15 

 

GAS SUPPLY AND PIPING (CONT.) 

2.  Install a drip leg (if not already incorporated as part of the water 

heater) as shown. The drip leg must be no less than 3 inches long for 
the accumulation of dirt, foreign material and water droplets. 

3.  Install a ground joint union between the gas valve/thermostat and the 

manual shutoff valve. This is to allow easy removal of the gas valve/ 
thermostat. 

 

IMPORTANT

: Refer to the "Gas Pressure Testing" section on this page before 

pressure testing the gas lines. 

4. 

Turn the gas supply on and check for leaks. Use a chloride-free soap 
and water solution (bubbles forming indicate a leak) or other approved 
method. 

Do not use an open flame. ALL LEAKS MUST BE FIXED 

IMMEDIATELY.

 

DANGER 

DO NOT USE AN OPEN FLAME OR ANY KIND OF SPARK TO CHECK 

GAS PIPING FOR LEAKS. IF LEAKING GAS IS PRESENT, AN 

EXPLOSION OR FIRE MAY RESULT CAUSING PROPERTY DAMAGE, 

PERSONAL INJURY OR DEATH. 

IMPORTANT

: This water heater’s gas controls and its gas connection 

must be leak tested before placing the appliance in operation.

IMPORTANT: 

Air may be present in the gas lines and could prevent the 

pilot from lighting on initial start-up. The gas lines should be purged of air 
by a qualified service technician after installation of the gas piping system. 
The gas supply pressure must not exceed the maximum supply pressure as 
stated on the water heater’s data plate. The minimum supply pressure is 
for the purpose of input adjustment

 

GAS PRESSURE TESTING

 

IMPORTANT: Subjecting the gas valve/thermostat to pressures 
exceeding 14” W.C. (1/2 psi, 3.7 kPa) may cause damage resulting in 
an extremely hazardous condition.

  

• 

If the code requires the gas lines to be tested at a pressure exceeding 
14” W.C., the water heater and its manual shutoff valve must be 

disconnected 

from the gas supply piping system and the line 

capped.  

• 

If the gas lines are to be tested at a  pressure less than 14” W.C. the 
water heater must be 

isolated 

from the gas supply piping system by 

closing its manual shutoff valve. 

 

A U.L. RECOGNIZED FUEL GAS AND CO DETECTOR(S) ARE 
RECOMMENDED IN ALL APPLICATIONS AND THEIR INSTALLATION 
SHOULD BE IN ACCORDANCE WITH THE MANUFACTURER’S 
RECOMMENDATIONS AND/OR LOCAL LAWS, RULES, REGULATIONS, 
OR CUSTOMS. 
 
 

ELECTRICAL CONNECTIONS 

WARNING

 

ELECTRICAL WIRING CONNECTIONS MUST ONLY BE 
PERFORMED BY A QUALIFIED ELECTRICIAN.

  

 

The electrical rating of this water heater is 115 volts and less than 
5 amps. All electrical wiring and connections must be properly 
grounded in accordance with the local codes or in the absence of 
local codes, with the National Electric Code ANSI/NFPA 70 - Latest 
Edition. In Canada, all electrical connections must be in accordance 
with the Canadian Electrical Code Part 1-022.1. 

The electrical service to the water heater must be equipped 
with the proper overload fuse or breaker protection for the 
specified electrical rating.

 

The power vent module is supplied with a flexible, grounded power 
cord and connects to a standard three wire, grounding type 
receptacle. 

Do not use an extension cord.

 

WARNING 

THIS WATER HEATER MUST BE ELECTRICALLY GROUNDED 
IN ACCORDANCE WITH THE PREVAILING ELECTRICAL CODE.

  

 

 

Содержание PVCG

Страница 1: ...FREE SOAP AND WATER SOLUTION OR OTHER APPROVED METHOD IF A LEAK CANNOT BE FOUND BUT IS STILL SUSPECTED FOLLOW THE STEPS UNDER WHAT TO DO IF YOU SMELL GAS AS OUTLINED ON THIS PAGE FAILURE TO OBSERVE T...

Страница 2: ...quipped for use with one type gas only Check the data plate near the gas control valve for the correct gas FAILURE TO USE THE CORRECT GAS CAN CAUSE PROBLEMS WHICH CAN RESULT IN DEATH SERIOUS BODILY IN...

Страница 3: ...IBLE FLOOR HOWEVER WHEN THIS WATER HEATER IS INSTALLED OVER CARPETING THE CARPETING MUST BE PROTECTED BY A METAL OR WOOD PANEL BENEATH THE WATER HEATER AND EXTENDING BEYOND THE FULL WIDTH AND DEPTH OF...

Страница 4: ...W DO NOT SMOKE OR HAVE ANY OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN REPAIR REPLACEMENT SERVICE AND CLEANING OF WATER HEATER PARTS MUST ONLY BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN IMPO...

Страница 5: ...and pressure relief valve or any labels or instruction materials applied to the water heater These labels must remain visible for reference by the user Do not remove these labels as they are a perman...

Страница 6: ...mit the water level to a maximum depth of 1 3 4 inches and be two inches wider than the heater and piped to an adequate drain Locate the water heater near a suitable inside drain Outside drains are su...

Страница 7: ...s BTUH inputs BTUH INPUT MIN SQ FEET WITH 8 CEILING TYPICAL ROOM SIZE WITH 8 CEILING 30 000 188 9 X 21 45 000 281 14 X 20 60 000 375 15 X 25 75 000 469 15 X 31 90 000 563 20 X 28 105 000 657 20 X 33 1...

Страница 8: ...ngs to achieve the required minimum free area Screens must not be smaller than 1 4 inch mesh If the free area through a particular design of louver or grille is known it should be used in calculating...

Страница 9: ...please note the following Use only Schedule 40 PVC CPVC or ABS DWV plastic pipe and fittings Maximum vent pipe length is 40 feet with three 90 degree long sweep elbows The minimum clearance from plast...

Страница 10: ...S TO ENTER THE HOME RESULTING IN CARBON MONOXIDE POISONING OR DEATH THROUGH THE WALL The vent terminal is a 45 degree elbow This is shipped with the water heater and must be used as the vent terminal...

Страница 11: ...es and Automatic Shut off Devices for Hot Water Supply Systems ANSI Z21 22 The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive...

Страница 12: ...Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts If solder connections are used solder the pipe to the adapter before attaching the adapter to the hot a...

Страница 13: ...relief valve on the water heater to discharge or weep due to expansion of the heated water A diaphragm type expansion tank suitable for potable water will normally eliminate this weeping condition Pl...

Страница 14: ...e 16 and install as follows 1 Install a readily accessible manual shutoff valve in the gas supply line as recommended by the local utility Know the location of this valve and how to turn off the gas t...

Страница 15: ...TANT Subjecting the gas valve thermostat to pressures exceeding 14 W C 1 2 psi 3 7 kPa may cause damage resulting in an extremely hazardous condition If the code requires the gas lines to be tested at...

Страница 16: ...Water heater not located near an air moving device VENTILATION AND COMBUSTION AIR SUPPLY Sufficient fresh air supply for proper water heater operation Fresh air not taken from areas that contain nega...

Страница 17: ...ve If using liquid propane gas shut off the gas at the L P tank outside of your residence 7 Use an outside phone and immediately call the gas company and the fire department Give your name and address...

Страница 18: ...re water heater LIGHTING INSTRUCTIONS 1 STOP It is imperative that you read all the safety warnings before lighting the pilot 2 Remove outer and inner doors 3 Turn the temperature dial counterclockwis...

Страница 19: ...rnings before lighting the pilot 2 Remove outer and inner doors 3 Set the thermostat to its lowest setting Rotate clockwise 4 Depress the gas control knob slightly and turn clockwise to OFF If the kno...

Страница 20: ...RLY IMPAIRED OR DISABLED MEMBERS AND ANYONE WITH TEMPERATURE SENSITIVE SKIN MAY REQUIRE A LOWER TEMPERATURE SETTING TO REDUCE THE RISK OF SCALD INJURY STACKING Stacking occurs when short draws of hot...

Страница 21: ...EEN USED FOR A LONG PERIOD OF TIME GENERALLY TWO WEEKS OR MORE HYDROGEN GAS IS EXTREMELY FLAMMABLE AND CAN IGNITE WHEN EXPOSED TO A SPARK OR FLAME TO PREVENT THE POSSIBILITY OF INJURY UNDER THESE COND...

Страница 22: ...on at the thermostat Figure 22 Note that L P gas systems use reverse left handed threads on the manifold tube 6 Grasp the manifold tube and push down slightly to free the manifold pilot tube bleed tub...

Страница 23: ...ontrol valve thermostat repeat the previous procedure in reverse order Be sure to use Approved Teflon Tape or Pipe Joint Compound on the gas piping connections and fitting on the back of gas valve tha...

Страница 24: ...ower to outlet 5 Replace control cable 6 Temporarily jumper across the two terminal on the switch If the blower operates replace the switch 7 Check voltages Replace if defective 8 Replace blower BLOWE...

Страница 25: ...h correct orifice 4 Replace thermostat 5 Turn temperature dial to lower setting 6 Install adequate heater 7 Correct piping dip tube must be in cold inlet 8 Advise customer 9 Clean flue locate source a...

Страница 26: ...he proper gas type Natural gas thermostat will be marked FOR NATURAL GAS ONLY Propane gas thermostats will be marked FOR L P GAS ONLY REPAIR PARTS LIST ITEM NO PARTS DESCRIPTION 1 BLOWER MOTOR ASSEMBL...

Страница 27: ...27 REPAIR PARTS CONT PARTS ILLUSTRATION...

Отзывы: