VENTILATION AND COMBUSTION AIR SUPPLY (CONT.)

 

ALL AIR FROM OUTDOORS 

Outdoor fresh air can be provided to a confined area either directly or by 
the use of vertical and horizontal ducts. The fresh air can be taken from the 
outdoors or from crawl or attic spaces that freely communicate with the 
outdoors. Attic or crawl spaces cannot be closed and must be properly 
ventilated to the outside.  
Ductwork must be of the same cross-sectional area as the free area of the 
opening to which they connect. The minimum dimension of rectangular air 
ducts cannot be less than 3 inches. 
The size of each of the two openings is determined by the method in which 
the air is to be provided. Refer to Table 1 to calculate the minimum free 
area for each opening. Figures 6, 7,  and 8 are typical examples of  each 
method.

 

CAUTION 

INLET AIR CANNOT BE TAKEN FROM AN ATTIC EQUIPPED WITH 
POWER VENTILATION.

 

LOUVERS AND GRILLES 

In calculating free area for ventilation and combustion air supply openings, 
consideration must be given to the blocking affect of protection louvers, 
grilles, and screens. These devices can reduce air flow which in turn may 
require larger openings to achieve the required minimum free area. Screens 
must not be smaller than 1/4 inch mesh. If the free area through a 
particular design of louver or grille is known, it should be used in 
calculating the specified free area of the opening. If the design and free 
area are not known, it can be assumed that most wood louvers will allow 
20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of 
free area. Louvers and grilles must be locked open or interconnected with 
the equipment so that they are opened automatically during equipment 
operation.  
Keep louvers and grilles clean and free of debris or other obstructions. 
 
 
 
 
 
 
 
 

 

TABLE 1

 

 

 

MINIMUM FREE AREA OF PERMANENT OPENINGS FOR 

VENTILATION AND COMBUSTION AIR SUPPLY - ALL AIR 

FROM OUTSIDE ONLY. 

OPENING SOURCE 

MINIMUM FREE AREA PER 

OPENING (SQ. IN.) 

REFERENCE 

DRAWING 

DIRECT TO 
OUTDOORS*  

1 SQUARE INCH PER 4000 BTUH 

FIGURE 6 

VERTICAL DUCTS 

1 SQUARE INCH PER 4000 BTUH 

FIGURE 7 

HORIZONTAL DUCTS 

1 SQUARE INCH PER 2000 BTUH 

FIGURE 8 

Example: A water heater with an input rate of 50,000 Btuh using horizontal 
ducts would require each opening to have a minimum free area of 25 square 
inches.   

Minimum Free Area  = 50,000 Btuh x 1 sq. in. / 2000 Btuh = 25 Sq Inches 

These openings may communicate directly with the outdoors through a 

ventilated attic, a ventilated crawl space, or through an outside wall. 

 

 

Содержание PVCG

Страница 1: ...FREE SOAP AND WATER SOLUTION OR OTHER APPROVED METHOD IF A LEAK CANNOT BE FOUND BUT IS STILL SUSPECTED FOLLOW THE STEPS UNDER WHAT TO DO IF YOU SMELL GAS AS OUTLINED ON THIS PAGE FAILURE TO OBSERVE T...

Страница 2: ...quipped for use with one type gas only Check the data plate near the gas control valve for the correct gas FAILURE TO USE THE CORRECT GAS CAN CAUSE PROBLEMS WHICH CAN RESULT IN DEATH SERIOUS BODILY IN...

Страница 3: ...IBLE FLOOR HOWEVER WHEN THIS WATER HEATER IS INSTALLED OVER CARPETING THE CARPETING MUST BE PROTECTED BY A METAL OR WOOD PANEL BENEATH THE WATER HEATER AND EXTENDING BEYOND THE FULL WIDTH AND DEPTH OF...

Страница 4: ...W DO NOT SMOKE OR HAVE ANY OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN REPAIR REPLACEMENT SERVICE AND CLEANING OF WATER HEATER PARTS MUST ONLY BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN IMPO...

Страница 5: ...and pressure relief valve or any labels or instruction materials applied to the water heater These labels must remain visible for reference by the user Do not remove these labels as they are a perman...

Страница 6: ...mit the water level to a maximum depth of 1 3 4 inches and be two inches wider than the heater and piped to an adequate drain Locate the water heater near a suitable inside drain Outside drains are su...

Страница 7: ...s BTUH inputs BTUH INPUT MIN SQ FEET WITH 8 CEILING TYPICAL ROOM SIZE WITH 8 CEILING 30 000 188 9 X 21 45 000 281 14 X 20 60 000 375 15 X 25 75 000 469 15 X 31 90 000 563 20 X 28 105 000 657 20 X 33 1...

Страница 8: ...ngs to achieve the required minimum free area Screens must not be smaller than 1 4 inch mesh If the free area through a particular design of louver or grille is known it should be used in calculating...

Страница 9: ...please note the following Use only Schedule 40 PVC CPVC or ABS DWV plastic pipe and fittings Maximum vent pipe length is 40 feet with three 90 degree long sweep elbows The minimum clearance from plast...

Страница 10: ...S TO ENTER THE HOME RESULTING IN CARBON MONOXIDE POISONING OR DEATH THROUGH THE WALL The vent terminal is a 45 degree elbow This is shipped with the water heater and must be used as the vent terminal...

Страница 11: ...es and Automatic Shut off Devices for Hot Water Supply Systems ANSI Z21 22 The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive...

Страница 12: ...Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts If solder connections are used solder the pipe to the adapter before attaching the adapter to the hot a...

Страница 13: ...relief valve on the water heater to discharge or weep due to expansion of the heated water A diaphragm type expansion tank suitable for potable water will normally eliminate this weeping condition Pl...

Страница 14: ...e 16 and install as follows 1 Install a readily accessible manual shutoff valve in the gas supply line as recommended by the local utility Know the location of this valve and how to turn off the gas t...

Страница 15: ...TANT Subjecting the gas valve thermostat to pressures exceeding 14 W C 1 2 psi 3 7 kPa may cause damage resulting in an extremely hazardous condition If the code requires the gas lines to be tested at...

Страница 16: ...Water heater not located near an air moving device VENTILATION AND COMBUSTION AIR SUPPLY Sufficient fresh air supply for proper water heater operation Fresh air not taken from areas that contain nega...

Страница 17: ...ve If using liquid propane gas shut off the gas at the L P tank outside of your residence 7 Use an outside phone and immediately call the gas company and the fire department Give your name and address...

Страница 18: ...re water heater LIGHTING INSTRUCTIONS 1 STOP It is imperative that you read all the safety warnings before lighting the pilot 2 Remove outer and inner doors 3 Turn the temperature dial counterclockwis...

Страница 19: ...rnings before lighting the pilot 2 Remove outer and inner doors 3 Set the thermostat to its lowest setting Rotate clockwise 4 Depress the gas control knob slightly and turn clockwise to OFF If the kno...

Страница 20: ...RLY IMPAIRED OR DISABLED MEMBERS AND ANYONE WITH TEMPERATURE SENSITIVE SKIN MAY REQUIRE A LOWER TEMPERATURE SETTING TO REDUCE THE RISK OF SCALD INJURY STACKING Stacking occurs when short draws of hot...

Страница 21: ...EEN USED FOR A LONG PERIOD OF TIME GENERALLY TWO WEEKS OR MORE HYDROGEN GAS IS EXTREMELY FLAMMABLE AND CAN IGNITE WHEN EXPOSED TO A SPARK OR FLAME TO PREVENT THE POSSIBILITY OF INJURY UNDER THESE COND...

Страница 22: ...on at the thermostat Figure 22 Note that L P gas systems use reverse left handed threads on the manifold tube 6 Grasp the manifold tube and push down slightly to free the manifold pilot tube bleed tub...

Страница 23: ...ontrol valve thermostat repeat the previous procedure in reverse order Be sure to use Approved Teflon Tape or Pipe Joint Compound on the gas piping connections and fitting on the back of gas valve tha...

Страница 24: ...ower to outlet 5 Replace control cable 6 Temporarily jumper across the two terminal on the switch If the blower operates replace the switch 7 Check voltages Replace if defective 8 Replace blower BLOWE...

Страница 25: ...h correct orifice 4 Replace thermostat 5 Turn temperature dial to lower setting 6 Install adequate heater 7 Correct piping dip tube must be in cold inlet 8 Advise customer 9 Clean flue locate source a...

Страница 26: ...he proper gas type Natural gas thermostat will be marked FOR NATURAL GAS ONLY Propane gas thermostats will be marked FOR L P GAS ONLY REPAIR PARTS LIST ITEM NO PARTS DESCRIPTION 1 BLOWER MOTOR ASSEMBL...

Страница 27: ...27 REPAIR PARTS CONT PARTS ILLUSTRATION...

Отзывы: