- (01 - 38) -
3) Room temperature control for indoor unit sensor
Refer to Function 95, before performing this setting.
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00"
(manufacturer's recommended value).
*When Function 95-01(High insulation) is set, the Standard setting "00" will be the same as No
correction "01" [0.0°F (0.0°C)].
(
. . .Factory setting)
Function number
Setting value
Setting description
30
(For cooling)
31
(For heating)
00
Standard setting*
01
No correction 0.0°F 0.0°C
02
-1°F (-0.5°C)
More cooling
Less heating
03
-2°F (-1.0°C)
04
-3°F (-1.5°C)
05
-4°F (-2.0°C)
06
-5°F (-2.5°C)
07
-6°F (-3.0°C)
08
-7°F (-3.5°C)
09
-8°F (-4.0°C)
10
+1°F (+0.5°C)
Less cooling
More heating
11
+2°F (+1.0°C)
12
+3°F (+1.5°C)
13
+4°F (+2.0°C)
14
+5°F (+2.5°C)
15
+6°F (+3.0°C)
16
+7°F (+3.5°C)
17
+8°F (+4.0°C)
In case of Slim duct type and Floor/Ceiling type models:
In
fl
oor console installations, select “01”.
4) Auto restart
Enable or disable automatic restart after a power interruption.
(
... Factory setting)
Function number
Setting value
Setting description
40
00
Enable
01
Disable
*Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
5) Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperture sensor, change the setting to "Both" (01).
(
... Factory setting)
Function number
Setting value
Setting description
42
00
Indoor unit
01
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*Remote controller sensor must be turned on by using the remote controller.
Содержание RIDH09AVFJ
Страница 2: ...1 INDOOR UNIT DUCT TYPE RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Страница 12: ...01 09 5 WIRING DIAGRAMS MODELS RIDH09AVFJ RIDH12AVFJ RIDH18AVFJ...
Страница 48: ...2 OUTDOOR UNIT SINGLE TYPE ROSH09AFCJ ROSH12AFCJ ROSH18AFCJ...
Страница 53: ...02 04 4 WIRING DIAGRAMS MODEL ROSH09AFCJ ROSH12AFCJ...
Страница 54: ...02 05 MODEL R O S H 1 8 A F C J...
Страница 62: ...02 13 SOUND LEVEL CHECK POINT 8 2 39 3 8in 1m Airflow Microphone Microphone...