Chapter 4 Parameter List
56
4
Func.
Name
Description
Range of
Setting
Unit Def50 Page
F_007
Pressure
Transducer
Setting
Set upper limit value of pressure in
accordance with pressure transducer
specification.(pressure setting value is
corresponding to maximum voltage or current.
0.0~160.0 0.1bar 10.0 104
F_008
Maximum
Allowabel
Operating
Pressure
Set the maximum operating pressure value
(F_007*F_008) in accordance with the
specification of pump.
0~100
1
﹪
100 104
F_009
Starting
Frequency
The starting frequency of drive.
0.1~10.0 0.1Hz
0.5
F_010
Starting
Voltage
The voltage correspond to the starting
frequency.
0.1~50.0
0.1V
8.0
(Note1)
0.1~100.0
12.0
(
Note2)
F_011
Base
Frequency
The frequency correspond to the base
voltage in V/F pattern.
0.1~400.0 0.1Hz 60.0
F_012
Base
Voltage
The voltage correspond to the base
frequency in V/F pattern.
0.1~255.0
0.1V
220.0
(Note1)
0.1~510.0
380.0
(Note2)
F_013
Selection of
Pump Shift
Operation
(Parallel
control)
0: Disable.
1: Shift the pump operation arriving the
operating time (F_024).
2: Shift the pump operation after a drive
stops.
3: Both 1 and 2 enabled.
0~3
─
3
F_014 Reserved
─
F_015
Control
Mode
Selection
(Parallel
control)
0: Disable the functions related to pump.
1: Single pump application.
2: Multi-pump applications; (E-mode)
3: Multi-pump applications; (F-mode)
4: Multi-pump applications; (M-mode)
5. Multi-pump applications; (S-mode)
0~5
─
1
F_016
Set Drive
’s
No. for
Parallel
Control
Set the individual number for every drive.
#0 as the lead drive to command others.
0~3
─
0
The color as means the function can be set during the operation.