- (01 - 39) -
6) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(
... Factory setting)
Function number
Setting value
Setting description
44
00
A
01
B
02
C
03
D
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
... Factory setting)
Function number
Setting value
Setting description
46
00
Operation/Stop mode
01
(Setting prohibited)
02
Forced stop mode
8) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
"Wired remote controller" (01). This function will only work if the function setting 42 is set at
"Both" (01).
(
... Factory setting)
Function number
Setting value
Setting description
48
00
Both
01
Wired remote controller
9) Room temperature control for wired remote controller sensor
Refer to Function 95, before performing this setting.
Depending on the installed environment, correction of the wired remote controller
temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both "01".
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(
. . .Factory setting)
Function number
Setting value
Setting description
92
(For cooling)
93
(For heating)
00
No correction 0.0°F 0.0°C
01
No correction 0.0°F 0.0°C
02
-1°F (-0.5°C)
More cooling
Less heating
03
-2°F (-1.0°C)
04
-3°F (-1.5°C)
05
-4°F (-2.0°C)
06
-5°F (-2.5°C)
07
-6°F (-3.0°C)
08
-7°F (-3.5°C)
09
-8°F (-4.0°C)
10
+1°F (+0.5°C)
Less cooling
More heating
11
+2°F (+1.0°C)
12
+3°F (+1.5°C)
13
+4°F (+2.0°C)
14
+5°F (+2.5°C)
15
+6°F (+3.0°C)
16
+7°F (+3.5°C)
17
+8°F (+4.0°C)
Содержание RIDH09AVFJ
Страница 2: ...1 INDOOR UNIT DUCT TYPE RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Страница 12: ...01 09 5 WIRING DIAGRAMS MODELS RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Страница 48: ...2 OUTDOOR UNIT SINGLE TYPE ROSH09AFCJ ROSH12AFCJ ROSH18AFCJ...
Страница 53: ...02 04 4 WIRING DIAGRAMS MODEL ROSH09AFCJ ROSH12AFCJ...
Страница 54: ...02 05 MODEL R O S H 1 8 A F C J...
Страница 62: ...02 13 SOUND LEVEL CHECK POINT 8 2 39 3 8in 1m Airflow Microphone Microphone...