Chapter 4 Parameter List
65
4
Func.
Name
Description
Range of
Setting
Unit Def50 Page
F_129
AM+ Analog
Output Signal
Selection
0: Output frequency.
1: Frequency command.
2: Output current.
3: Vin frequency command.
4: Iin frequency command.
0~4
─
2
F_130
AM+ Analog
Output Gain
AM+ analog output adjustment ratio.
0.00~2.00 0.01 1.00
F_131
Multi-function
Output
Terminal
Ta2/Tc2
The way of settings are same as
multi-function output terminals setting.
(F_058 ~ F_060)
0.0~10.0 0.1Hz 2.0
F_132
DC Braking
Frequency
at Stop
Active frequency level of DC braking at stop. 0.1~60.0 0.1Hz 0.5
F_133
(Water Usage
Detection)
Drive Standby
level
When the frequency during the operation is
lower than the setting value, drive will
decelerate to 0Hz and entering stand by
status.
0~120
1Hz
10
F_134
Default
Setting
0: Disable
0
─
CLF: Clear fault records
dEF60: Restore the default value of drive for
60Hz.
dEF50: Restore the default value of drive for
50Hz. Distributor A setting value for
constant pressure setting (single
pump)
dEF52: Restore the default value of drive for
60Hz.Distributor A setting value for
constant pressure
setting(multi-pump)
dEF53: Restore the default value of drive for
50Hz.
SAv: Save the setting value.
rES: Restore the setting value.
rd_EE: Read the parameters from drive to
digital keypad
Wr_EE: Write the parameters from digital
keypad to drive
Cpy: In multi-pump control system, copy lead
drive’s parameter.
F_135
Set Standby
Drives
In multi-pump control systems, setting the
drives standby numbers.
0~3
─
0
F_136
Noise
Prevention
0: Disable.
1: Enable.
0,1
─
0
F_137
Delay Time at
Pump Shift
Operation
The delay time setting is to remain the stable
pressure of the system at the interchanging of
the pump operation.
0~250
1sec
10
F_138
200%
Current Limit
0: Disable.
1: Enable.
0,1
─
0