Backup heating mode and series of red flashes 

During  the  backup  heating  mode  by  the  booster  heating  unit,  caused  by  either  the  thermal  cut  out 
activating or a heat pump fault condition, the red LED will emit a series of flashes. 

At  the  completion  of  a  heating  cycle  by  the  booster  heating  unit  in  the  backup  heating  mode  and  the 
water temperature reaches 70°C, the thermostat controlling the booster heating unit opens circuit cutting 
power to the heat pump causing the red LED to go out. The fault mode is recorded to the heat pump 
controller‟s  memory.  The  fault  condition  which  led  to  the  red  LED  flashing  may  be  cleared  when  the 
backup heating cycle has completed. 

Both LEDs  will remain off for an extended  period of time until the  water temperature  in the top of the 
water heater drops to below 62°C and the thermostat closes circuit reinstating power to the heat pump. 

The red LED will recommence to flash the fault mode for thirty (30) seconds and then extinguish. If the 
red LED then recommences to flash, the fault condition which led to the red LED flashing may not have 
cleared and there may be a problem with the heat pump. Count the number of red flashes and phone 
Rheem Service or their nearest Accredited Service Agent to arrange for an inspection. 

At the end of the thirty (30) second period, the green LED will commence to glow or flash. 

The green LED will glow (standby mode – water is hot) if the water temperature in the lower part of the 
water heater is 50°C or more. 

The green LED will flash if the water temperature in the lower part of the water heater is less than 50°C. 

Note:

  If  the  green  LED  is  glowing,  then  to  check  whether  there  may  be  problem  with  the  heat  pump, 

open a hot tap and allow to run for ten to fifteen minutes. This will draw cold water into the lower part of 
the  water  heater  and  the  green  LED  will  commence  to  flash.  Close  the  hot  tap  when  the  green  LED 
commences to flash. 

The heat pump will commence to operate when the green LED is flashing and at least 45 minutes has 
elapsed after power is reinstated to the heat pump, i.e. 45 minutes after the red LED flashed the fault 
mode for thirty (30) seconds and then extinguished. 

If the heat pump stops operating and the red LED recommences to flash, the fault condition which led to 
the red LED flashing may not have cleared and there may be a problem with the heat pump. Count the 
number of red flashes and phone Rheem Service or their nearest Accredited Service Agent to arrange 
for an inspection. 

Note:

 If the ambient air temperature is outside of the heat pump‟s operating range, the water heater may 

switch to the booster heating unit (long green flash) to heat the water in booster heating mode. 

The fault mode is cleared  from the  heat pump controller‟s memory after the  water heater successfully 
completes a full heat up cycle using the heat pump. 

 

Green LED is off 

There may be a fault condition with the heat pump if: 

 

there is power available at the water heater and the green LED is off, and  

 

the  water  heater 

has not

  operated  outside  of  the  heat  pump‟s  operating  range  –  refer  to 

“Heat 

pump operating range”

 on page 15. 

Before phoning to arrange a service inspection: 

 

inspect  the isolating switch marked “HOT WATER” or “WATER HEATER” at  the switchboard  and 
the isolating switch (if one is installed) at the water heater and ensure they are turned on 

 

check the fuse marked “HOT WATER” or “WATER HEATER” at the switchboard 

 

if a timer has been installed, check the time settings 

 

check the power supply tariff the water heater is connected to confirm power should be available to 
the water heater. 

Refer also to 

“Thermal cut out activated”

 on page 15 and to 

“Heat pump fault condition”

 on page 15. 

If  the  green  LED  is  off  and  one  of  these  conditions  is  not  the  cause,  phone  Rheem  Service  or  their 
nearest Accredited Service Agent to arrange for an inspection. 

Содержание MPi 554 Series

Страница 1: ...water heater must be installed and serviced by a qualified person Please leave this guide with the householder Owner s Guide and Installation Instructions Air Sourced Heat Pump Water Heater MPi 554 Se...

Страница 2: ...Rheem Australia Pty Ltd TRADE MARKS Registered trademark of Rheem Australia Pty Ltd Trademark of Rheem Australia Pty Ltd Note Every care has been taken to ensure accuracy in preparation of this public...

Страница 3: ...nded for the installer but may be of interest About Your Water Heater 4 Regular Care 10 Water Supplies 12 Save A Service Call 14 Installation 19 Heat Pump And Tank Assembly 24 Connections Plumbing 34...

Страница 4: ...tlet grille back to atmosphere and the heated water is circulated back into the storage tank This process continues while heating is required until the water in the storage tank reaches a temperature...

Страница 5: ...jury A RheemPlus water heater will not deliver temperatures exceeding 50 C in accordance with AS 3498 The risk of scald injury will be reduced TEMPERATURE ADJUSTMENT The thermostats controlling the he...

Страница 6: ...ered with or if the installation is not in accordance with these instructions OPERATING MODE MONITOR An operating mode monitor is located on the front of the heat pump module and houses a green and a...

Страница 7: ...in the top of the water heater drops to below 62 C and the thermostat closes circuit reinstating power to the heat pump when the red LED will emit a solid glow for three 3 seconds and then extinguish...

Страница 8: ...the power supply is switched on The heat pump will only operate when power is available at the water heater the water in the storage tank requires heating the heat pump compressor is cool and the amb...

Страница 9: ...ctorian Customers from the Victorian Plumbing Industry Commission This water heater must be installed by a licensed person as required by the Victorian Building Act 1993 Only a licensed person will gi...

Страница 10: ...cted on the water heater Warning Servicing of a water heater must only be carried out by a qualified person Phone Rheem Service or their nearest Accredited Service Agent Note The five year service and...

Страница 11: ...intervals not exceeding 5 years or more frequently in areas where there is a high incidence of water deposits refer to Water Supplies on page 12 TEMPERATURE LIMITING VALVE A RheemPlus water heater is...

Страница 12: ...tent in the water is less than 2500 mg L and when the correct colour coded anode is used If an incorrect colour coded anode is used in the water heater any resultant faults will not be covered by the...

Страница 13: ...ter In a corrosive water supply the water can attack copper parts and cause them to fail Where the saturation index exceeds 0 40 the water is very scaling and the Rheem warranty does not apply to the...

Страница 14: ...sage Heat pump fault Has the heat pump developed a fault and the red LED is flashing The heat pump will not operate and the water heater will switch to backup heating mode using the booster heating un...

Страница 15: ...e water heater is 50 C or more The green LED will flash if the water temperature in the lower part of the water heater is less than 50 C If at least 45 minutes has elapsed after power is reinstated to...

Страница 16: ...r heater and the green LED will commence to flash Close the hot tap when the green LED commences to flash The heat pump will commence to operate when the green LED is flashing and at least 45 minutes...

Страница 17: ...e mains water pressure sometimes rises above the designed pressure of the water heater Ask your installing plumber to fit a pressure limiting valve Warning Never replace the relief valve with one of a...

Страница 18: ...ter on page 14 Is there a leaking hot water pipe dripping hot water tap etc Even a small leak will waste a surprising quantity of hot water and energy Replace faulty tap washers and have your plumber...

Страница 19: ...e inoperable for any reason We recommend you provide advice to the system owner about their needs and building backup redundancy into the hot water supply system The 554 325 model water heater is reco...

Страница 20: ...e water heater is made of corrosion resistant material and it may be placed directly in contact with the supporting surface It is not necessary to allow for free air circulation under the base of the...

Страница 21: ...be necessary to fit an additional temperature limiting device to meet the requirements of AS NZS 3500 4 and or regulatory and local authorities CIRCULATED HOT WATER FLOW AND RETURN SYSTEM A RheemPlus...

Страница 22: ...a maximum length of 13 mm Should pre drilling be required extreme caution must be observed when penetrating the jacket of the water heater Note If the cylinder is damaged as a result of attaching pip...

Страница 23: ...age capacity litres 325 410 Rated heat pump power input 800 watts Boost capacity1 8 kW litres 100 Booster heating unit rating 1800 2400 3600 watts 2 4 kW 3 6 kW litres 180 200 Refrigerant type R134a D...

Страница 24: ...Good lifting practice should be followed There are two flexible hoses provided inside the heat pump module The flexible hoses are to be withdrawn from the module and fixed to the two water fittings o...

Страница 25: ...escription Quantity 080199 Kit Installation Heat Pump Module Integrated 126558 Installation instructions heat pump module integrated 1 052158 Saddle clamp 20 mm Clipsal 261 20 1 080021 Screw phillips...

Страница 26: ...ge tank The storage tank must also be positioned such that when the heat pump module is in position there is a clearance of at least 300 mm perpendicular from both the front air inlet louvres and the...

Страница 27: ...of the foam tape are to line up with the two vertical slots in the jacket The mid point of the tape lengthways is to line up over the join between the jacket of the storage tank and the jacket bottom...

Страница 28: ...pump housing Step 8 apply cover strip to heat pump housing 9 Heat Pump Module Cover Remove the two screws securing the module cover to the heat pump module Remove the module cover from the heat pump...

Страница 29: ...is not required Position the hose such that when the heat pump module is moved and secured to the tank it does not kink Step 13 attach flexible hose with blue collar to inlet 14 Hot Hose Connection At...

Страница 30: ...the heat pump module against the tank Engage the tab at the bottom of the heat pump module on the wall side of the module into the slot in the tank Align the holes in the side of the heat pump module...

Страница 31: ...ND TANK ASSEMBLY 31 20 Fixing Bolts Screw in the three fixing bolts to connect the front side of the heat pump module to the storage tank Step 20 screw in fixing bolts to connect heat pump module to s...

Страница 32: ...CABLE PLUG POWER CABLE PLUG Steps 21 and 22 connect power cable and tank sensor cable 23 Positioning of Water Heater Complete final positioning of the water heater Ensure the heat pump module is firm...

Страница 33: ...ect wiring refit electrical front cover to terminal block 28 Mains Power Connection Connect the mains power supply wiring to the terminal block and earth connection inside of the electrical cover Secu...

Страница 34: ...t nearby They will be pushed into the correct position as the fitting is screwed in PIPE SIZES To achieve true mains pressure operation the cold water line to the water heater should be the same size...

Страница 35: ...can discharge into a tundish Subject to local regulatory authority approval the drain lines from the temperature pressure relief valve and expansion control valve from an individual water heater may...

Страница 36: ...isolating switch installed at the switchboard A secondary isolating switch may be installed within reach of the water heater The 554 325 model water heater is recommended for connection to a minimum...

Страница 37: ...GREEN YELLOW RED BLUE BLACK GREEN YELLOW GREEN YELLOW M F M F M F M F M F 1 3 4 2 1 1 4 3 4 2 1 2 3 3 2 WIRING DIAGRAM HEAT PUMP 554325 554410 WITH ST THERMOSTAT MAIN POWER CONNECTION BRACKET PUMP FA...

Страница 38: ...e booster heating unit When the heat pump is operating the system will switch to the booster heating unit if the detected ambient air temperature is outside the operating temperature range of between...

Страница 39: ...meter measure the temperature of the water from the tap until the temperature stops increasing If the water temperature is below 50 C the maximum outlet temperature of the water heater can be adjusted...

Страница 40: ...over temperature possible circulator fault 2 x red Heating unit off compressor fault condition 3 x red Heating unit on compressor cooling fault condition 4 x red Heating unit on tank thermistor fault...

Страница 41: ...s Guide or the red LED is flashing the red LED may emit up to nine flashes in each series of flashes The fault condition which led to the red LED flashing may be cleared after the backup heating cycle...

Страница 42: ...page 38 Close all hot water taps Operate the relief valve release lever do not let the lever snap back or you will damage the valve seat Operating the lever will release the pressure in the water heat...

Страница 43: ...d site shall be the owner s responsibility 2 5 Where the water heater is installed in a position that does not allow safe or ready access the cost of that access including the cost of additional mater...

Страница 44: ...O MAKE A CLAIM UNDER THIS WARRANTY 4 1 To be entitled to make a claim under this warranty you need to a Be the owner of the water heater or have consent of the owner to act on their behalf b Contact R...

Отзывы: