Chapter 5 Parameter Setting Description
78
5
5-2 Preset Speed Setup
F_031
Primary Speed
F_032
Preset Speed 1
F_033
Preset Speed 2
F_034
Preset Speed 3
F_035
Preset Speed 4
F_036
Preset Speed 5
F_037
Preset Speed 6
F_038
Preset Speed 7
F_039
Jog Speed
a. Related functions:
(I)
The setting of acceleration and deceleration time (F_018 ~ F_20
、
F_027
、
F_029).
(II) The setting of multi-function input terminals (F_052 ~ F_055).
b. Switch of jog speed, primary speed and preset speeds.
※
The ON/OFF conditions as below table are “contact a (N.O)” setting of
functions.
Jog speed
command
Multi-speed level 3
command
Multi-speed level 2
command
Multi-speed level 1
command
Command
Description
ON
X
X
X
Jog speed
OFF
OFF
OFF
OFF
Primary speed
OFF
OFF
OFF
ON
Preset speed 1
OFF
OFF
ON
OFF
Preset speed 2
OFF
OFF
ON
ON
Preset speed 3
OFF
ON
OFF
OFF
Preset speed 4
OFF
ON
OFF
ON
Preset speed 5
OFF
ON
ON
OFF
Preset speed 6
OFF
ON
ON
ON
Preset speed 7
Note:
1.
―
X
― : Don’t care
2. The following chart shows jog speed having highest precedence, and jog speed
command is ON, the motor is running at jog speed
3. Jog speed command and the multi-speed commands are programmed by the
multi-function input terminals (X1 ~ X4) by functions (F_052 ~ F055). ON / OFF the
terminal in accordance with above table to switch the speed.
4.
― ON ― :
The terminal is short-circuit at contact a (N.O) setting.
The terminal is open-circuit at contact b (N.C) setting.
― OFF ‖ :
The terminal is open-circuit at contact a (N.O) setting
The terminal is short-circuit at contact b (N.C) setting.
5. The priority of speed command: Jog speed>Multi-sped>primary speed