact de sécurité 0 ...

Страница 17: ...ce En cas de défaillance du programmateur électronique qui ne répond plus aux commandes intervenirsurl entréeEMRG1ouEMRG2pourmanœuvrerleportail enmodedefonctionnementhomme mort LesentréesEMRG1etEMRG2agissent directement sur le contrôle du moteur excluant la logique Attention Pendant la manœuvre d urgence tous les dispositifs de sécurité sont invalidés et il n y a aucun contrôle sur la position du ...

Страница 18: ...bare Verlangsamung Die Apparatur ist für den Einsatz eines Cardin Standard Funksteckempfän gers vorbereitet DiemitnureinerTasteausführbareProgrammierunggestattetdieRegelung die gesamten Torflügelläufe Achtung An einige Stelle der Steuerungsleiterplatte befindet sich die Stromspannung von 230 Vac GemäßderVorschriftüberdieelektrischeSicherheitistesverboten die Anschlussklemmen 3 4 und 5 direkt an ei...

Страница 19: ...usgänge für die externen Stromabnehmer darf nicht mehr als 10 W betragen Anmerkung 2 Die Auswahl der Art des Kontakts N C 8 2 kΩ erfolgt über das Menü das im 6 stelligen Display angezeigt werden kann Parameter SC ALLENICHTVERWENDETENN C KONTAKTEMÜSSENÜBERBRÜCKTundsomit auch die Tests der entsprechenden Sicherheitsvorrichtungen FTCI FTCS DIP9 und DIP10 in der Position OFF ausgeschaltet werden Wenn ...

Страница 20: ... an die kontrollierten Stromabnehmer CTRL24 Vdc angeschlossen werden Bei eingeschaltetem Test vergeht zirka eine Sek zwischen dem Empfang eines Befehls und dessen tatsächlicher Ausführung Test von FTCS DIP 10 ON Test von FTCS eingeschaltet OFF Test von FTCS abgeschaltet Wenn der Test der Sicherheitsvorrichtungen eingeschaltet ist muss sowohl der sendende Teil als auch der empfangende Teil an die k...

Страница 21: ...TAL TB FTCI FTCS CSP einmal ein Zur Rückkehr zur normalen Betriebsweise PROG drücken wonach der Schriftzug test erscheint nun 10 Sekunden abwarten 10 Sek 10 Sek PROG DRÜCKEN Durch die aktivierung der Eingänge TA TC TD TAL TB FTCI FTCS CSP wird das Blinklicht betätigt 10 Sek 10 Sekunden nach der letzten Änderung erfolgt automatisch der Austritt aus dem Verfahren und die Speicherung des eingestellte...

Страница 22: ...ektes nicht mehr auf die Befehlseingabe anspricht sind die Eingänge EMRG1 oder EMRG2 zur manuellen Betätigung des Tors zu verwenden Die Eingänge EMRG1 und EMRG2 schließen die Logik aus und haben somit einen direkten Einfluss auf die Kontrolle des Motors Achtung Während der Notfall Betätigung sind alle Sicherheitsvorrichtungen abgeschaltet und die Torstellung wird nichtkontrolliert Deshalbmüssendie...

Страница 23: ...rranque inicial limitación de par y gestión de las ralentizaciones con espacio de ralentización configurable El equipo está predispuesto para la inserción de una tarjeta radio receptora estándar Cardin La programación realizable mediante una sola tecla permite el ajuste del recorrido completo de las hojas Atención En algún punto de la tarjeta del programador está presente la tensión de 230 Vac Par...

Страница 24: ... selección del tipo de contacto N C 8 2 kΩ se efectúa desde el menú visualiza ble en el display de 6 cifras parámetro SC TODOS LOS CONTACTOS N C QUE NO SE UTILICEN DEBEN PUENTEARSE y en consecuencia deben deshabilitarse los test en los dispositivos de seguridad correspon dientes FTCI FTCS DIP9 y DIP10 en posición OFF Si se habilita el test en FTCI y FTCS tanto la parte emisora como la parte recept...

Страница 25: ...ad tanto la parte emisora como la parte receptora deben ser conectadas a las cargas controladas CTRL 30Vdc Con el test habilitado transcurre aproximadamente un segundo tras la recepción de un control y la ejecución efectiva del mismo Cerradura eléctrica DIP 11 ON Cerradura eléctrica habilitada OFF Cerradura eléctrica inhabilitada Habilitando la cerradura eléctrica antes de iniciar el movimiento de...

Страница 26: ... PROG Tras cada pulsación de la tecla se incrementará el número de 1 a 3 PULSAR PROG PULSAR PROG Selección del contacto de seguridad 0 1 2 3 4 5 6 7 8 9 TB N C N C N C N C N C N C N C N C 8 2 KΩ 8 2 KΩ FTCS N C N C N C N C 8 2 KΩ 8 2 KΩ 8 2 KΩ 8 2 KΩ N C N C FTCI N C N C 8 2 KΩ 8 2 KΩ N C N C 8 2 KΩ 8 2 KΩ N C N C CSP N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ N C 8 2 KΩ Para el valor de A a F ve...

Страница 27: ...mandos por un mal funciona miento actuar sobre la entrada EMRG1 o EMRG2 para mover la cancilla en modo manual Las entradas EMRG1 y EMRG2 actúan directamente sobre el control del motor excluyendo la lógica Atención Durante la maniobra de emergencia todos los dispositi vos de seguridad resultan deshabilitados y no existe control alguno sobre la posición de la cancilla en consecuencia soltar las tecl...

Страница 28: ...motors power 470 470 W Output for a courtesy light 230 Vac 40W Output for an indicator light 24 Vac 3W Output for warning lights 230 Vac 40W continuous or intermittent activation Output for an electric lock 12 Vac 15W Output for external devices 24 Vac 10W Optional receiver card Reception frequency MHz 433 92 868 3 Number of channels Nr 4 Number of functions Nr 2 Number of stored codes Nr 300 1000...

Отзывы: