Rheem 3805 Series Скачать руководство пользователя страница 23

 

 

P a g e

 | 

21

 

Troubleshooting 

Error Code: 

Code 

Failure type 

Reset method 

E01 

Open or short circuit - water temperature sensor 

Auto 

E02 

Open or short circuit - outlet opening sensor cable 

Auto 

E03 

Open or short circuit - Evaporator sensor cable 

Auto 

E04 

Outlet opening over-temperature protection 

(≥95

o

C) 

Auto 

E05 

Outlet opening over-temperature protection 

(≥105

o

C) 

Reset power 

E06 

Open or short circuit - ambient temperature sensor cable 

Auto 

E07 

Data wire connection 

Auto 

E08 

Sub-controller and main board to be separated 

Reset power or press 

SET

 

on Mainboard 

E09 

High pressure protection 

Auto 

E10 

Low pressure protection 

Auto 

Auto

 means the heater will automatically begin to work once the failure is resolved;   

Reset power means technician must isolate power supply and restore once the failure is fixed to 
reset error code. 
 

Failure and Solution   

Control Panel 

Failure 

Possible reason 

Solution 

Remote display is blank; 
buttons do not work. 

No power available 

Check power supply. 
Over-temperature device activated; determine cause 
and manually reset. 

Loose connection of 
remote wires 

Repair/replace the remote connecting wires. 

Remote display is blank; 
buttons do work   

Dusty or damp 
conditions at remote 
wiring.   

Clean area and use air dryer to eliminate presence of 
moisture. 

“E01”

 displayed 

Water temperature 
sensor cable open or 
short circuit 

Check water temperature sensor cable; make sure it 
is plugged in and lead is not severed. Repair or 
replace sensor cable as necessary. 

“E02”

displayed 

Outlet opening 
temperature sensor 
cable open or short 
circuit 

Check outlet opening temperature sensor cable; 
make sure it is plugged in and lead is not severed. 
Repair or replace sensor cable as necessary. 

“E03”

 displayed 

Evaporator sensor 
cable open or short 

Check evaporator sensor cable; make sure it is 
plugged in and lead is not severed. Repair or replace 

Содержание 3805 Series

Страница 1: ...Guide and Installation Instructions Rheem Heat Pump Water Heater 3805 Series 270 340 Models This water heater must be installed and serviced by a qualified person Please leave this guide with the hous...

Страница 2: ......

Страница 3: ...ed for use in a single family domestic dwelling for the purpose of heating potable water The main features of the water heater include automatic operation whilst power and water supplies available sim...

Страница 4: ...ECV 12 RELIEF VALVE DRAIN 12 CONDENSATION DRAIN 13 REDUCING HEAT LOSSES 13 WATER SUPPLIED BY STORAGE TANK ON THE ROOF 13 ELECTRICAL CONNECTION 14 OPERATION AND USAGE 15 TO FILL AND TURN ON THE WATER H...

Страница 5: ...PANEL 21 USING HOT WATER 22 WIRING DIAGRAM 24 WARRANTY 25 1 HEAT PUMP WATER HEATER MODEL ERROR BOOKMARK NOT DEFINED 2 TERMS OF THE SOLAHART WARRANTY AND EXCLUSIONS TO IT ERROR BOOKMARK NOT DEFINED 3 W...

Страница 6: ...an approved temperature limiting device be fitted This will ensure the water temperature does not exceed 50 C and the risk of scald injury will be reduced Do not use aerosols stain removers and househ...

Страница 7: ...operation of the equipment isolate power supply promptly and contact the Service Department Do not attempt to repair the unit Operate the easing lever on the temperature pressure relief valve at least...

Страница 8: ...ter temperature setting o C 30 65 Preset 55 Suitable ambient temperature o C 7 43 Refrigerant quantity R134a 1 35 Kg Water Side Heat exchanger type Copper Pipe coiled outside the tank Tank capacity L...

Страница 9: ...P a g e 7...

Страница 10: ...P a g e 8 Dimensions MODEL A mm B mm RHP270 3805 1151 1815 RHP340 3805 1461 2125...

Страница 11: ...of the water heater Make sure the temperature pressure relief valve lever is accessible and the top and front cover air inlet and outlet louvres system controls and thermostat can be removed for servi...

Страница 12: ...n contact with potable water Connection Sizes Cold water inlet RP 20 English system Sealed cylindrical inner thread Hot water outlet RP 20 English system Sealed cylindrical inner thread TPR valve RP 2...

Страница 13: ...n union must always be provided at the cold water inlet and hot water outlet on the water heater to allow for disconnection of the water heater Hot Water Delivery This water heater can deliver water a...

Страница 14: ...f valve and expansion control valve if one is installed to carry the discharge clear of the water heater Connect the drain lines to the valves using disconnection unions The drain line from the valve...

Страница 15: ...e pipe work from the condensate drain should be as short as possible and fall all the way from the water heater with no restrictions It should have no more than three right angle bends in it The outle...

Страница 16: ...o a 220V AC 10 50 Hz mains power supply The water heater must be on its own circuit with an isolating switch installed at the switchboard A secondary isolating switch may be installed within reach of...

Страница 17: ...taps Close each tap as water flows freely from it Check the pipe work for leaks Switch on the electrical supply at the isolating switch to the water heater Program the remote controller Remote Contro...

Страница 18: ...F Press the ON OFF button to switch on off the system When the system is switched off the remote control will display the time only b Temperature Setting Switch on the system factory preset temperatur...

Страница 19: ...rature appears iii Press OK again Pxx Temperature of Evaporator Coil appears f System Component Checks i During the time delay phase at start up or when system is switched off press and hold the up bu...

Страница 20: ...Water Quality Poor water quality will have a detrimental effect on the water heater and its operation and or life expectancy If you are unsure of your water quality information can be obtained from y...

Страница 21: ...parts and cause them to fail Where the saturation index exceeds 0 40 the water is very scaling and warranty does not apply to the water heater In a scaling water supply the calcium carbonate is depos...

Страница 22: ...s not replaced at this time it should be inspected regularly from this time Check the electric heating unit for excessive calcium build up or corrosion and replace if necessary Check and inspect the h...

Страница 23: ...Failure and Solution Control Panel Failure Possible reason Solution Remote display is blank buttons do not work No power available Check power supply Over temperature device activated determine cause...

Страница 24: ...cian E10 displayed Ambient temperature is too low and the inlet water temperature is too low Auxiliary heating required Lack of refrigerant Refer to refrigeration technician Check pipe work TX valve R...

Страница 25: ...hand lever to discharge water repeat Replace T PR if necessary High water supply pressure Ask plumber to install pressure reduction valve Noise inside water heater or pipes It is normal for slight noi...

Страница 26: ...P a g e 24 Wiring Diagram...

Страница 27: ...nents are covered The period in which the fault must appear in order to be covered What coverage you receive All components Year 1 Replacement of the faulty component at exwork price ONLY The cylinder...

Страница 28: ......