P a g e
|
22
circuit failure
as necessary.
“E06”
displayed
Ambient sensor cable
open or short circuit
failure
Check ambient sensor cable; make sure it is plugged
in and lead is not severed. Repair or replace sensor
cable as necessary.
“E07”
displayed
Loose connection
between the remote
control and main
board.
Repair/replace remote connection cable.
“E09”
displayed
Water volume is not
enough and water
temperature is too
high.
Ensure tank is full of water; decrease the water
temperature setting.
Refrigerant overcharge Refer to refrigeration technician.
Non-condensing gas in
system
Refer to refrigeration technician.
TX valve setting
Refer to refrigeration technician.
“E10”
displayed
Ambient temperature
is too low and the inlet
water temperature is
too low
Auxiliary heating required.
Lack of refrigerant
Refer to refrigeration technician. Check pipe work, TX
valve.
Refrigerant blockage
Refer to refrigeration technician. Clean pipe work and
replace dryer/filter.
TX valve setting
Refer to refrigeration technician.
Heavy dust/debris
build-up on
evaporator.
Clean the evaporator fins.
Using Hot Water
Failure
Possible reason
Solution
No hot water or
insufficient hot water
No power supply
No power supply, connect power supply.
Over-temperature device activated; determine cause
and manually reset.
Excessive draw of hot
water
Wait for heater to reheat tank.
Water heater
component failure
Contact distributor to arrange repair.
TPR valve draining
It is normal for 3-5% of
tank volume to be
discharged everyday
Normal operation.