- (01 - 33) -
FUNCTION SETTINGS
12.
INDOOR UNIT
12-1.
INDOOR UNIT
DIP Switch
1
Remote controller address setting
2
3
4
Jumper Wire
JM1
Drainage function setting
JM2
Setting change prohibited
JM3
Fan delay setting
SWITCH POSITION
DIP SWITCH SETTING
Remote controller address setting
A number of indoor units can be operated at the same time using a wired remote controller.
Set the unit number of each indoor unit using the DIP switches on the indoor unit MAIN PC board.
(See the following table.)
The DIP switches are normally set to make the unit number 00.
(
. . .Factory setting)
Remote controller
address setting
DIP switch No.
1
2
3
4
00
OFF
OFF
OFF
OFF
01
ON
OFF
OFF
OFF
02
OFF
ON
OFF
OFF
03
ON
ON
OFF
OFF
04
OFF
OFF
ON
OFF
05
ON
OFF
ON
OFF
06
OFF
ON
ON
OFF
07
ON
ON
ON
OFF
08
OFF
OFF
OFF
ON
09
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
JM3
JM2
JM1
1
ON
OFF
2
3
4
MAIN PC board
Содержание RIDH09AVFJ
Страница 2: ...1 INDOOR UNIT DUCT TYPE RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Страница 12: ...01 09 5 WIRING DIAGRAMS MODELS RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Страница 48: ...2 OUTDOOR UNIT SINGLE TYPE ROSH09AFCJ ROSH12AFCJ ROSH18AFCJ...
Страница 53: ...02 04 4 WIRING DIAGRAMS MODEL ROSH09AFCJ ROSH12AFCJ...
Страница 54: ...02 05 MODEL R O S H 1 8 A F C J...
Страница 62: ...02 13 SOUND LEVEL CHECK POINT 8 2 39 3 8in 1m Airflow Microphone Microphone...