
14
GAS SUPPLY AND PIPING
GENERAL INFORMATION
DANGER
THIS WATER HEATER IS EQUIPPED FOR ONE TYPE OF GAS ONLY.
DO NOT USE THIS WATER HEATER WITH ANY GAS OTHER THAN
THE ONE LISTED ON THE DATA PLATE LOCATED NEAR THE GAS
CONTROL. FAILURE TO USE THE CORRECT GAS CAN RESULT IN
PROPERTY DAMAGE, BODILY INJURY, OR DEATH.
This water heater must only be connected to gas supplied by a
commercial utility.
GAS PIPING
Install the gas piping according to all local and state codes or with the
”National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-Latest Edition.
Do not use copper and brass piping and fittings (except tin-lined copper
tubing) if the gas contains more than 0.3 grains of hydrogen sulfide per
100 standard cubit feet of gas. Contact your local gas utility company if
you are unsure about this.
Table 2 and or Table 3 are provided as a sizing reference for commonly
used gas pipe materials. Consult the “National Fuel and Gas Code” for the
recommended gas pipe size of other materials.
DANGER
THE GAS LINE MUST BE OF ADEQUATE SIZE SO AS TO PREVENT
UNDUE PRESSURE DROP AND NEVER SMALLER THAN THE PIPE
SIZE TO THE GAS VALVE ON THE WATER HEATER. FAILURE TO
PROPERLY SIZE THE GAS LINE CAN CAUSE A FIRE OR EXPLOSION
RESULTING IN PROPERTY DAMAGE, BODILY INJURY OR DEATH.
When installing gas piping, use a pipe joint compound that is resistant
to the action of propane (LPG) gases. Apply the compound to male
threads only. Do not apply the compound to the first 2 threads. Do not
use TEFLON tape.
Do not use pipe joint compound or TEFLON tape on the union
connection.
When making pipe connections, use a back-up wrench to prevent any
twisting of the control valve/thermostat assembly. Do not use
excessive force when tightening the pipe joint at the thermostat inlet.
Refer to Figure 16 and install as follows:
1.
Install a readily accessible manual shutoff valve in the gas
supply line as recommended by the local utility. Know the
location of this valve and how to turn off the gas to this unit.
TABLE 3
LP GAS PIPE CAPACITY TABLE
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column pressure). Based on a
Pressure Drop of 0.5 Inch Water Column.
Nominal iron
pipe size, in.
Length of Pipe, Feet
10 20 30 40 50 60 70 80 90 100 125 150
1/2
275 189 152 129 114 103 96 89 83 78 69 63
3/4
567 393 315 267 237 217 196 185 173 162 146 132
1
1071 732 590 504 448 409 378 346 322 307 275 252
1-1/4
2205 1496 1212 1039 913 834 771 724 677 630 567 511
Example: Input BTU requirement of the water heater, 100,000 BTUH Total pipe length, 80 feet = 3/4" IPS required.
TABLE 2
NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in.
and specific gravity of 0.60 (natural gas).
Nominal
Iron Pipe
Size, Inches
Length of Pipe, Feet
10 20 30 40 50 60 70 80 90 100
1/2 132 92 73 63 56 50 46 43 40 38
3/4
278 190 152 130 115 105 96 90 84 79
1
520 350 285 245 215 195 180 170 160 150
1-1/4 1050 730 590 500 440 400 370 350 320 305
1-1/2 1600 1100 890 760 670 610 560 530 490 460
After the length of pipe has been determined, select the pipe size which will provide the minimum cubit feet per
hour required for the gas input rating of the water heater. By formula:
Cu. Ft. Per Hr. Required =
Gas Input of Water Heater (BTU/HR)
Heating Value of Gas (BTU/FT³)
The gas input of the water heater is marked on the water heater data plate. The heating value of the gas
(BTU/FT3) may be determined by consulting the local natural gas utility.
WARNING
CONTAMINANTS IN THE GAS PIPING
MAY FOUL THE THERMOSTAT CAUSING
A MALFUNCTION, FIRE, OR EXPLOSION.
BE SURE ALL GAS PIPING IS CLEAN AND
CLEAR ON THE INSIDE BEFORE
ATTACHING THE GAS LINE.
Содержание PVCG
Страница 27: ...27 REPAIR PARTS CONT PARTS ILLUSTRATION...