53
FIGURE 62
MODELS WITH HONEYWELL S9201E2001 OR UTEC 1012-920 CONTROL BOARD
INTEGRATED FURNACE CONTROL (IFC) TROUBLESHOOTING GUIDE
(115 VAC IGNITER)
START
1. SET FAN SWITCH TO AUTO
2. SET THERMOSTAT TO
CALL FOR HEAT
INDUCED DRAFT MOTOR
(IDM) STARTS
30 SEC. PREPURGE
IGNITER WARMS UP
AND GLOWS RED
30 SECONDS WARMUP
MAIN BURNER
LIGHTS
WARNING
DISCONNECT POWER BEFORE
SERVICING.
SERVICE MUST BE BY A TRAINED,
QUALIFIED SERVICE TECHNICIAN.
HAZARDOUS VOLTAGE
LINE VOLTAGE
CONNECTIONS CAN
CAUSE PERSONAL
INJURY OR DEATH
• REMOVE (IFC) COVER, CHECK LIGHTS
POWER LED ON
• CHECK LINE VOLTAGE POWER
• CHECK LOW VOLTAGE TRANSFORMER
REPLACE (IFC)
CHECK FOR 24 VAC FROM
CHECK THERMOSTAT
TERMINAL “W” TO “C” ON IFC
WIRING
• CHECK LIMITS, (CLOSED)
• CHECK WIRING
• CHECK PRESSURE SWITCH, (OPEN)
REPLACE SWITCH
IF THE PRESSURE SWITCH DOESN’T
CLOSE WITHIN 60 SEC. THE IDM WILL
STOP FOR 5 MIN. AND RETRY
• CHECK FOR 115VAC TO IDM MOTOR
REPLACE (IFC)
IF WIRING TO
IDM MOTOR IS OK
REPLACE IDM MOTOR
• CHECK FOR BLOCKED VENT
REPLACE SWITCH
• CHECK AIR PROVING SWITCH (CLOSED)
• CHECK WIRING TO IGNITER
REPLACE (IFC)
• CHECK FOR 115 VAC AT IGNITER,
IF WIRING TO
TERMINALS AND AT (IFC) TERMINALS
IGNITER IS OK
REPLACE IGNITER
SYSTEM WILL ATTEMPT TO LIGHT 4 TIMES. VOLTAGE IS PRESENT
AT THE VALVE FOR ONLY 9 SECONDS DURING EACH TRIAL FOR
IGNITION (SYSTEM WILL GO INTO A 1-HOUR LOCKOUT AFTER
4 TRIES).
➤
THE SEQUENCE WILL REPEAT AFTER A ONE HOUR
DELAY. IT WILL CONTINUE UNTIL IGNITION IS SUCCESSFUL OR THE
CALL FOR HEAT IS TERMINATED. THE BLOWER AND INDUCED DRAFT
BLOWER WILL RUN 180 SEC. IF THE FIRST AND SECOND IGNITION
TRIALS FAIL TO SENSE FLAME
• CHECK FOR 24 VAC ACROSS THE VALVE AND
VALVE TERMINALS ON THE (IFC)
• CHECK IGNITER POSITION
• CHECK FOR GAS FLOW TO AND FROM VALVE
REPLACE VALVE
REPLACE (IFC)
IF WIRING TO
VALVE IS OK
FLOW CHART CONTINUED ON NEXT PAGE
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
NO
NO
NO
NO
NO
!
MICROPROCESSOR STATUS LED ON
NOTE: “OK LED WILL FLASH TO INDICATE
TWINNING CIRCUIT FAULTS.
NO
Содержание RGRA SERIES
Страница 38: ...38 FIGURE 45 HONEYWELL NO S9201E2001 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION I400...
Страница 39: ...39 FIGURE 46 HONEYWELL NO S9201E2001 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I401...
Страница 40: ...40 FIGURE 47 UTEC NO 1012 920 1028 927 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION I398...
Страница 41: ...41 FIGURE 48 UTEC NO 1012 920 1028 927 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I398...
Страница 42: ...42 FIGURE 49 JOHNSON CONTROLS G961DAJ 2401 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION I399...
Страница 43: ...43 FIGURE 50 JOHNSON CONTROLS G961DAJ 2401 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I399...
Страница 62: ...62...
Страница 63: ...63...
Страница 64: ...64 Rheem Manufacturing Company Air Conditioning Division Fort Smith Arkansas CM 1197...